AUTO RANDOM RE-START FUNCTION
2. Sealing Material
•
It is possible to seal one of
the four air discharge outlet.
(Sealing two or more air dis-
charge outlet could cause a
malfunction).
•
Remove the front panel and
insert the sealing material
into the air discharge outlet
on the indoor unit to seal the
air outlet.
•
The sealing material is the
same length as the longer air
discharge outlet. If it is
desired to seal the shorter air
discharge outlet, cut the
sealing material to shorten it.
•
Push the sealing material in
about 10mm beyond the
bottom surface of the indoor
unit so that it does not touch
the air louver. Be sure not to
push the sealing material in
any farther than about 10mm.
ACCESSORY PARTS
3. Charge Operation
This operation must be done by using a gas cylinder and a precise weighing
machine. The additional charge is topped-up into the water source heat pump
unit using the suction valve via the service port.
•
Remove the service port cap.
•
Connect the low pressure side of the charging gauge to the suction service
port center of the cylinder tank and close the high pressure side of the
gauge. Purge the air from the service hose.
•
Start the air conditioner unit.
•
Open the gas cylinder and low pressure charging valve.
•
When the required refrigerant quantity is pumped into the unit, close the
low pressure side and the gas cylinder valve.
•
Disconnect the service hose from service port. Put back the service port
cap.
Open
Open
Suction
Valve
Discharge Valve
Fan Coil Unit
Water Source
Heat Pump Unit
Liquid side
Gas side
Check
Valve
Close
Hi
Low
1. Short Duct Specification
Possible Direction For Air Discharge And Air Intake
Possible Opening Dimension For Duct Connection
Air Intake
Air Discharge
Air Discharge
Air Discharge
Air Discharge
Air Discharge Knock Out Hole
Air Intake Knock
Out Hole
10
50
50
50
50
50
10
20
70
20
109
11
9
90
Ø100
PCD Ø140
115
20
115
•
The indoor unit is provided with air discharge and air intake “knock-out” hole for duct
connection. However the connection of the short duct for air discharge is possible on
only one side.
•
The use of short duct for air discharge will improve airflow distribution if there is an
obstruction (such as a lighting fixture) or in a long, narrow room or an L-shaped room.
It also use for air-conditioning of two rooms simultaneously.
Note:
•
Avoid using the short duct on which the air discharge grille can be completely closed, to
prevent evaporator freezing.
•
In order to prevent condensation forming, be sure that there is sufficient thermal
insulation and no leakage of cool air when installing the short duct.
•
Keep the introduction of fresh air intake within 20% of total air flow. Also provide a
chamber and use a booster fan.
If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power is
restored. (Applicable only to units with this feature).
INDICATOR LIGHTS
Remote Control
When there is infrared remote control operating signal, the signal receiver on indoor unit will make a <beep> for signal accep-
tance confirmation.
Action
Call Your
Dealer
Faulty Indication
PWR LED
Timer LED
LED in SLM
1.
Room sensor missing
Blink 1 time
-
Blink Fan
2.
Fan coil unit sensor missing
Blink 2 times
-
Blink Dry & Fan
3.
Water source heat pump unit sensor missing
Blink 3 times
-
Blink Dry
4.
Compressor overload/Fan coil unit sensor short/
-
Blink 1 time
Blink Cool
Water source heat pump unit sensor short
5.
Gas leak
-
Blink 3 times
Blink Cool & Dry
6.
Water pump fault
-
Blink 2 times
Blink Cool & Fan
7.
Outdoor defrost
-
-
(No indication in display panel.)
Blink HEAT in SLM3 only.
8.
Water source heat pump unit water fault
Blink 5 times
Blink Cool & Sleep