36
OM 200MICRO
Basic Chiller Setup
Press the "NEXT MENU" key and menu 26
(Unit Setup)
will be displayed. Menu 26 has three
screens. This menu is password protected and requires the operator password. Changing the values
in this menu can cause network communications failure.
There are several menus that require resetting the default values for proper unit operation. The setup
procedure will be performed by the startup technician and the information should be recorded for
future use. This following procedure will show how to setup a single compressor
(WSC)
stand-alone
unit without a network.
Set the toggle switch on the face of the MicroTech panel to the stop position. Press the "ALARM"
key under the Category group. This brings up menu 27. Press the "PREV. MENU" key and menu 26
will be displayed. Menu 26 should be the first menu to be modified because the information entered
affects other menus. The following will be in the sequence displayed on the screen. The values
entered will depend upon the unit and the information required should be obtained and recorded
before an attempt is made at inputting the data.
Menu 26, Unit Setup
Item
Screen
Line
Display
Field
Range
Extended Name
IDENT=CFG3E04I
1
Software Version
WSC048
WSC050
WSC063
WSC079
WSC087
WSC100
1
Unit Type=WSC063
2
WSC126
Chiller Model Number
L1-TTY-Master
L1-TTY-TTY
L2-Master-Slave
L2-TTY-Slave
Config=L2 TTY-Slave
1
L3-TTY-Slave
Unit Controller Configuration
Chiller
2
Chiller Only
2
Templifier
Chiller Control Options
1200
2400
4800
Port A Baud =9600
1
9600
Port A Comm Rate
1
3
Low Temperature=No
2
No-Yes
Ice Operation
Master
Master/Slave=Slave
1
Slave
Network Configuration
1
Evap Gpm Sensor=No
2
Yes-No
Evaporator Flow Transmitter
None
Local
OAT Sensor=None
1
Remote
Location of OAT
2
Evap Full Gpm=6500
2
0-65535
Maximum Flow Rate
Ambient Lockout=No
1
Yes-No
Lockout on OAT
2
3
Cond Gpm Sensor=No
2
Yes-No
Condenser Flow Transmitter
Cond Full Gpm=6500
1
0-65535
Maximum Flow Rate
Valve
1
Oil Cooler=Solenoid
2
Solenoid
Oil Cooler Control Method
Refrig Leak Sen=No
1
Yes-No
Refrigerant Leak Sensor Signal
2
Full Load Amp=300
2
0-65535
Chiller RLA
3
3
Ht Recovery Sen=No
1
Yes-No
Heat Recovery Temp Sensor
Unit Type=
This value is the chiller unit model number. The MicroTech has different look up tables
depending on the type of chiller.
Ident=
This is the MicroTech software identification.
Config=
This defines the network communication link, com port type and MicroTech controller level.
The first field indicates the controller's network hierarchy. The second field indicates Port A's
protocol. TTY is equal to the RS232 type and Master/Slave is equal to the RS 485 type.
Chiller
= This value defines the chiller as a cooling only unit
(only)
or templifier unit.