b) Ensure that the compressor is not expose to open air for more than the recommended time
specified by its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when
the compressor is about to be brazed.
c) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level
is more stringent than R22 system so as to ensure no incompressible gas and moisture in the
system.
d) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is
to ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
R32/R125/R134
33% / 33% / 34%
23% / 25% / 52%
Composition of R407C in vapour phase
is different from liquid phase.
e) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal.
However, if the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the
valve at the bottom.
Dip-pipe
Invert cylinder
without dip-pipe
Liquid
withdrawal
f) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended
for R407C system. Unlike R22 where the refrigerant is of a single component, the composition of
R407C, which made-up of three different components, may have changed during the leak.
Consequently, a top-up may not ensure that the R407C in the system is of original composition.
This composition shift may adversely affect the system performance. It is recommended that the
system should be evacuated thoroughly before recharging with R407C.
71
Summary of Contents for MWM 007F
Page 37: ...MWM 007F FR NC Curves MWM 010F FR NC Curves 35...
Page 38: ...36 MWM 015F FR NC Curves MWM 020F FR NC Curves...
Page 39: ...MWM 025F FR NC Curves MWM 030F 030FR NC CURVES 37...
Page 43: ...Indoor Unit Model MWM 010F 010FR 015F 015FR Outdoor Unit Model MLC 010C 010CR 015C 015CR 41...
Page 45: ...43 Model MLC 030B Model MLC M4LC 030C...
Page 46: ...Heatpump Models Model M4LC 007BR 010BR MLC 010CR Model M4LC 015BR 44...
Page 47: ...Model MLC 015CR Model MLC M4LC 020BR 45...
Page 48: ...Model MLC M4LC 025BR MLC 030BR Model MLC M4LC 030CR 46...
Page 52: ...Outdoor Unit Model MLC 030B Indoor Unit Model MWM 030F D2 0 I C 50 1 PHASE 220 240V 50Hz...
Page 53: ...Indoor Unit Model MWM 030F D2 01 C Outdoor Unit Model MLC M4LC 030C 51...
Page 54: ...Indoor Unit Model MWM 030F D2 01 C Outdoor Unit Model MLC M4LC 030C 52...
Page 55: ...Indoor Unit Model MWM 015F D2 0 I C Outdoor Unit Model MLC 015C 1 PHASE 220 240V 50 Hz 53...
Page 56: ...Indoor Unit Model MWM 010F D2 0 I C 1 PHASE 220 240V 50 Hz Outdoor Unit Model MLC 010C 54...
Page 60: ...Indoor Unit Model MWM 030FR U1 4 1 C Outdoor Unit Model MLC M4LC 030CR 58...
Page 61: ...59 Indoor Unit Model MWM 030FR U1 4 1 C Outdoor Unit Model MLC M4LC 030CR...
Page 62: ...Indoor Unit Model MWM 030FR U1 4 I C Outdoor Unit Model MLC 30BR 1 PHASE 220 240V 50HZ 60...
Page 63: ...Indoor Unit Model MWM 010FR U1 4 I C Outdoor Unit Model MLC 010CR 61...
Page 64: ...Indoor Unit Model MWM 015FR U1 4 I C 1 PHASE 220 240V 50 Hz Outdoor Unit Model MLC 015CR 62...
Page 74: ...Installa Installa Installa Installa Installation tion tion tion tion Installation Diagram 72...
Page 108: ...2005 McQuay International 1 800 432 1342 www mcquay com...