background image

8

McQuay IM 777-2

Installation Guidelines

Injected-Foam Insulated Panels 

Skyline air handlers now are furnished with double-wall, 
injected-foam insulated panels. Foam panels are stronger, 
more rigid, and lighter than panels with fiberglass insulation. 
The insulation R-value is improved to 13. However, foam 
insulation can burn when exposed to flame or other ignition 
sources and release toxic fumes. Take care in cutting and 
sealing all field-cut openings in these panels.

Panel Cutting Procedure

1

Determine the number and location of holes required for 
electrical conduit, piping, and control wiring as follows:

• 

Check that adequate space is available inside the unit for 

conduit or pipe routing.

• 

Do not locate holes in a panel that provides access to key 

maintenance components such as filters and fan 
assemblies.

• 

Do not locate where the conduit or piping blocks airflow 

or obstructs hinged access doors.

2

Once a proper location is determined, drill a small pilot 
hole completely through the panel. Then use a sharp hole 
saw or a saber saw and cut from each side of the panel.

3

Seal the double-wall panel on each side with an industrial/
commercial grade silicone sealant or duct seal compound. 
It is extremely important to seal each panel hole or 
penetration securely so it is airtight, watertight, and so that 
there is 

no exposed insulation

.

Figure 12: Cutting/Sealing Injected-Foam Insulated Panels

Field Mounting Junction Boxes and
Other Components

For field mounting 4" × 4" or smaller junction boxes to the 
standard panel exterior, use a minimum quantity of 4, 3/16" 
diameter pop rivets. 

Do not use self-tapping drill screws. 

They will not tighten nor secure properly and panel 
damage can occur.

If larger, heavier components require mounting on unit panels, 
use through-bolts with flat washers through both outer and 
inner panels. To maintain panel integrity, seal both ends with 
an industrial/commercial grade silicone sealant or duct seal 
compound.

The unit frame channel is another excellent location for 
securing heavier components; self-tapping screws are not 
acceptable. Ensure that the location permits the full operation 
of all access doors and panels and does not interfere with other 
vital components.

Duct Connections

Use flexible connectors on the outlet and inlet duct 
connections of all units. Do not position down flow fans over 
air ducts that are routed down intothe building. Use a 
discharge plenum when bottom connections are necessary. See 
Figure 13

.

Figure 13: Discharge Plenum

WARNING

Flame and smoke can cause equipment 
damage, severe personal injury, or 
death.

Before operating unit, seal all piping and 
wiring holes on both inner and outer panels 
with an industrial grade silicone sealant or 
duct seal compound. 

Do not use a cutting 

torch or expose panel to fire. Panel 
damage can occur.

WARNING

La fumée et les flammes peuvent 
endommager le matériel et causesr des 
blessures graves ou la mort.

Avant d’utiliser le dispositif, obturer tous les 
trous de passage de tubulures et de fils 
ménagés dans les panneaux intérieurs et 
extérieurs au moyen d’une pâte à base de 
silicone ou d’un mastic d’étanchéite â 
conduits de qualité industrielle.

Ne pas se servir d’un chalumeau 
coupeur ni exposer les pannequx à une 
flamme nue pour ne pas risquer de les 
endommager.

Cut hole from both sides of panel

Seal completely with silicone 
sealant or duct seal compound

Prop 65—Substances in fuel or from fuel combustion can cause personal injury or death, 
and are known to the State of California to cause cancer, birth defects or other reproductive harm.

D i s c h a r g e

P l e n u m

Summary of Contents for Skyline IM 777-2

Page 1: ...Installation and Maintenance Manual IM 777 2 Skyline Air Handler Group Applied Air Sizes 003 090 Part Number IM 777 Date July 2007 2007 McQuay International...

Page 2: ...ounting 10 Piping Vestibules 10 Piping and Coils 10 Drain Pan Traps 13 Internal Isolation Assembly Adjustment 14 Electrical Installation 14 Operation Guidelines 16 Startup Checks 16 Fan Wheel Alignmen...

Page 3: ...and shaft before unit installation to verify this has not happened Screws bolts etc for assembling sections are supplied in a bag attached to each section All necessary gasketing is applied in the fa...

Page 4: ...12 deep See Figure 2 Figure 1 Servicing Space Requirements Figure 2 Service Clearance for Electrical Power Devices Rigging Skyline air handlers ship as separate sections completely assembled or in mo...

Page 5: ...1 Caulk all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the mating faces of the cabinet Use the splice joint as a guide for applying th...

Page 6: ...flanges Bend the ends of the splice cap down to secure in place 6 Assemble the small splice plate at the top rail to secure the sections together at the top Use 5 16 bolts See Figure 9 Figure 9 Splic...

Page 7: ...quire the use of tools to access compartments containing moving parts or electrical wiring See Figure 11 1 Remove padlock if one is present 2 Insert 1 2 socket into cup and rotate 1 4 turn clockwise a...

Page 8: ...ccur If larger heavier components require mounting on unit panels use through bolts with flat washers through both outer and inner panels To maintain panel integrity seal both ends with an industrial...

Page 9: ...er Between Hoods Mounting Actuators The installing contractor is responsible for the mounting of all field installed actuators No provisions are made for the location of these actuators due to the num...

Page 10: ...cal codes and industry standards Do not apply undue stress at the connection to coil headers always use a backup pipe wrench Support pipework independently of the coils Water Cooling Coils Note Use gl...

Page 11: ...thermostatic or bucket traps for low pressure steam On high pressure steam use bucket traps Use thermostatic traps only for air venting Use bucket traps for on off control only Locate traps at least 1...

Page 12: ...Return main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two position Float and thermostatic tr...

Page 13: ...drain pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the static...

Page 14: ...when adjustments are completed For models 040 through 090 the isolators should be at equal height during fan operation 6 Center the fan outlet in the outlet panel opening If adjustment is required lo...

Page 15: ...vicing Perform lockout tagout procedures to ensure that power can not be energized For variable frequency drives or other energy storing components that have been furnished and mounted by either McQua...

Page 16: ...Can cause property damage personal injury or death Wire fan power supply and ground motor frame in accordance with local electric codes AVERTISSEMENT Risques d incendie et d lectrocution pouvant cause...

Page 17: ...by loosening wheel hub setscrews shifting wheel s axially as needed and retightening setscrews Figure 26 Wheel to Inlet Funnel Relationship Plenum Fans Table 2 Wheel to Inlet Funnel Relationship Airf...

Page 18: ...line Fans Wheel funnel overlap Size Overlap 150 375 165 438 182 562 200 625 222 688 245 750 270 812 300 875 330 1 000 365 1 125 402 1 250 445 1 375 Overlap Table 6 Bearing Collar and Wheel Hub Set Scr...

Page 19: ...56 24 00 Maximum rpm Class I 3000 3000 2300 2000 1700 1500 Maximum rpm Class Il 4335 3918 3457 2858 2427 2255 300 250 200 150 100 90 80 Torque in lb 350 400 450 500 600 650 700 750 800 850 1000 1500...

Page 20: ...ameter 13 5 15 16 5 18 25 20 22 25 24 5 27 30 33 36 5 40 25 44 50 49 54 25 60 Maximum rpm Class I 2895 2589 2376 2256 2077 1875 1691 1479 1328 1209 1073 972 882 799 725 651 Maximum rpm Class II 3786 3...

Page 21: ...t or debris on wheel blades b Loose set screws in wheel hub or bearing to shaft c Wheel distorted from overspeed 2 Bent shaft 3 Drive faulty a Variable pitch sheaves Axial and radial runout of flanges...

Page 22: ...nts Upon completion of the air balance replace the variable pitched motor sheave with a properly sized fixed sheave A matching fixed sheave provides longer belt and bearing life and minimizes vibratio...

Page 23: ...3 Replace external key E and securely tighten setscrews B over key and setscrews C into keyway in fixed half of the sheave 4 Put on belts and adjust belt tension Do not force belts over grooves See F...

Page 24: ...ews E 9 Put on belts and adjust belt tension Do not force belts over grooves See Fan Drive Belt Adjustment on page 26 10 Before starting the drive ensure that all keys are in place and all setscrews a...

Page 25: ...s or 6 turns for the B belts Do not open C sheaves more than 9 1 2 turns Do not open 5V sheaves more than 6 turns Do not open 8V sheaves more than 8 turns 6 Tighten BOTH locking screws A in the outer...

Page 26: ...o N o t R e m o v e I n n e r L o c k i n g R i n g O u t e r L o c k i n g R i n g S p l i t T a p e r B u s h i n g 3 H o l e s f o r S p a n n e r W r e n c h o r D r i f t Belt span Deflection Bel...

Page 27: ...Filter Gauge Table 15 Belt Deflection Force per Browning specifications Cross section Sheave diameter in Deflection force lbs Smallest sheave diameter range rpm range Cross section A B 5V Cross secti...

Page 28: ...ls Removing and Replacing Components See Access Doors and Panels on page 7 for instructions on removing panels and opening fan access doors to remove or replace components Removing the Fan Section The...

Page 29: ...in place with a clamp See Figure 41 1 Disconnect all piping and remove the brass plugs for the vents and drains located in the connections 2 Remove all screws and remove the access panel 3 Remove the...

Page 30: ...ce bolt the coil to the section 4 Caulk the mounting surface of the steel plate and install the plate on the coils 5 Caulk the mounting surface of the drain trough and install the drain trough on the...

Page 31: ...arges must be prepaid The return of the part does not constitute an order for replacement Therefore a purchase order must be entered through the nearest McQuay representative The order should include...

Page 32: ...training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consul...

Reviews: