IM702-3
4
General Information
This manual contains the information you need to install the communication modules and incorporate it into the network,
and maintain it.
!
WARNING
Electric shock hazard. Can cause personal injury or equipment damage.
This equipment must be properly grounded. Connections and service to the MicroTech II
control panel must be
performed only by personnel who are knowledgeable in the operation of the equipment being controlled.
!
CAUTION
Static sensitive components. Can cause equipment damage.
Discharge any static electrical charge by touching the bare metal inside the control panel before performing any
service work. Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel.
NOTICE
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance
with this instruction manual, may cause interference to radio communications. It has been tested and found to comply
with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his or her own expense. McQuay International disclaims any liability resulting
from any interference or for the correction thereof.
Description
A MicroTech II LonWorks Communications Module provides the interface between a MicroTech II unit controller and a
LonWorks Local Operating Network (LON). It translates the LonTalk variables used on the network to the variables used in
the unit controller and vice versa. Two versions are available: one in accordance with the LonMark Space Comfort Control
(SCC) Functional Profile and one in accordance with the LonMark Discharge Air Control (DAC) Functional Profile.
Profiles are interpreted in loaded programs (firmware). Each profile is interpreted in a separate MicroTech II LonWorks
Communications Module. This manual covers both.
Each MicroTech II LonWorks Communications Module is a printed circuit board that plugs onto the MicroTech II Main
Control Board. Figure 1 is an outline drawing with dimensions of a printed circuit board.
Figure 1. MicroTech II LonWorks Communications Module
0.250
6.750
0.250
3.750