0
12.
Status Indicator Light
(Lt 0, 1, 2)
0 = Status indicator never on
1 = Status indicator on with first stage
2 = Status indicator on with second stage
Press the or button to select.
Note:
Red light indicates heating cycle and green light indicates cooling cycle.
Slide the
Mode
switch to
Heat
or
Cool
to exit configuration.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
10.
Room temperature offset
(+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Note:
When not set to 0,
ROOM
will display
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
11.
Maximum compressor cycles allowed per hour
(-, 2-6)
- = as many as needed, and 2-6 = maximum cycles/hour
Press the or button to select.
Press the
SW6
button to advance to the next screen.
9.
Maximum Heat Setpoint
(55°F to 90°F) (13°C to 32°C)
Adjust to control the maximum Heat set temperature allowed.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE