Technical Manual
Blind Push Button Smart 55
BE-JTA5504.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
45
45
Setting the Time switch
fix via database (cannot
be changed on the
device)
manual input and
database (database
overwrites all switching
times)
manual input and
database (Transmission
aborted if switching times
are changed on the
device)
Setting whether and how the settings
of the timer can be changed
Make up switching times
on restart
not active
active
Setting whether the unit makes up
(sends) all currently valid switching
states after a restart.
Make up switching times
on time change
not active
active
Setting whether the unit catches up
(sends) the skipped switching states
after a clock adjustment to "forward".
Make up switching times
after unlock
not active
active
Setting whether the unit makes up
(sends) all omitted switching states
after an unlocking process.
Public holiday
not active
active
Activating the public holiday function
Automatic calculation
of public holiday
not active
active
Activation of the automatic public
holiday calculation.
When activated, a new submenu
"Automatic calculation of public
holidays" appears.
Shown if public holiday is "active".
Manual control via
object
not active
active, reset after the 1
st
change of day
active, reset after the 2
nd
change of day
active
Setting whether and when manual
control via an object is active.
Shown if public holiday is "active
".
Behaviour on public
holiday
like Sunday
Specify that public holidays behave
like Sundays.
Fix setting, cannot be changed!
Table 31: Settings – Time switch: Settings
Name of Time switch (for Visualisation interface)
This parameter is prepared but not yet active. In future, the name will be transmitted via the object
"Time switch - VisuControlEasy interface" when using the MDT VisuControl Easy object server and
made visible there.
Output objects
The setting refers to the selected hanging.
height and slats
: Objects 26 "Blinds absolute position" and 27 "Slats absolute position" are
shown here. This setting is used when selecting "Blinds".
Only height
: Object 26 "Blinds absolute position" is shown here. This setting is used when
selecting "Shutter".