8) Refrigerant Piping
Maximum Pipe Length And Maximum Number Of Bends
Always choose the shortest path for refrigerant piping and follow the recommendations as tabulated below:
* Need to add external accumulator
Flare Connection
•
Cut the pipe stages by stages, advancing the blade of pipe cutter slowly.
•
Remove burr with the burr remover. Hold the flaring end down to prevent burrs from dropping inside pipe.
•
The exact length of pipe protruding from the face of the flare die is determined by the flaring tool. The
table shows the use of an imperial die and riged die.
Fix the pipe firmly on the flare die. Match the centers of both the flare die and the flaring punch, and tighten
flaring punch fully.
9) Vacuuming And Charging
•
The precharged outdoor unit does not need any vacuuming or charging. However once it is connected,
the connecting pipe line and the indoor need to be vacuumed before releasing the R22/R407C from the
outdoor unit.
1) Open the service port core cap.
2) Connect pressure gauge to the service port.
3) Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum
to - 0.1 MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).
81
INDOOR UNIT
Flare Joint
Flare Valve
OUTDOOR UNIT
CHARGE SET
VACUUM PUMP
A(mm)
PIPE
∅
, D (mm)
IMPERIAL DIE
RIGID DIE
6.35(1/4”) 1.3 0.7
9.52(3/8”) 1.6 1.0
12.7(1/2”) 1.9 1.3
15.88(5/8”) 2.2 1.7
MWM 030F/FR
MODEL
DATA
MWM
010F/FR
MWM
015F/FR
MWM
020F/FR
MWM
025F/FR
MLC 030B/BR
MLC 030C/CR
Max. Length (m)
12
12
15
15
35
45
Max. Elevation (m)
5
5
8
8
15
25
Max. No of bends
10
10
10
10
10
10
Summary of Contents for MWM 007F
Page 37: ...MWM 007F FR NC Curves MWM 010F FR NC Curves 35...
Page 38: ...36 MWM 015F FR NC Curves MWM 020F FR NC Curves...
Page 39: ...MWM 025F FR NC Curves MWM 030F 030FR NC CURVES 37...
Page 43: ...Indoor Unit Model MWM 010F 010FR 015F 015FR Outdoor Unit Model MLC 010C 010CR 015C 015CR 41...
Page 45: ...43 Model MLC 030B Model MLC M4LC 030C...
Page 46: ...Heatpump Models Model M4LC 007BR 010BR MLC 010CR Model M4LC 015BR 44...
Page 47: ...Model MLC 015CR Model MLC M4LC 020BR 45...
Page 48: ...Model MLC M4LC 025BR MLC 030BR Model MLC M4LC 030CR 46...
Page 52: ...Outdoor Unit Model MLC 030B Indoor Unit Model MWM 030F D2 0 I C 50 1 PHASE 220 240V 50Hz...
Page 53: ...Indoor Unit Model MWM 030F D2 01 C Outdoor Unit Model MLC M4LC 030C 51...
Page 54: ...Indoor Unit Model MWM 030F D2 01 C Outdoor Unit Model MLC M4LC 030C 52...
Page 55: ...Indoor Unit Model MWM 015F D2 0 I C Outdoor Unit Model MLC 015C 1 PHASE 220 240V 50 Hz 53...
Page 56: ...Indoor Unit Model MWM 010F D2 0 I C 1 PHASE 220 240V 50 Hz Outdoor Unit Model MLC 010C 54...
Page 60: ...Indoor Unit Model MWM 030FR U1 4 1 C Outdoor Unit Model MLC M4LC 030CR 58...
Page 61: ...59 Indoor Unit Model MWM 030FR U1 4 1 C Outdoor Unit Model MLC M4LC 030CR...
Page 62: ...Indoor Unit Model MWM 030FR U1 4 I C Outdoor Unit Model MLC 30BR 1 PHASE 220 240V 50HZ 60...
Page 63: ...Indoor Unit Model MWM 010FR U1 4 I C Outdoor Unit Model MLC 010CR 61...
Page 64: ...Indoor Unit Model MWM 015FR U1 4 I C 1 PHASE 220 240V 50 Hz Outdoor Unit Model MLC 015CR 62...
Page 74: ...Installa Installa Installa Installa Installation tion tion tion tion Installation Diagram 72...
Page 108: ...2005 McQuay International 1 800 432 1342 www mcquay com...