Page 30 of 53
SK2017 AHRI PFWSL-V/P-AECM-001
D.6.
Sleep Mode
a)
The sleep mode can only be set when the unit is in cool mode or heat mode.
b)
If the sleep mode is activated when the unit is in cool mode, then the indoor fan will run at low speed and Ts will increase
by
3.6ºF
over 2 hours.
c)
If the sleep mode is activated when the unit is in heat mode, then the indoor fan will run at set speed and Ts will decrease
by
3.6ºF
over 2 hours.
d)
Changing the mode of operation will cancel the sleep mode.
The cool mode sleep profile is:
The heat mode sleep profile is:
D.7.
Auto Fan Speed
Fan speed cannot change until it has run for more than 30
seconds.
Fan speed is regulated according to the profile below.
Fan speed cannot change until it has run for more than 30
seconds.
Fan speed is regulated according to the profile below.
After 30 seconds the fan speed is modulated according to the difference between the room temperature and the set
temperature. The controller adjusts the motor signal input from 0 to 5VDC by PID calculation every 10 seconds. The air flow is
adjusted from 15% to100%.
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts+0.9
Ts+1.8
Ts+3.6
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts-3.6
Ts-1.8
Ts-0.9
High
Tr
Medium
Low
Low
Ts+5.4 ºF
Ts+3.6 ºF
Ts+1.8 ºF
Ts
High
Medium
Low
High
Tr
Low
Low
Medium
Ts
Ts-1.8 ºF
Ts-3.6 ºF
Ts-5.4 ºF
Low
Medium
High