4.5.2
Operating
modes
&
Setpoints
The
following
settings
are
available
at
the
ETS
‐
Software:
Illustration
9:
Operating
modes
&
setpoints
The
chart
shows
the
dynamic
range
of
the
operating
modes
and
setpoints:
ETS
‐
text
Dynamic
range
[default
value]
comment
Basis
comfort
setpoint
18,0°C
–
25,0°C
[21,0°C]
The
basis
comfort
setpoint
is
the
reference
point
of
the
control.
Night
reduction
Lowering
in
K
0
K
–
10,0
K
[3,0
K]
Lowering
of
the
temperature
by
choosing
the
operating
mode
night.
Relative
to
the
basis
comfort
setpoint.
Standby
reduction
Lowering
in
K
0
K
–
10,0
K
[2,0
K]
gets
activated
when
no
other
operating
mode
was
chosen
The
lowering
is
relative
to
the
basis
comfort
setpoint.
Setpoint
frost
protection
3°C
–
12°C
[7°C]
Setpoint
of
the
operating
mode
frost
protection.
indicated
by
an
absolute
value
Setpoint
heat
protection
24°C
–
40°C
[35°C]
Setpoint
of
the
operating
mode
heat
protection.
indicated
by
an
absolute
value
Chart
13:
Operating
modes
&
setpoints