background image

6

McQuay IM 777-1

Installation Guidelines

3

Seal the double-wall panel on each side with an industrial/
commercial grade silicone sealant or duct seal compound. 
It is extremely important to seal each panel hole or 
penetration securely so it is airtight and watertight and 
there is NO EXPOSED FOAM INSULATION.

Figure 11: Cutting and sealing injected-foam insulated panels

Field Mounting Junction Boxes and Other 
Components

For field mounting 4" × 4" or smaller junction boxes to the 
standard panel exterior, use a minimum quantity of 4, 3/16" 
diameter pop rivets. 

Do NOT use self-tapping drill screws. 

They will not tighten nor secure properly and panel 
damage can occur.

If larger, heavier components require mounting on unit panels, 
use through-bolts with flat washers through both outer and 

inner panels. To maintain panel integrity, seal both ends with 
an industrial/commercial grade silicone sealant or duct seal 
compound.

The unit frame channel is another excellent location for 
securing heavier components; self-tapping screws are not 
acceptable. Ensure that the location permits the full operation 
of all access doors and panels and does not interfere with other 
vital components.

Duct Connections

Use flexible connectors on the outlet and inlet duct connections 
of all units. Do not position down flow fans over air ducts that 
are routed down into the building. Use a discharge plenum 
when bottom connections are necessary. See Figure 12

.

Figure 12: Discharge plenum

If the unit has a top mixing box or economizer damper or a top 
duct connection, field fabricate and install flashing to divert 
moisture from the connection. The flashing must lap over the 
standing seams of the top panels. The flashing also must lap 
over the side edges of the unit. See Figure 13

.

Figure 13: Flashing over top panels and sides of units

WARNING

Flame and smoke can cause equipment 
damage, severe personal injury, or 
death.

Before operating unit, seal all piping and 
wiring holes on both inner and outer panels 
with an industrial grade silicone sealant or 
duct seal compound. 

Do not use a cutting 

torch or expose panel to fire

. Panel 

damage can occur.

WARNING

La fumée et les flammes peuvent 
endommager le matériel et causesr des 
blessures graves ou la mort.

Avant d’utiliser le dispositif, obturer tous les 
trous de passage de tubulures et de fils 
ménagés dans les panneaux intérieurs et 
extérieurs au moyen d’une pâte à base de 
silicone ou d’un mastic d’étanchéite â 
conduits de qualité industrielle.
Ne pas se servir d’un chalumeau coupeur ni 
exposer les pannequx à une flamme nue 
pour ne pas risquer de les endommager.

Cut hole from both sides of panel

Seal completely with silicone 
sealant or duct seal compound

Prop 65—Substances in fuel or from fuel combustion can cause personal injury or death, 
and are known to the State of California to cause cancer, birth defects or other reproductive harm.

D i s c h a r g e

P l e n u m

F l a s h i n g

D u c t

F l a s h i n g

U n i t   t o p

p a n e l

F l a s h i n g

D u c t

F l a s h i n g

Summary of Contents for Skyline IM 777-1

Page 1: ...McQuay IM 782 1 1 Installation and Maintenance Manual IM 777 1 Group Applied Air Part Number IM 777 Date June 2005 2005 McQuay International Skyline Air Handler Sizes 003 090...

Page 2: ...ater Cooling Coils 8 Direct Expansion Coils 8 Steam Coils see Figure 18 on page 10 9 Water Heating Coils 11 Drain Pan Traps 11 Internal Isolation Assembly Adjustment 12 Electrical Installation 13 Oper...

Page 3: ...fore unit installation to verify this has not happened 4 Screws bolts etc for assembling sections are supplied in a bag attached to each section All necessary gasketing is applied in the factory for s...

Page 4: ...igure 2 Figure 1 Servicing space requirements Figure 2 Service clearance for electrical power devices Rigging Skyline air handlers ship as separate sections completely assembled or in modules of assem...

Page 5: ...all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the mating faces of the cabinet Use the splice joint as a guide for applying the sealan...

Page 6: ...slip the splice cap over the top panel flanges Bend the ends of the splice cap down to secure in place 6 Assemble the small splice plate at the top rail to secure the sections together at the top Use...

Page 7: ...the jam nuts Figure 10 Opening fan section door Injected Foam Insulated Panels Skyline air handlers now are furnished with double wall injected foam insulated panels Foam panels are stronger more rig...

Page 8: ...ctions are necessary See Figure 12 Figure 12 Discharge plenum If the unit has a top mixing box or economizer damper or a top duct connection field fabricate and install flashing to divert moisture fro...

Page 9: ...same actuator if the dampers are the same size If the dampers are different sizes they must be driven by separate actuators and controlled appropriately Exhaust dampers are always driven by a separate...

Page 10: ...e coils to freezing temperatures Water supply water return drain and vent connections extend through the end panel of the coil section All connections are labeled on the end panel Water supply and wat...

Page 11: ...Use thermostatic traps only for air venting Use bucket traps for on off control only Locate traps at least 12 inches below the coil return connection Multiple coil installation Individually trap each...

Page 12: ...aker 1 2 check valve Steam main Return main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two po...

Page 13: ...n pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the static pre...

Page 14: ...he cap screw when adjustments are completed For models 040 through 090 the isolators should be at equal height during fan operation 6 Center the fan outlet in the outlet panel opening If adjustment is...

Page 15: ...m of the fan motor junction box See Figure 22 Figure 22 Electrical conduit location CAUTION The base section of each cabinet has a drip pan installed below every panel that drains to the outside frame...

Page 16: ...t m me la mort L alimentation lectrique du moteur du ventilateur de m me que la mise la terre du ch ssis du moteur doivent tre faits conform ment aux codes d nstallations lectriques en vigueur WARNING...

Page 17: ...wheel s axially as needed and retightening setscrews 3 To obtain dimension B loosen screw and washer fasteners around periphery of funnel s shifting funnel radially as required and re torquing fastene...

Page 18: ...5 440 24 5 500 27 560 30 620 33 750 36 5 810 40 25 880 44 5 940 49 1 000 54 25 1 060 60 1 120 Overlap Table 5 Wheel to inlet funnel relationship inline fans Wheel funnel overlap Size Overlap 150 375 1...

Page 19: ...1 56 24 00 Maximum rpm Class I 3000 3000 2300 2000 1700 1500 Maximum rpm Class Il 4335 3918 3457 2858 2427 2255 300 250 200 150 100 90 80 Torque in lb 350 400 450 500 600 650 700 750 800 850 1000 1500...

Page 20: ...00 AF30 00 500 600 700 800 2000 1000 1500 1500 2000 3000 2500 Torque in lb Table 9 Operating limits plenum fans Fan operating limits Plenum fans Diameter 13 5 15 16 5 18 25 20 22 25 24 5 27 30 33 36...

Page 21: ...ble pitch sheaves Axial and radial runout of flanges uneven groove spacing out of balance Also similar faults in driven sheave b Bad V belts lumpy or mismatched belt tension too tight or too loose 4 B...

Page 22: ...the air balance replace the variable pitched motor sheave with a properly sized fixed sheave A matching fixed sheave provides longer belt and bearing life and minimizes vibration Initially it is best...

Page 23: ...number of turns from closed position 7 Verify that all keys are in place and that all se screws are tight before starting drive Check setscrews and belt tension after 24 hours service Figure 32 VP typ...

Page 24: ...t on page 24 9 Before starting the drive ensure that all keys are in place and all setscrews and all capscrews are tight Check and retighten all screws and retension belts after approximately 24 hours...

Page 25: ...hs L less than dia Seating torque Seating torque Seating torque Seating torque Length L Seating torque in lbs in lbs in lbs in lbs in lbs in lbs in lbs 1 4 20NC 150 12 5 100 87 7 3 3 16 50 5 16 11NC 3...

Page 26: ...oving belt and fan can cause severe personal injury or death During installation and filter maintenance Verify that the belt and fan guards on plenum fan units are always in place Lock and tag out fan...

Page 27: ...Filter gauge Table 15 Belt deflection force per Browning specifications Cross section Sheave diameter in Deflection force lbs Smallest sheave diameter range rpm range Cross section A B 5V Cross secti...

Page 28: ...reezing of coils Removing and Replacing Components See Access Doors and Panels on page 5 for instructions on removing panels and opening fan access doors to remove or replace components Removing the F...

Page 29: ...s See Figure 39 5 If this is an additional coil being installed and not a replacement locate the coil supply and return connections dimensionally Carefully drill holes in the end panels of the unit 6...

Page 30: ...and remove the brass plugs for the vents and drains located in the connections 2 To access bolts holding the coils in place remove the panels on both the connection and opposite connection end of the...

Page 31: ...must be prepaid The return of the part does not constitute an order for replacement Therefore a purchase order must be entered through the nearest McQuay representative The order should include part...

Page 32: ...30 McQuay IM 777 1...

Page 33: ...McQuay IM 777 1 31...

Page 34: ...32 McQuay IM 777 1...

Page 35: ......

Page 36: ...ipment its care should be a high priority For training information on all McQuay HVAC products please visit us at www mcquay com and click on training or call 540 248 9646 and ask for the Training Dep...

Reviews: