4.8.5.2 Temperature Shift
Two-button function
The temperature shift can be used to shift the heating control setpoint.
The following figure shows the available settings:
Figure 36: Settings - Temperature Shift
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Repeated sending at pressed
key
▪
Inactive
▪
Active
Setting whether the shift should be
repeated at fixed intervals while
holding down the key
Repetition time
200 ms
–
3 s
[1 s]
Setting the repetition time between
two transmissions of the
temperature shift
Table 75: Settings - Temperature Shift
Note
: The "Step range" parameter is only displayed if the "Temperature controller -> Set point shift
via 1 bit" menu is active. The setting of the step size in the controller and here in the key function is
internally linked. Example: If, for example, the step size is changed here from 0.5 K to 1 K, the step
size is also automatically changed to 1 K in the controller. Change in the controller also changes the
value here.
Presentation:
Two-button function
The temperature shift is represented by the temperature symbol. The representation is fixed to the
symbol no. 6. In addition, the actual value and the setpoint value can be labelled as required:
Figure 37: Settings - Presentation of Temperature shift