McQuay IM 702-3 Installation And Maintenance Manual Download Page 14

14

IM702-3

Doubly Terminated Topology Restrictions

The restrictions on doubly-terminated bus topology are as follows:

1.

The maximum number of nodes per segment is 64.

2.

The maximum total bus length depends on the wire size (see Qualified Cables for details)

Wire Size

Maximum Cable Length

24 AWG

2952 ft (900 m)

22 AWG

4590 ft (1400 m)

16 AWG

8855 ft (2700 m)

3. The maximum stub length is 9.8 ft (3 m). The length of the cable harness stub is 7.2 ft (2.19 m).

Note: 

A stub is a piece of cable that is wired between the node and the bus.  See Figure 9. Note that if the bus is wired
directly to the node, there is no stub, and thus the stub length is zero. If you are wiring to a field terminal strip on a
unit, be sure to account for any factory wiring between the terminal strip and the controller. This wiring is
considered part of the stub.

4. Two terminations are required in each segment. One must be located at each end of the bus.

Physical Network

Qualified Cables

Echelon has qualified three twisted-pair network communications cables that are available from a large number of different
sources. Refer to Echelon LonWorks FTT-10A Free Topology Transceiver Users Guide. See Reference Documents for part
number. Some local codes or applications may require the use of plenum rated cable. The following cables meet this
specification.
1.

TIA568A Category 5 cable (24AWG/0.51mm)

2.

NEMA Level IV cable (22AWG/0.65mm)

3.

Generic 16AWG (1.3mm) (similar to Belden 85102)

Do not install the cable in the same conduit with power wiring. The temperature of the cable must not exceed 131

°

F (55

°

C).

Note: 

Ideally, you should connect two controllers with one continuous piece of cable in order to reduce the risk of com-
munications errors. If you must splice the cable, use crimp-type butt connectors (good) or solder (best).  Do not
use wire nuts.

Network Cable Termination

LonWorks network segments require termination for proper data transmission performance. The type and number of
terminations depend on network topology.  Refer to Echelon LonWorks FTT-10A Transceiver User’s Guide. See Echelon’s
Reference Documents for part number.

Addressing and Establishing Communications

LonWorks Network Addressing

Every Neuron Chip has a unique 48-bit Neuron ID or physical address. This address is generally used only at initial
installation or for diagnostic purposes. For normal network operation, a device address is used.

Device addresses are defined at the time of network configuration. All device addresses have three parts. The first part is the
Domain ID, designating the domain. Devices must be in the same domain in order to communicate with each other. The
second part is the Subnet ID that specifies a collection of up to 127 devices that are on a single channel or a set of channels
connected by repeaters. There may be up to 255 subnets in a domain. The third part is the Node ID that identifies an
individual device within the subnet.

A group is a logical collection of devices within a domain. Groups are assembled with regard for their physical location in
the domain. There may be up to 256 groups in a domain. A group address is the address that identifies all devices of the
group. There may be any number of devices in a group when unacknowledged messaging is used. Groups are limited to 64
devices if acknowledged messaging is used.

A broadcast address identifies all devices within a subnet or domain.

Summary of Contents for IM 702-3

Page 1: ...s module into the unit and connect the unit to your network You also need the appropriate McQuay Engineering Data Sheet known as the Protocol Data Packet to integrate the unit into your network The Pr...

Page 2: ...7 Integration 12 Network Connection 12 Network Topology 12 Free Topology Networks 12 Free Topology Restrictions 13 Doubly Terminated Networks 13 Doubly Terminated Topology Restrictions 14 Addressing a...

Page 3: ...MicroTech II Vertical Self Contained Unit Controller Installation Manual OM711 McQuay International MicroTech II Vertical Self Contained Discharge Air Controller Operation Manual OM712 McQuay Internat...

Page 4: ...protection against harmful interference when the equipment is operated in a commercial environment Operation of this equipment in a residential area is likely to cause harmful interference in which c...

Page 5: ...ce Documents for part numbers Figure 2 Building Automation System MicroTech II Main Control Board MicroTech II LonWorks Communications Module MicroTech II Keypad LonWorks Interface Adapter LonWorks Wo...

Page 6: ...Standard Network Variable Types SNVTs and Standard Network Configuration Parameters SCPTs in accordance with the LonMark profiles used on the LonWorks network into the variables and parameters used in...

Page 7: ...able harness down to the shelf below the controller and to the left along the shelf to the edge Route the cable through a hole down the raceway to Terminal Block TB2 c Connect the cable harness white...

Page 8: ...10 Connect the MicroTech II LonWorks Communications Module to the network a Replace the network plug in P8 See Figure 3 11 Reconnect the network to TB 2 terminals 128 and 129 if it is necessary Figure...

Page 9: ...nection Schematic Diagram 522 523 LonWorks Communications Module Main Control Board MCB Unit Terminal Block Tb2 128 129 LonWorks Network A B Figure 6 Mount LonWorks Communications Module 12 Pin Header...

Page 10: ...10 IM702 3 Figure 7 Cable Harness Routing Applied Rooftop Unit LonWorks Comunications Module Controller Cable Shelf Cable Raceway Terminal Block TB2 Network Cable Communications...

Page 11: ...IM702 3 11 Figure 8 Cable Harness Routing Self Contained Unit Controller LonWorks Comunications Module Terminal Block TB2 Network Cable Harness Communications...

Page 12: ...s Additional nodes may be added with little regard to existing cable routing Free Topology Networks A LonWorks free topology network means that devices nodes can be connected to the network in a varie...

Page 13: ...ft 450 m 22 AWG 1312 ft 400 m 1640 ft 500 m 16 AWG 1640 ft 500 m 1640 ft 500 m The longest cable path between any possible pair of nodes on a segment must not exceed the maximum node to node distance...

Page 14: ...ld connect two controllers with one continuous piece of cable in order to reduce the risk of com munications errors If you must splice the cable use crimp type butt connectors good or solder best Do n...

Page 15: ...ware and configured at the factory for stand alone unit operation The unit is ready to operate in a stand alone manner with default set point parameters that can be changed with the unit s keypad disp...

Page 16: ...Length parameter should not be set higher than 1024 for BACnet IP or 501 for BACnet MSTP 4 The Xs in Device Object Name are factory set equal to the last nine digits of the 18 digit number on the bar...

Page 17: ...ce personnel of McQuay International in Minneapolis Minnesota 763 553 5330 A Return Goods tag must be included with the returned material Enter the required information to expedite handling and prompt...

Page 18: ...2 3 2004 McQuay International www mcquay com 800 432 1342 This document contains the most current product information as of this printing For the most current product information please go to www mcqu...

Reviews: