c) Ensure that the compressor is not exposed to open air for more than the recommended time
specified by its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the
compressor is about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
23% / 25% / 52%
33% / 33% / 34%
R32/R125/R134
Composition of R407C in vapor
phase is different from liquid phase.
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
Liquid
withdrawal
Invert cylinder
without dip-pipe
Dip-pipe
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
73
Summary of Contents for MCK 010C
Page 19: ...CK20B BR NC Curves CK15B BR NC Curves 18...
Page 20: ...CK30B BR NC Curves CK25B BR NC Curves 19...
Page 44: ...Outdoor Unit MLC030 040 050C CR M4LC030 040 050C CR 43...
Page 46: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC030B 45...
Page 47: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC M4LC030C 46...
Page 48: ...Indoor Unit Cooling Only Model MCK040A Outdoor Unit Model MLC035C 47...
Page 49: ...Indoor Unit Cooling Only Model MCK040 050A Outdoor Unit Model MLC M4LC040 050C 48...
Page 51: ...Indoor Unit Heat Pump Model MCK030AR Outdoor Unit Model MLC030BR 50...
Page 52: ...Indoor Unit Heat Pump Model MCK030AR M4LC030CR Outdoor Unit Model MLC 51...
Page 53: ...Indoor Unit Heat Pump Model MCK040AR Outdoor Unit Model MLC035CR 52...
Page 54: ...Indoor Unit Heat Pump Model MCK040 050AR Outdoor Unit Model MLC M4LC040 050CR 53...
Page 55: ...Indoor Unit Cooling Only Model MCK015B Outdoor Unit Model MLC015B 54...
Page 56: ...Indoor Unit Cooling Only Model MCK020 025B Outdoor Unit Model MLC020 025B 55...
Page 57: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030C 56...
Page 58: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030B 57...
Page 59: ...Indoor Unit Heat Pump Model MCK015BR Outdoor Unit Model MLC015BR 58...
Page 60: ...Indoor Unit Heat Pump Model MCK020 025BR Outdoor Unit Model MLC020 025BR 59...
Page 61: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030BR 60...
Page 62: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030CR 61...
Page 63: ...Indoor Unit Cooling Only Model MCK010 015C Outdoor Unit Model MLC010 015B 62...
Page 64: ...Indoor Unit Cooling Only Model MCK020C Outdoor Unit Model MLC020B 63...
Page 100: ...Fresh Air Kit for MCK C Models 99...
Page 101: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...