26

McQuay IM 777-2

Service and Maintenance

Figure 36: Sheave Adjustment

Fan Drive Belt Adjustment

General Rules of Tensioning

1

The ideal tension is the lowest tension at which the belt 
does not slip under peak load conditions.

2

Check tension frequently during the first 24 to 48 hours of 
operation.

3

Over tensioning shortens belt and bearing life.

4

Keep belts free from foreign material that can cause 
slippage.

5

Inspect V-drive on a periodic basis. Adjust tension if the 
belt is slipping. Do not apply belt dressing. This can 
damage the belt and cause early failure.

Tension Measurement Procedure

1

Measure the belt span. See Figure 37.

2

Place belt tension checker squarely on one belt at the center 
of the belt span. Apply force to the checker, perpendicular 
to the belt span, until the belt deflection equals belt span 
distance divided by 64. Determine the force applied while 
in this position.

3

Compare this force to the values in Table 15.

Figure 37: Drive Belt Adjustment

A d j u s t a b l e

C e n t e r - F l a n g e

F i x e d

C e n t e r - F l a n g e

S t a t i o n a r y

E n d - F l a n g e

C a p s c r e w s

( D o   N o t   R e m o v e )

( 2 )   L o c k i n g  

S e t s c r e w s   " A "

F l a t h e a d   S o c k e t   S c r e w s

( D o   N o t   R e m o v e )  

I n n e r   L o c k i n g - R i n g

O u t e r

L o c k i n g - R i n g

S p l i t   T a p e r

B u s h i n g

( 3 )   H o l e s   f o r

S p a n n e r   W r e n c h

o r   D r i f t

Belt span

Deflection =

Belt span

64

WARNING

Moving belt and fan can cause severe personal injury or 
death.

 During installation and filter maintenance:

Verify that the belt and fan guards on plenum fan units are 
always in place.

Lock and tag out fans to prevent accidental start up.

Do not enter the filter compartment until the fan is 
completely stopped.

Use approved equipment for reaching filters located above 
normal reach. Do not step on filter frames or unit 
components.

Floor surfaces must be dry and free of oil or grease.

WARNING

Pendant l’installation et où l’entretien des filtres, une 
courroie en mouvement ou un ventilateur en opération 
peuvent causer des blessures graves où même causer la 
mort.

S’assurer que les gardes de courroie et de ventilateur sont 
toujours en place.

Verouiller les démarreurs des ventilateurs et afficher un 
avis de mise-en-garde afin de prévenir tout accident ou 
démarrage.

Attendre que le ventilateur soit complètement arrêté avant 
d’entrer dans l’unité.

Utiliser seulement des équipements approuvé pour joindre 
les bancs de filtres; ne pas mettre soit sur les cadres des 
filtres ou même sur toutes composantes de l’unité.

La surface des planchers doit être sec et libre de toute 
trace d'huile et où de graisse.

Summary of Contents for Skyline IM 777-2

Page 1: ...Installation and Maintenance Manual IM 777 2 Skyline Air Handler Group Applied Air Sizes 003 090 Part Number IM 777 Date July 2007 2007 McQuay International...

Page 2: ...ounting 10 Piping Vestibules 10 Piping and Coils 10 Drain Pan Traps 13 Internal Isolation Assembly Adjustment 14 Electrical Installation 14 Operation Guidelines 16 Startup Checks 16 Fan Wheel Alignmen...

Page 3: ...and shaft before unit installation to verify this has not happened Screws bolts etc for assembling sections are supplied in a bag attached to each section All necessary gasketing is applied in the fa...

Page 4: ...12 deep See Figure 2 Figure 1 Servicing Space Requirements Figure 2 Service Clearance for Electrical Power Devices Rigging Skyline air handlers ship as separate sections completely assembled or in mo...

Page 5: ...1 Caulk all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the mating faces of the cabinet Use the splice joint as a guide for applying th...

Page 6: ...flanges Bend the ends of the splice cap down to secure in place 6 Assemble the small splice plate at the top rail to secure the sections together at the top Use 5 16 bolts See Figure 9 Figure 9 Splic...

Page 7: ...quire the use of tools to access compartments containing moving parts or electrical wiring See Figure 11 1 Remove padlock if one is present 2 Insert 1 2 socket into cup and rotate 1 4 turn clockwise a...

Page 8: ...ccur If larger heavier components require mounting on unit panels use through bolts with flat washers through both outer and inner panels To maintain panel integrity seal both ends with an industrial...

Page 9: ...er Between Hoods Mounting Actuators The installing contractor is responsible for the mounting of all field installed actuators No provisions are made for the location of these actuators due to the num...

Page 10: ...cal codes and industry standards Do not apply undue stress at the connection to coil headers always use a backup pipe wrench Support pipework independently of the coils Water Cooling Coils Note Use gl...

Page 11: ...thermostatic or bucket traps for low pressure steam On high pressure steam use bucket traps Use thermostatic traps only for air venting Use bucket traps for on off control only Locate traps at least 1...

Page 12: ...Return main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two position Float and thermostatic tr...

Page 13: ...drain pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the static...

Page 14: ...when adjustments are completed For models 040 through 090 the isolators should be at equal height during fan operation 6 Center the fan outlet in the outlet panel opening If adjustment is required lo...

Page 15: ...vicing Perform lockout tagout procedures to ensure that power can not be energized For variable frequency drives or other energy storing components that have been furnished and mounted by either McQua...

Page 16: ...Can cause property damage personal injury or death Wire fan power supply and ground motor frame in accordance with local electric codes AVERTISSEMENT Risques d incendie et d lectrocution pouvant cause...

Page 17: ...by loosening wheel hub setscrews shifting wheel s axially as needed and retightening setscrews Figure 26 Wheel to Inlet Funnel Relationship Plenum Fans Table 2 Wheel to Inlet Funnel Relationship Airf...

Page 18: ...line Fans Wheel funnel overlap Size Overlap 150 375 165 438 182 562 200 625 222 688 245 750 270 812 300 875 330 1 000 365 1 125 402 1 250 445 1 375 Overlap Table 6 Bearing Collar and Wheel Hub Set Scr...

Page 19: ...56 24 00 Maximum rpm Class I 3000 3000 2300 2000 1700 1500 Maximum rpm Class Il 4335 3918 3457 2858 2427 2255 300 250 200 150 100 90 80 Torque in lb 350 400 450 500 600 650 700 750 800 850 1000 1500...

Page 20: ...ameter 13 5 15 16 5 18 25 20 22 25 24 5 27 30 33 36 5 40 25 44 50 49 54 25 60 Maximum rpm Class I 2895 2589 2376 2256 2077 1875 1691 1479 1328 1209 1073 972 882 799 725 651 Maximum rpm Class II 3786 3...

Page 21: ...t or debris on wheel blades b Loose set screws in wheel hub or bearing to shaft c Wheel distorted from overspeed 2 Bent shaft 3 Drive faulty a Variable pitch sheaves Axial and radial runout of flanges...

Page 22: ...nts Upon completion of the air balance replace the variable pitched motor sheave with a properly sized fixed sheave A matching fixed sheave provides longer belt and bearing life and minimizes vibratio...

Page 23: ...3 Replace external key E and securely tighten setscrews B over key and setscrews C into keyway in fixed half of the sheave 4 Put on belts and adjust belt tension Do not force belts over grooves See F...

Page 24: ...ews E 9 Put on belts and adjust belt tension Do not force belts over grooves See Fan Drive Belt Adjustment on page 26 10 Before starting the drive ensure that all keys are in place and all setscrews a...

Page 25: ...s or 6 turns for the B belts Do not open C sheaves more than 9 1 2 turns Do not open 5V sheaves more than 6 turns Do not open 8V sheaves more than 8 turns 6 Tighten BOTH locking screws A in the outer...

Page 26: ...o N o t R e m o v e I n n e r L o c k i n g R i n g O u t e r L o c k i n g R i n g S p l i t T a p e r B u s h i n g 3 H o l e s f o r S p a n n e r W r e n c h o r D r i f t Belt span Deflection Bel...

Page 27: ...Filter Gauge Table 15 Belt Deflection Force per Browning specifications Cross section Sheave diameter in Deflection force lbs Smallest sheave diameter range rpm range Cross section A B 5V Cross secti...

Page 28: ...ls Removing and Replacing Components See Access Doors and Panels on page 7 for instructions on removing panels and opening fan access doors to remove or replace components Removing the Fan Section The...

Page 29: ...in place with a clamp See Figure 41 1 Disconnect all piping and remove the brass plugs for the vents and drains located in the connections 2 Remove all screws and remove the access panel 3 Remove the...

Page 30: ...ce bolt the coil to the section 4 Caulk the mounting surface of the steel plate and install the plate on the coils 5 Caulk the mounting surface of the drain trough and install the drain trough on the...

Page 31: ...arges must be prepaid The return of the part does not constitute an order for replacement Therefore a purchase order must be entered through the nearest McQuay representative The order should include...

Page 32: ...training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consul...

Reviews: