background image

13

Output Module in Series Connection

Output Module in Parallel Connection

NOTE:

Recommended torque setting for output terminal screws is 6kgf-cm

Recommended torque setting for output terminal screws is 6kgf-cm

 Total output current should not exceed the current rating of the lowest rated module that is connected in series.

 Difference of rise time in each module may lead to step/ stair shape output voltage waveform during turn on.

 The series voltage should be less than 60V in order to satisfy IEC60950-1 SELV (Safety Extra Low Voltage) requirement.

.

 Series connection accessory: FAS-005

STEP 6:

 Connect AC power to the NMP unit and test each module to ensure proper operation.The green LED indicator on module should light up.

 Measure the output voltage of each module and make sure it is within the specified output voltage tolerance range. If the load requires 

 a different voltage that is within the specified voltage adjustment range, adjust the voltage by turning the SVR as shown below. Turning 

 the SVR clockwise will increase the voltage, and turning the SVR counter-clockwise will decrease the voltage. Once the output voltages 

 of all modules have been tested and adjusted to the desired values, the output configuration is done.









 



















 























 

  



,











10





Higher  output  voltage  can  be  acquired  by  connecting  adjacent  output  modules  in  series.  Example:  if  a  load  requires  60V  to 
power, then two NMS-240-24 can be connected in series for this requirement. First, follow assembly steps STEP 1-STEP 6 and 
install  the  two  NMS-240-24  modules  in  slot  1  and  slot  2.  Second,  adjust  the  output  voltage  of  each  module  to  30V  via  SVR. 
Finally, use the FAS-005 series connection accessory to connect the -V terminal of slot 1 to the +V terminal of slot 2. Measure 
and verify that the voltage V terminal of slot 1 and - V terminal of slot 2 is 60V.

Higher output current can be acquired by connecting adjacent output moduels in prallel. Example: connecting three NMS-240-
12 in parallel. First, follow assembly steps STEP 1-STEP 6 and install the three NMS-240-12 modules in slot 1, slot 2, and slot 
3. Second, measure and adjust the voltage of each modules to be within 0.2V. Finally, use two 3-unit parallel accessory (FAP-
010)  to  connect  the  +V  and  -V  terminals  of  the  three  modules  (left  figure).  The  CS  and  GND  pins  of  CN81  also  need  to  be 
connected together using accessory NMS-240-P3 (right figure), as shown below.

Summary of Contents for NMP1K2

Page 1: ...NMP650 1K2 Instruction Manual...

Page 2: ...ns 5 1 Input Voltage 5 2 Inrush Current Limiting 6 1 Assembly Procedures 7 1 Front End Mounting 7 2 Output Wiring Guidelines 7 3 De rating 7 4 Warranty 5 3 Output Voltage Current Adjustment 5 4 Short...

Page 3: ...tive current sharing and parallel control capabilities Output voltage programmable PV Constant current level programmable PC Global or Local ON OFF control Remote sense for output module DC OK signal...

Page 4: ...ption code 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Code 00 31 for NMP1K2 Code 00 01 02 03 06 07 10 16 for NMP650 NMP1K2 Code 01 00 02 03 04 05 06 07 08 09 10 11 12 13 14 15 SLOT 1 SLOT 2 SLOT...

Page 5: ...2 2 2 1 1 1 1 2 SLOT1 2 3 4 5V 36A 12V 20A 24V 10A 24V 10A SLOT1 SLOT2 SLOT3 SLOT4 V V CN81 48V 5A SLOT5 48V 5A SLOT6 5 6 2 3 4 5V 36A 12V 20A 24V 10A 48V 5A SLOT1 V V CN81 SLOT1 SLOT2 SLOT3 SLOT4 Mod...

Page 6: ...High 4 5 5 5V When the internal temperature exceeds the limit safe limit of temperature alarm Low 0 0 5V When the internal temperature is normal 3 4 GND P Ground 6 RC1 Turns the output on and off by...

Page 7: ...ANDARDS WORKING TEMP WORKING HUMIDITY STORAGE TEMP HUMIDITY TEMP COEFFICIENT VIBRATION FUNCTION 30 70 Derate at 50 refer to Derating Curve 20 90 RH non condensing RC RC Short Power ON RC RC Open Power...

Page 8: ...ower on to recover Protection type constant current limiting protection 6 1 8V 15 1 20V 6 15V 30 1 37V 15 30V 56 66V 30 55V REMOTE ON OFF CONTROL REMOTE SENSE OUTPUT VOLTAGE PROGRAMMABLE PV OUTPUT CUR...

Page 9: ...of the units Since the inrush limiting circuit mainly consists of thermistors and a relay inrush current will be much higher than the specified value if input thermistor is not allowed sufficient tim...

Page 10: ...mperature continues to increase and exceeds the safe limit value then the output will shut down automatically Please switch off the AC input remove all possible causes and then leave the unit to cool...

Page 11: ...e Remote Sense When using this function the sensing wires should either be twisted or shielded to prevent external noise interference refer to Figure 5 6 Built in remote sense circuit that is able to...

Page 12: ...LED V V V V V V V V V V V V CN81 CN81 CN81 CN81 CN81 CN81 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 CS PIN6 GND PIN1 or 2 GND GND GND GND GND GND 9 9 9 9 9 9 10 10 10 10 10 10 GND GND GND GND GN...

Page 13: ...All 6 pins must be inserted into the correct sockets Grab the circled location and lift module The power supply unit may remain hot after power off please leave the unit to cool for at least 5 minutes...

Page 14: ...e all modules are slotted into the notches circled in red securing the top cover ensure all modules are held secure by the notches and screws Please set the electric screw driver s torque setting to 6...

Page 15: ...ll decrease the voltage Once the output voltages of all modules have been tested and adjusted to the desired values the output configuration is done 10 Higher output voltage can be acquired by connect...

Page 16: ...ay be connected in parallel Before making the parallel connection adjust the voltage of each modules individually to the desired voltage and ensure the difference in voltages is less than 0 2V The com...

Page 17: ...ot 1 and slot 2 is less than 0 2V Use two 2 unit parallel copper plates accessory FAP 009 to connect the V and V terminals of slot 1 and slot 2 and use accessory and GND pins of CN81 in parallel d App...

Page 18: ...o the product otherwise the warranty shall be void When the ambient temperature is high or input AC voltage is low the power supply needs to be de rated according to curves shown below Derating Curve...

Page 19: ...HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS...

Page 20: ...le Green Blue Brown PIN NO Blank Plate Accessory BLANK NMS240 A1 3 V Series Connection Accessory A1 4 Front End Accessory Series Connection Accessory FAS 005 For 1 slot modules NMS 240 200mm NMP CN32...

Page 21: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Reviews: