background image

Model

5CKWS20AR

5CKWS25AR

5CKWS30AR

5CKWS40AR

5CKWS50AR

Coupling Unit

5WSS16AR

5WSS20AR

5WSS25AR

5WSS30AR

5WSS40AR

5WSS50AR

Nominal Cooling Capacity

Btu/hr

16000

20000

25000

30000

38500

51500

kW

4.68

5.86

7.32

8.78

11.27

15.08

Nominal Heating Capacity

Btu/hr

16500

20500

25500

31000

41500

54500

kW

4.83

6.03

7.47

9.08

12.15

15.96

Unit Nett Weight

kg

31 + 4

32 + 4

35 + 4

38 + 4

40 + 4

Fan Motor

6 Poles x 35W

6 Poles x 50W

6 Poles x 65W

6 Poles x 85W

6 Poles x 120W

Fan Blower

Air flow rate (high speed)

m

3

/min

20.9

22.1

24.9

28.0

29.5

Refrigerant Circuit

Liquid valve connection

inches

1/4

1/4

3/8

3/8

3/8

Gas valve connection

inches

1/2

5/8

5/8

5/8

5/8

Drain Pipe Connection

inches

3/4

3/4

3/4

3/4

3/4

Air Filter

WASHABLE SARANET FILTER

Ø Tube, D

A (mm)

Inch

mm

Imperial

Rigid

1/4"

6.35

1.3

0.7

3/8"

9.52

1.6

1.0

1/2"

12.70

1.9

1.3

5/8"

15.88

2.2

1.7

3/4"

19.05

2.5

2.0

REFRIGERANT PIPING WORK

Refrigerant piping is important in particular. Refrigerant cycle of the split air conditioner is realized by the perfect piping work.

1. Piping Length And Elevation

If the piping is too long, both the capacity and reliability of unit will drop.

• As the number of bends increase, resistance to flow of refrigerant system increases, thus lowering cooling capacity and as a

result the compressor may become defective.

• Always choose the shortest path and follow the recommendation as tabulated below.

Model

5CKWS20AR

5CKWS25AR

5CKWS30/40/50AR

Maximum Length (m)

15

15

35

Maximum Elevation (m)

8

8

10

Maximum No. of Bends

10

10

10

Liquid Pipe Size

1/4”

1/4”

3/8”

Gas Pipe Size

1/2”

5/8”

5/8”

Copper tube

Swaging block

Pipe Size mm / (in)

Torque Nm / (ft - lb)

6.35 (1/4)

18 (13.3)

9.53 (3/8)

42 (31.0)

12.7 (1/2)

55 (40.6)

15.88 (5/8)

65 (48.0)

19.05 (3/4)

78 (57.6)

2. Piping Connection

Do not use contaminated or damaged copper tubing. If any piping, evaporator
or condenser had been exposed or had been opened for 15 seconds or more,
then vacuum and purge with field supplied refrigerant. Generally, do not re-
move plastic, rubber plugs and brass nuts from the valves, fittings, tubing and
coils until it is ready to connect suction or liquid line into valves or fittings.

If any brazing work is required, ensure that nitrogen gas is passed through coil
and joints while the brazing work is being done. This will eliminate soot forma-
tion on the inside wall of copper tubings.

Cut the pipe stages by stages, advancing the blade of pipe cutter slowly. Extra
force and a deep cut will cause more distortion of pipe and therefore extra burr.

Remove burrs from cut edges of pipes with a remover. This will avoid uneven-
ness on the flare face which will cause gas leak.

Flare the pipe with extra length above the flaring tool as shown in the table
beside.

The flared edge must be even and not cracked or scratched.

Align the center of the piping and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.

Be sure to execute heat insulation. (Polyurethane form with thickness more
than 15mm)

Except the water source heat pump unit which is pre-charge with refrigerant,
the fan coil unit and the refrigerant connection pipes must be purged because
the air that contain moisture remaining in the refrigerant cycle may cause mal-
function to the compressor.

PHYSICAL DATA

R410A – Heat Pump

D

A

Summary of Contents for WSHP

Page 1: ...WATER SOURCE HEAT PUMP CEILING CASSETTE SPLIT TYPE AIR CONDITIONER A SERIES 2006 McQuay International INSTALLATION MANUAL Group WSHP Part Number A08019027750 Date MAY 2006 IM 5CKWSAR 0506 0 McQuay...

Page 2: ...er Position 1 SINGLE WSHP Default 2 TANDEM 3 DX 1 2 3 1 2 3 1 2 3 Model A B C D E F G H I J K 20AR 820 820 363 335 28 930 930 642 622 555 555 25AR 32 2 32 2 14 3 13 2 1 1 36 6 36 6 25 2 24 5 21 9 21 9...

Page 3: ...OFF position to prevent the nuisance tripping of the unit If this is not done the unit s fans will start turning automatically when power resumes posing a hazard to service personnel or the user Do n...

Page 4: ...avoid the condensed water dripping inside the room 5 Drain Test Main Drain Pipe Feed Water Flexible Drain Hose Connect the main drain pipe to the flexible drain Feed water from flexible drain hose to...

Page 5: ...Size 1 2 5 8 5 8 Copper tube Swaging block Pipe Size mm in Torque Nm ft lb 6 35 1 4 18 13 3 9 53 3 8 42 31 0 12 7 1 2 55 40 6 15 88 5 8 65 48 0 19 05 3 4 78 57 6 2 Piping Connection Do not use contam...

Page 6: ...ection Cable 220 240V 1PH 50Hz Terminal Block 5WSS AR 4WV OF COMP L N N 4WV COMP N The electrical power must be provided with protection devices circuit breaker or fuse with double pole separation sys...

Page 7: ...ifold valve charging hose pressure gauge gas leak detector flare tools torque wrench vacuum pump and refrigerant cylinder As an R410Aair conditioner incurs higher pressure than R22 units it is essenti...

Page 8: ...e Air Discharge Air Discharge Air Discharge Knock Out Hole Air Intake Knock Out Hole 10 50 50 50 50 50 10 20 70 20 109 119 90 100 PCD 140 115 20 115 The indoor unit is provided with air discharge and...

Page 9: ...ge are clogged The regulated temperature is not high enough Odors may be caused by cigarettes smoke particles perfume etc which might have adhered onto the coil This is caused by air humidity after an...

Reviews: