Technical Manual Motion Detector SCN-BWM55.x1
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
48
HCV
Status automatic mode
DPT 1.011
send
HCV channel sends
status
Visu, Diagnostics,
Display
Object is permanently
displayed and has the value 1 if
HCV channel is in automatic
mode.
49
HCV
Switch dark
DPT 1.001
receive
HCV channel
reacts to incoming
telegram
External button for
overriding the
brightness
dependency
Object is displayed when the
parameter "Brightness" is set to
"Basic setting or active object
´Dark´"
Objects per Alarm:
50
Alarm - Output 1
Switching
DPT 1.001
send
Alarm channel
sends switching
command
Switch actuator,
Visu, Display, etc.
Object is permanently
displayed and sends the value 1
if the Alarm function detects a
motion
51
Alarm - Night mode
Switching
DPT 1.001
send
Alarm channel
sends switching
command
Switch actuator,
Visu, Display, etc.
Object is displayed when object
is activated via parameter
"Separate switch object at
night"
56
Alarm - Input
Lock/Enable
DPT 1.003
receive
Alarm channel
reacts to incoming
telegram
Push button for
switching
presence/absence,
etc.
Object is permanently
displayed; The type of the
object is set via parameter
"Lock object or enable object";
Object is used to lock/enable
the alarm function.