background image

Chapter 6

 

INSTALLATION AND USE MANUAL 

page

 38  

 

Operation 

            Technical service – MCZ Group S.p.A. all rights reserved - Reproduction prohibited 

 

6.6.  

CONTROL OF COMBUSTION 

PRIMARY AIR 

The fireplace stove is equipped with a rear hole of Ø100 mm for the 

entry of primary air which ensures combustion. 
Turn the register all the way to the left to allow the maximum flow of  
PRIMARY

and SECONDARY  air to light the fireplace stove. 

Once the flame in the fireplace stove is burning well, turn the register 

until the knob reaches the centre position. In this condition, the primary 

air inlet is completely closed and the secondary air flow is at a 

maximum. See sheet 17 
 

SECONDARY AIR 

The adjustment is made with the previously mentioned register.  Turn 

this register from the middle position to the right or left to adjust from 

MAX to MIN to adjust the flow of only secondary air.  

 

 

In normal conditions of use, dirt deposits on the glass at 

lighting, but disappears as soon as the combustion chamber 

is hot enough. 
The use of damp or treated wood emits a higher quantity of 

smoke than normal that can dirty glass faster. Also the low 

performance of the flue pipe can jeopardise glass cleanliness 

since smoke remains in the combustion chamber longer than 

normal. 

6.7.  

SMOKE VALVE ROD 

The system works only with efficient draught of the flue pipe (see 

technical characteristics) and lets you better control combustion, thus 

prolonging it. 
By inserting the smoke valve rod in the hole, you mechanically close 

the valve on the smoke outlet connection. Figure 18 
For example, in the evening, if you load a substantial amount of wood 

(about 5 kg) and you adjust the air to the minimum (figure 19) , you 

will keep the room comfortable all night. In the morning, the fire box 

will still contain embers ready for a fresh load of wood. 
Obviously you can also use the rod in the morning or when you like. 
 

 

You must not use the inserted rod if there is poor 

draught. Use in these conditions (low pressure, or 

flue pipe partially obstructed) may cause choked 

combustion and dirtying of the glass. 

 
 
 
 
 
 
 
 
 

Figure 17 –

 Detail of air register 

Figure 18 – 

Smoke valve inserted 

Summary of Contents for VIVO 70 WOOD

Page 1: ...8901156000 MANUALE DI USO ED INSTALLAZIONE EN...

Page 2: ...RT AIR VF 16 4 3 EXTERNAL AND INTERNAL AIR INTAKE 17 4 3 1 Combustion air inlet 17 4 3 2 Air inlet for natural ventilation 17 4 3 3 Air inlet for forced ventilation 17 4 4 POSITIONING 18 4 5 ADJUSTMEN...

Page 3: ...ON 34 6 1 PRE LIGHTING WARNINGS 34 6 2 OPERATING TEST 34 6 2 1 Phases for first test lighting 35 6 3 CHOICE OF FUEL 35 6 4 FIRST LIGHTING 36 6 5 LOADING THE FUEL 37 6 6 CONTROL OF COMBUSTION 38 6 7 SM...

Page 4: ...ut prior notice Reproduction even partial of this manual without the Manufacturer s authorisation is prohibited Manual preservation Please take care of this manual and keep it in a place that can be q...

Page 5: ...on original spare parts may be hazardous to the user and releases MCZ from any civil or penal liability Parts of the surfaces of the fireplace stove are very hot door handle glass Therefore avoid dire...

Page 6: ...y for any damage which may be caused directly or indirectly by persons animals or things as a result of the failure to observe all the provisions set forth in the instruction booklet especially those...

Page 7: ...with outdoor air vents and not bedrooms or bathrooms or rooms where fire hazards do not exist such as garages wood sheds flammable material warehouses strictly observing the provisions of current regu...

Page 8: ...apertures in the room walls that lead directly outdoors or ventilated rooms according to UNI 10683 REV For this purpose drill a hole with minimum 360 cm free section near the fireplace stove 22 cm dia...

Page 9: ...too short to avoid smoke leakage If metal connecting pipes are used they must be insulated with suitable material such as ceramic fibre matting to avoid deterioration of the masonry and of the decorat...

Page 10: ...irtight door IMPORTANT In the event of doubt on your chimney flue operations or that its dimensions are different from those recommended we highly suggest an authorised MCZ technician inspect and meas...

Page 11: ...lt to prevent rain snow and any foreign objects from getting into the flue pipe They must be installed to guarantee adequate smoke dispersion and out of the reflux area where negative pressure forms F...

Page 12: ...ssembly Technical service MCZ Group S p A all rights reserved Reproduction prohibited 3 DIMENSIONS AND TECHNICAL SPECIFICATIONS 3 1 Dimensions VIVO 70 WOOD 717 D150 D200 D150 15 670 8 5 620 539 15 8 5...

Page 13: ...Installation and assembly Technical service MCZ Group S p A all rights reserved Reproduction prohibited 3 2 Dimensions VIVO 90 WOOD D150 D200 D150 432 432 182 170 202 864 11 5 11 5 458 23 5 15 45 12 4...

Page 14: ...5x25 cm 25 Between 5 and 7 m 22x22 cm 22 Over 7 m 20x20 cm 20 Note Intermittent combustion unit Appliance suitable for installation in a shared flue Data may vary according to the fuel used Technical...

Page 15: ...ARATION AND UNPACKING Open the packaging remove the stove unit from the pallet and position it in the chosen location taking care that its position complies with the above instructions The fireplace s...

Page 16: ...n the back of the stove unit figure 1 If it is not possible to connect directly to the air intake at least connect the flange to the outside of the cladding This operation is necessary to ensure prope...

Page 17: ...of the duct with the flange F 100 5 turn the duct F so that the flange 100 faces downwards 6 Perform the steps in points 1 2 3 4 in reverse order In the absence of this direct connection B it is obli...

Page 18: ...hem Do not for any reason obstruct the air intakes if the fireplace stove or ventilation kit is in operation 4 4 POSITIONING The VIVO fireplace stove can be placed in a corner or along a wall It can b...

Page 19: ...USE MANUAL page 19 Installation and assembly Technical service MCZ Group S p A all rights reserved Reproduction prohibited 530 510 870 500 10 960 610 510 705 500 790 10 Vivo 90 Wood wall hole size Vi...

Page 20: ...ed by fitting one into another Figure 9 Any increase in the section of the connecting pipe must start immediately above the hood of the fireplace and not along the flue pipe section When installation...

Page 21: ...i dalla mancata osservanza di questa avvertenza For proper operation of room ventilation remember that In the lower part of the cladding an opening for the entry of convective air must be provided tha...

Page 22: ...nation 1 2 4 3 5 1 Structure of basic natural ventilation outlet 2 pieces 2 Fastening bracket group 2 pieces 3 Hose 150 L 1 5 m 2 pieces 4 Flange 150 2 pieces 5 Hose clamp D 60 170 4 pcs 5 1 2 Compone...

Page 23: ...natural ventilation kit with and without illumination A C D B E A One direction air outlet without illumination includes container for dehumidification B One direction air outlet with illumination in...

Page 24: ...S p A all rights reserved Reproduction prohibited 5 2 2 Air outlets for forced ventilation kit B C D A A One direction air outlet includes container without illumination B One direction air outlet in...

Page 25: ...uts provided fig 2 5 connect the hose a previously fastened to the fireplace hose to the connection located on the structure of the air outlet e 6 tighten the hose a on the connection e with the provi...

Page 26: ...t is facing the front of the structure fig 6 Fasten the light using the two brackets c with the screws b and bolts d provided Once you have inserted the light a make the electrical connections In the...

Page 27: ...are resistant to high temperatures such as those used in kitchen ovens Cleaning glass light fixture of the air outlet 1 Open the door that contains the dehumidification container 2 Remove the contain...

Page 28: ...ed with 6 double terminals for the connection of 1 Line 1 2 LINEA 2 Fan 1 3 4 VENTIL 3 Fan 2 5 6 VENTIL 4 Light 7 8 AUX 5 Switch for door opening 9 10 PORT 6 Probe 11 12 SONDA 5 4 2 Positioning of the...

Page 29: ...to 10 speed steps 0 V1 V9 V10 MANUAL AUTOMATIC mode is set using button 4 5 5 1 On off The control unit is turned on and off by turning knob 3 On status is indicated by LED 1 5 5 2 Operation Activati...

Page 30: ...of the structure If the safety function trips frequently contact the technical service department of MCZ 5 5 4 Light on if present Press button 5 to turn the light on or off The LED 5a indicates the...

Page 31: ...y the installer PROBE INSTALLATION Insert the plastic piece C in D and screw in B without forcing it On the threaded part of piece D insert washer E The group thus formed A1 must be inserted on the ri...

Page 32: ...4 and 5 6 Connect the probe 11 12 see paragraph 5 6 For air outlet with light connect the power cord to the control unit on the terminals 7 8 For air outlets with a light for natural ventilation make...

Page 33: ...t fixture has a light bulb disconnect the power cables when extracting the flange It is now sufficient to turn the fan with respect to the duct to allow passage without damaging the piece IMPORTANT TH...

Page 34: ...ing the fireplace stove is subject to expansion and contraction therefore you may hear slight creaking noises This phenomenon is absolutely normal the structure being made of sheet steel and must not...

Page 35: ...used with caution to avoid overheating which could damage the stove It is advisable to use fuels such as poplar pine lime tree or chestnut which have low calorific power since they are soft wood and a...

Page 36: ...the door open to the first stage When the twigs are burning the door can be closed Only once the flame is burning well presence of a bed of coals and full combustion place the air adjustment between...

Page 37: ...rts During normal use always keep the fire door completely closed since intermediate positions cause abnormal combustions forge effect rapid consumption of wood and a drastic reduction in the heating...

Page 38: ...the combustion chamber is hot enough The use of damp or treated wood emits a higher quantity of smoke than normal that can dirty glass faster Also the low performance of the flue pipe can jeopardise...

Page 39: ...n the screws on the sides Loosen the frame This operation is possible to replace the frame provided with the optional one of 50 mm 6 9 EMERGENCY SITUATIONS If for any reason the stove fire needs to be...

Page 40: ...kept outdoors with great care and not placed in a waste container Leave them to cool down in the open air in a metal container 7 1 3 Cleaning the refractory material walls ALUTEC They do not require a...

Page 41: ...DEALT WITH BY SPECIALIZED TECHNICIAN 7 2 1 Cleaning flue pipe Mechanical cleaning of the flue pipe is recommended at least once a year Excessive deposits of unburnt solid material can cause problems...

Page 42: ...MCZ GROUP S p A Via La Croce 8 33074 Vigonovo di Fontanafredda PN ITALY Telephone 39 0434 599599 PBX Fax 39 0434 599598 Internet www mcz it e mail mcz mcz it 8901155700 Rev 0 12 2011...

Reviews: