![McQuay MicroTech 200 Series Operating Manual Download Page 38](http://html1.mh-extra.com/html/mcquay/microtech-200-series/microtech-200-series_operating-manual_1756112038.webp)
38
OM 200MICRO
Alarm Menus Description
Press the "ALARM" key under the 'Category Group' and menu 27
(Alarms)
will be displayed. Menus
27-35 are the alarm menus.
Menu 27 has four screens. This menu is a display and does not require a password. The values
displayed indicate the current alarm and the conditions at the time the alarm reported. When another
alarm reports the values in this menu will be shifted to menu 28
(Alarm Buffer #1)
. Each time another
alarm reports the alarms are shifted and the alarm buffers #1-#8
(Menu 28-35)
are filled. The oldest
alarm will be removed from memory. This allows for the current alarm and eight
(8)
previous alarms to
be recorded for troubleshooting purposes.
Menu 27, Current Alarm
Item
Screen
Line
Display
Field
Range
Extended Name
No Active Alarms
1
Alarm Status Table
Current Alarm
At 0:00
2
00:23-23:59
Time of Alarm
1
On N/A-00
3
Jan-Dec/01-31
Date of Alarm
Unit Status
1
Alarm Status Table
Unit Operating Mode at Alarm
2
Ent Evap=xxx.x°F
2
Ent Evap Chw Temp at Alarm
Motor Current=xxx%
1
0-100%
Percent RLA at Alarm
1
3
Lvg Evap=xxx.x°F
2
Lvg Evap Chw Temp at Alarm
Ent cond=xxx.x°F
1
Ent Cond Water Temp at Alarm
1
Cond=xxx.xpsi
2
Cond Refrigerant Press at Alarm
Lvg Cond=xxx.x°F
1
Lvg Cond Water Temp at Alarm
2
Evap Aprch=xxx.x°F
2
Evap Approach at Alarm
Evap=xx.xpsi
1
Evap Refrigerant Press at Alarm
2
3
Cond Aprch=xxx.x°F
2
Cond Approach at Alarm
Dischange=xxx.x°F
1
Discharge Temp at Alarm
1
Subcool=xxx.x°F
2
Subcooling at Alarm
Dsch Suprht=xxx.x°F
1
Discharge Superheat at Alarm
2
Sump Temp=xxx.x°F
2
Oil Sump Temp at Alarm
Suct Suprhtxxx.x°F
1
Suction Superheat at Alarm
3
3
Feed Tempxxx.x°F
2
Oil Feed Temp at Alarm
1
Feed Press=xx.xpsi
1
Oil Feed Pressure at Alarm
2
Evap Flow=xxxxgpm
1
Evaporator Water Flow at Alarm
4
3
Cond Flow=xxxxgpm
1
Condenser Water Flow at Alarm
Press the "NEXT MENU" key and menu 28
(Alarm Buffer #1)
will be displayed. Menu 28 has four
screens. This menu is a display and does not require a password. This is the first of eight alarm
buffers. The information displayed can provide troubleshooting information.
Menu 28, Alarm Buffer #1
Item
Screen
Line
Display
Field
Range
Extended Name
No Active Alarms
1
Alarm Status Table
Current Alarm
At 0:00
2
00:23-23:59
Time of Alarm
1
On N/A-00
3
Jan-Dec/01-31
Date of Alarm
Unit Status
1
Alarm Status Table
Unit Operating Mode at Alarm
2
Ent Evap=xxx.x°F
2
Ent Evap Chw Temp at Alarm
Motor Current=xxx%
1
0-100%
Percent RLA at Alarm
1
3
Lvg Evap=xxx.x°F
2
Lvg Evap Chw Temp at Alarm
Ent cond=xxx.x°F
1
Ent Cond Water Temp at Alarm
1
Cond=xxx.xpsi
2
Cond Refrigerant Press at Alarm
Lvg Cond=xxx.x°F
1
Lvg Cond Water Temp at Alarm
2
Evap Aprch=xxx.x°F
2
Evap Approach at Alarm
Evap=xx.xpsi
1
Evap Refrigerant Press at Alarm
2
3
Cond Aprch=xxx.x°F
2
Cond Approach at Alarm
Dischange=xxx.x°F
1
Discharge Temp at Alarm
1
Subcool=xxx.x°F
2
Subcooling at Alarm
Dsch Suprht=xxx.x°F
1
Discharge Superheat at Alarm
2
Sump Temp=xxx.x°F
2
Oil Sump Temp at Alarm
Suct Suprhtxxx.x°F
1
Suction Superheat at Alarm
3
3
Feed Tempxxx.x°F
2
Oil Feed Temp at Alarm
4
1
Feed Press=xx.xpsi
1
Oil Feed Pressure at Alarm