Chapter 2

 

INSTALLATION AND USE MANUAL 

page

 10  

 

Theoretical notions for installation 

Technical service – MCZ Group S.p.A. all rights reserved - Reproduction prohibited 

 

2.5.1.  

Examples of flue pipes 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Square or rectangular section flue pipes must have rounded internal 

corners with radius not less than 20mm. For the rectangular section, 

the ratio between internal dimensions must be 

1.5. 

The sections/lengths of the flue pipe shown in the technical data table 

are guidelines for correct installation. Any alternative configurations 

must be suitably sized in accordance with EN13384-1. 
The smoke duct should be equipped with a solid material collection 

chamber at the mouth of the smoke duct to be easily opened with an 

airtight door. 

 

  

IMPORTANT ! 

In the event of doubt on your chimney flue operations or 

that its dimensions are different from those recommended, 

we highly suggest an authorised MCZ technician inspect and 

measure chimney flue performance (micro-gauge 

measurements) 
MCZ s.p.a. shall not be held liable for poor operation of the 

fireplace stove that is due to a flue pipe of improper size or 

installation that does not comply with provided 

requirements. 

 
 
 
 

AISI 316 stainless steel flue 

pipe with dual chamber 

insulated with ceramic wool 

or equivalent resistant to 

400°C. 

EXCELLENT 

Flue pipe in refractory brick 

with insulated double wall and 

external coat of cement mix 

lightened with honeycomb 

material such as clay. 

GOOD 

Traditional square section 

clay flue pipe with insulating 

hollow inserts. 

GOOD 

Avoid flue pipes with internal 

rectangular sections whose 

larger side is double the smaller 

such as 20x40 or 15x30. 

AVERAGE 

Summary of Contents for VIVO 70 WOOD

Page 1: ...8901156000 MANUALE DI USO ED INSTALLAZIONE EN...

Page 2: ...RT AIR VF 16 4 3 EXTERNAL AND INTERNAL AIR INTAKE 17 4 3 1 Combustion air inlet 17 4 3 2 Air inlet for natural ventilation 17 4 3 3 Air inlet for forced ventilation 17 4 4 POSITIONING 18 4 5 ADJUSTMEN...

Page 3: ...ON 34 6 1 PRE LIGHTING WARNINGS 34 6 2 OPERATING TEST 34 6 2 1 Phases for first test lighting 35 6 3 CHOICE OF FUEL 35 6 4 FIRST LIGHTING 36 6 5 LOADING THE FUEL 37 6 6 CONTROL OF COMBUSTION 38 6 7 SM...

Page 4: ...ut prior notice Reproduction even partial of this manual without the Manufacturer s authorisation is prohibited Manual preservation Please take care of this manual and keep it in a place that can be q...

Page 5: ...on original spare parts may be hazardous to the user and releases MCZ from any civil or penal liability Parts of the surfaces of the fireplace stove are very hot door handle glass Therefore avoid dire...

Page 6: ...y for any damage which may be caused directly or indirectly by persons animals or things as a result of the failure to observe all the provisions set forth in the instruction booklet especially those...

Page 7: ...with outdoor air vents and not bedrooms or bathrooms or rooms where fire hazards do not exist such as garages wood sheds flammable material warehouses strictly observing the provisions of current regu...

Page 8: ...apertures in the room walls that lead directly outdoors or ventilated rooms according to UNI 10683 REV For this purpose drill a hole with minimum 360 cm free section near the fireplace stove 22 cm dia...

Page 9: ...too short to avoid smoke leakage If metal connecting pipes are used they must be insulated with suitable material such as ceramic fibre matting to avoid deterioration of the masonry and of the decorat...

Page 10: ...irtight door IMPORTANT In the event of doubt on your chimney flue operations or that its dimensions are different from those recommended we highly suggest an authorised MCZ technician inspect and meas...

Page 11: ...lt to prevent rain snow and any foreign objects from getting into the flue pipe They must be installed to guarantee adequate smoke dispersion and out of the reflux area where negative pressure forms F...

Page 12: ...ssembly Technical service MCZ Group S p A all rights reserved Reproduction prohibited 3 DIMENSIONS AND TECHNICAL SPECIFICATIONS 3 1 Dimensions VIVO 70 WOOD 717 D150 D200 D150 15 670 8 5 620 539 15 8 5...

Page 13: ...Installation and assembly Technical service MCZ Group S p A all rights reserved Reproduction prohibited 3 2 Dimensions VIVO 90 WOOD D150 D200 D150 432 432 182 170 202 864 11 5 11 5 458 23 5 15 45 12 4...

Page 14: ...5x25 cm 25 Between 5 and 7 m 22x22 cm 22 Over 7 m 20x20 cm 20 Note Intermittent combustion unit Appliance suitable for installation in a shared flue Data may vary according to the fuel used Technical...

Page 15: ...ARATION AND UNPACKING Open the packaging remove the stove unit from the pallet and position it in the chosen location taking care that its position complies with the above instructions The fireplace s...

Page 16: ...n the back of the stove unit figure 1 If it is not possible to connect directly to the air intake at least connect the flange to the outside of the cladding This operation is necessary to ensure prope...

Page 17: ...of the duct with the flange F 100 5 turn the duct F so that the flange 100 faces downwards 6 Perform the steps in points 1 2 3 4 in reverse order In the absence of this direct connection B it is obli...

Page 18: ...hem Do not for any reason obstruct the air intakes if the fireplace stove or ventilation kit is in operation 4 4 POSITIONING The VIVO fireplace stove can be placed in a corner or along a wall It can b...

Page 19: ...USE MANUAL page 19 Installation and assembly Technical service MCZ Group S p A all rights reserved Reproduction prohibited 530 510 870 500 10 960 610 510 705 500 790 10 Vivo 90 Wood wall hole size Vi...

Page 20: ...ed by fitting one into another Figure 9 Any increase in the section of the connecting pipe must start immediately above the hood of the fireplace and not along the flue pipe section When installation...

Page 21: ...i dalla mancata osservanza di questa avvertenza For proper operation of room ventilation remember that In the lower part of the cladding an opening for the entry of convective air must be provided tha...

Page 22: ...nation 1 2 4 3 5 1 Structure of basic natural ventilation outlet 2 pieces 2 Fastening bracket group 2 pieces 3 Hose 150 L 1 5 m 2 pieces 4 Flange 150 2 pieces 5 Hose clamp D 60 170 4 pcs 5 1 2 Compone...

Page 23: ...natural ventilation kit with and without illumination A C D B E A One direction air outlet without illumination includes container for dehumidification B One direction air outlet with illumination in...

Page 24: ...S p A all rights reserved Reproduction prohibited 5 2 2 Air outlets for forced ventilation kit B C D A A One direction air outlet includes container without illumination B One direction air outlet in...

Page 25: ...uts provided fig 2 5 connect the hose a previously fastened to the fireplace hose to the connection located on the structure of the air outlet e 6 tighten the hose a on the connection e with the provi...

Page 26: ...t is facing the front of the structure fig 6 Fasten the light using the two brackets c with the screws b and bolts d provided Once you have inserted the light a make the electrical connections In the...

Page 27: ...are resistant to high temperatures such as those used in kitchen ovens Cleaning glass light fixture of the air outlet 1 Open the door that contains the dehumidification container 2 Remove the contain...

Page 28: ...ed with 6 double terminals for the connection of 1 Line 1 2 LINEA 2 Fan 1 3 4 VENTIL 3 Fan 2 5 6 VENTIL 4 Light 7 8 AUX 5 Switch for door opening 9 10 PORT 6 Probe 11 12 SONDA 5 4 2 Positioning of the...

Page 29: ...to 10 speed steps 0 V1 V9 V10 MANUAL AUTOMATIC mode is set using button 4 5 5 1 On off The control unit is turned on and off by turning knob 3 On status is indicated by LED 1 5 5 2 Operation Activati...

Page 30: ...of the structure If the safety function trips frequently contact the technical service department of MCZ 5 5 4 Light on if present Press button 5 to turn the light on or off The LED 5a indicates the...

Page 31: ...y the installer PROBE INSTALLATION Insert the plastic piece C in D and screw in B without forcing it On the threaded part of piece D insert washer E The group thus formed A1 must be inserted on the ri...

Page 32: ...4 and 5 6 Connect the probe 11 12 see paragraph 5 6 For air outlet with light connect the power cord to the control unit on the terminals 7 8 For air outlets with a light for natural ventilation make...

Page 33: ...t fixture has a light bulb disconnect the power cables when extracting the flange It is now sufficient to turn the fan with respect to the duct to allow passage without damaging the piece IMPORTANT TH...

Page 34: ...ing the fireplace stove is subject to expansion and contraction therefore you may hear slight creaking noises This phenomenon is absolutely normal the structure being made of sheet steel and must not...

Page 35: ...used with caution to avoid overheating which could damage the stove It is advisable to use fuels such as poplar pine lime tree or chestnut which have low calorific power since they are soft wood and a...

Page 36: ...the door open to the first stage When the twigs are burning the door can be closed Only once the flame is burning well presence of a bed of coals and full combustion place the air adjustment between...

Page 37: ...rts During normal use always keep the fire door completely closed since intermediate positions cause abnormal combustions forge effect rapid consumption of wood and a drastic reduction in the heating...

Page 38: ...the combustion chamber is hot enough The use of damp or treated wood emits a higher quantity of smoke than normal that can dirty glass faster Also the low performance of the flue pipe can jeopardise...

Page 39: ...n the screws on the sides Loosen the frame This operation is possible to replace the frame provided with the optional one of 50 mm 6 9 EMERGENCY SITUATIONS If for any reason the stove fire needs to be...

Page 40: ...kept outdoors with great care and not placed in a waste container Leave them to cool down in the open air in a metal container 7 1 3 Cleaning the refractory material walls ALUTEC They do not require a...

Page 41: ...DEALT WITH BY SPECIALIZED TECHNICIAN 7 2 1 Cleaning flue pipe Mechanical cleaning of the flue pipe is recommended at least once a year Excessive deposits of unburnt solid material can cause problems...

Page 42: ...MCZ GROUP S p A Via La Croce 8 33074 Vigonovo di Fontanafredda PN ITALY Telephone 39 0434 599599 PBX Fax 39 0434 599598 Internet www mcz it e mail mcz mcz it 8901155700 Rev 0 12 2011...

Reviews: