background image

IM 368 / Page 12 of 20 (Rev 11/03)

Units that are furnished with remote mounted thermostats should
be wired as shown in Figure 17. Other considerations for this
arrangement are as follows:
1. When wiring the low voltage plug and receptacle disconnect,

provide enough wire to move harness out of the way for
chassis removal.

2. If subbase is used, a small hole must be drilled and grommeted

in the subbase front to allow passage of the low voltage wires.

3. If slave units are to be employed, connect as shown in Figure

17. With this arrangement, the loop between terminals N2
and N4 of the slave unit  must be severed. The standard
master transformer handles 10 VA power draw and each slave
unit draws 5 VA. If more than one slave unit is used, the
master transformer must be replaced with a larger one. The
number of slave units that can be connected is limited to the
maximum amperage rating of the thermostat contacts.

4. When using a programmable wall thermostat, splice into the

jumper going from N2 to N4 of the master unit and connect it
to the common terminal of the thermostat. Refer to the
instructions furnished with the chosen thermostat to locate
the common terminal. Note: It may be necessary to place a
larger VA transformer in the unit when using certain
programmable thermostats. Check the VA draw of the
chosen thermostat, plus a VA draw of the slave unit to be
sure it does not exceed 10 VA power draw.
 Slave units are
connected as described in #3 above.

Incremental conditioners are built to last. With proper care, the
unit should provide uninterrupted service for many years.
Scheduled maintenance of this equipment, as described below,
is the key to the equipment’s longevity.

A. Air filters must be cleaned at regular intervals. Twice annually

may be adequate in some areas while twice monthly may be
required in others. Areas with high dirt and lint content or heavy
usage of units require more frequent filter maintenance than
those areas of relatively clean operating or low usage
conditions. Unit malfunction may occur if air filters are not kept
clean. Rinse filters with hot water and a mild detergent. Let
dry and oil lightly to enhance dust collecting ability.

B. McQuay recommends that every year the chassis be removed

for a thorough checkup. This should be completed as follows:
1. Unplug unit from power source.
2. Remove front panel.
3. Remove chassis from cabinet and move it to the

maintenance department. Replace with spare chassis or
weather plate.

4. Check all seals and insulation and repair as required.
5. Check all wiring and controls for hazardous conditions.
6. Thoroughly clean discharge grilles.
7. Cover motors and control module with watertight

material and wash evaporator coil, condenser coil and base
pan using hot water and a mild soap.

8. Clean condensate drain and clear weep holes.
9. Dry equipment thoroughly, especially electric parts and

insulation.

10. Clean any rust spots with steel wool and paint with rust

inhibiting paint.

11. Clean insulation or replace if necessary.
12. Check insulation on suction tube and replace if necessary.
13. Check all fasteners and tighten as required.
14. Clean and oil damper door and linkage.
15. Test run chassis before reinstalling or returning to spare

parts stock.

Installing Remote Mounted Thermostat

Scheduled Maintenance

Residential and institutional cleaning compounds can
cause permanent damage to the packaged terminal unit.
To  avoid damage to unit controls and heat transfer
surfaces, do not spray cleaning compounds onto the
discharge grille, return air opening, or unit controls.
Normal cleaning can be accomplished by wiping the unit
surface with a damp cloth. When using cleaning
compounds on carpets, floors or walls, turn the unit off to
avoid drawing potentially damaging vapors into the
package terminal unit.

   WARNING

Figure 17.

Optional Wall Plate

Temperature
Fall

System
Switch

Heat

Off

Cool

On

Auto

Fan
Switch

See Note
3 Above

Low

Voltage

Plug &

Receptacle
Disconnect

Wires from Control

Master Unit

Wires from Control

Slave Unit

Summary of Contents for Suite Incremental

Page 1: ...Suite Incremental PTAC PTHP Conditioner Installation Maintenance Data Group PTAC Part No 106018472 Date November 2003 IM 368 7 2003 McQuay International...

Page 2: ...ntacted The unit nameplate should be checked to make sure the voltage agrees with the power supply available Suite II Series Comfort Conditioner is designed and built for through the wall installation...

Page 3: ...ubbase is 81 4 210mm Each subbase has leveling legs providing for up to 1 25 4mm additional height MCQUAY PTAC PTHP P DES 1 009 E Z 60 Product Category P PTAC Product Identifier see box below Suite De...

Page 4: ...architectural louver Louver should be flush to exterior surface when complete Note The wall sleeve is not intended to replace the lintel 5 Level cabinet wall sleeve in both directions and secure by a...

Page 5: ...rpose See Figure B page 7 5 Recess the wall sleeve so that the louver is flush with the exterior of the building 6 Level cabinet wall sleeve in both directions and secure by anchoring with appropriate...

Page 6: ...te outside louver This recess is 3 8 9 5mm for stamped louvers and 11 4 32mm for architec tural louvers Louver should be flush to exterior surface when completed Note The wall sleeve is not intended t...

Page 7: ...f the wall sleeve and another bead around the mating side of the wall sleeve extension so that the joint is watertight Be sure to use a resilient caulking such as silicone 3 Assemble the wall sleeve e...

Page 8: ...e to the incoming power supply Hydronic Subbase A subbase is supplied as standard with all hydronic units This subbase measures 8 203mm in height and includes the hydronic heating coil Refer to IM Bul...

Page 9: ...ure 14 illustrates the installation of the indoor drain kit The indoor drain kit should be installed before placing the cabinet wall sleeve into the opening Install as follows 1 Locate the drain so th...

Page 10: ...to make certain they did not loosen during shipment Do not loosen nuts holding down compressor they are factory installed 11 Do not lubricate motors before startup Motors are factory lubricated Consul...

Page 11: ...n accordance with all local and National Electrical Code requirements The conditioners are supplied as follows Electrical Heating Unit 1 208V and 230V models are supplied with an attachment cord and p...

Page 12: ...frequent filter maintenance than those areas of relatively clean operating or low usage conditions Unit malfunction may occur if air filters are not kept clean Rinse filters with hot water and a mild...

Page 13: ...the kinds of parts which McQuay International recommends to be carried in stock together with the quantity of parts recommended per 100 incremental conditioners installed Part Name Cooling Chassis Co...

Page 14: ...OOL and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on COOL but blowers do not run 6 Compressor starts and runs on COOL but blowers do...

Page 15: ...ilicone oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Adjust by bending or applying tape j Occasionally equipment will have noisy operation for no apparent reason In...

Page 16: ...IM 368 Page 16 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR DES THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Electric Heat Standard Manual Changeover Control...

Page 17: ...IM 368 Page 17 of 20 Rev 11 03 MODEL HEAT PUMP SUITE II 2 MOTOR DHS THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Heat Pump Standard Manual Changeover Control...

Page 18: ...age 18 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT WATER CHANGEOVER MANUAL Wiring Diagram Hot Water Heat with Normally Open Valve Standard Manual Changeover...

Page 19: ...Page 19 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT STEAM CHANGEOVER MANUAL Wiring Diagram Steam Heat with Normally Closed Valve Standard Manual Changeover...

Page 20: ...2003 McQuay International www mcquay com 800 432 1342 Page 20 of 20 IM 368 7 Rev 11 03...

Reviews: