33-ALARMS
NEGATIVE PRESSURE INSIDE THE HOPPER WITH FACTORY-SET PARAMETERS AND A DRAUGHT OF 5 Pa (MINIMUM
RECOMMENDED)
POWER
P1
P2
P3
P4
P5
VALUES
6 kW
13.7/14.2 Pa
15.1/15.6 Pa
17.1/17.5 Pa
19.1/19.5 Pa
22.0/22.2 Pa
Draught
95°C
110°C
125°C
141°C
165°C
Smoke temperature
8 kW
13.8/14.3 Pa
15.6/16.1 Pa
17.8/18.0 Pa
21.7/22.2 Pa
26.1/26.6 Pa
Draught
104°C
119°C
145°C
148°C
184°C
Smoke temperature
10 kW
15.9/16.3 Pa
20.4/20.9 Pa
25.8/26.3 Pa
31.8/32.3 Pa
36.5/37.0 Pa
Draught
108°C
°C
150°C
°C
230°C
Smoke temperature
12 kW
16.5/17.3 Pa
20.4/20.9 Pa
25.8/26.3 Pa
31.8/32.3 Pa
36.5/37.1 Pa
Draught
118°C
127°C
155°C
172°C
195°C
Smoke temperature
14 kW
17.6/18.0 Pa
19.8/20.4 Pa
23.1/23.7 Pa
28.9/29.6 Pa
37.8/38.2 Pa
Draught
118°C
131°C
161°C
187°C
210°C
Smoke temperature
PLEASE NOTE The indicated negative pressure readings may differ by ±1Pa based on flue gas temperature. Likewise, flue gas temperature
may differ by ±10°C based on fuel quality or appliance cleanliness.
Changing the smoke fan speed
In order to further improve combustion in critical conditions, you can change the percentage of the parameters for the minimum amount
of incoming combustion air. These changes can be performed upwards in the event of serious difficulties in evacuating smoke and/or air
intake or downwards in the event of excessive draught of the flue.
Refer to AIR RECIPE modification instructions.
AVAILABLE VALUES
-2 -10%
-1 -5%
0 0% (default value)
+1 + 5%
+2 +10%