McQuay IM 702-3 Installation And Maintenance Manual Download Page 15

IM702-3

 15

Commissioning the Network

Pressing the service pin, switch SW1, generates a service pin message, which contains the Neuron ID and the program code
identification of the node. A service pin message is a network message that is generated by a node and broadcast on the
network. It can be used to commission the LonWorks network.

A network configuration tool maps device Neuron IDs to the domain/subnet/node logical addressing scheme when it creates
the network image, the logical network addresses, and connection information for all devices (nodes) on the network.

Ex

ternal Interface File (XIF)

LonMark guidelines specify exact documentation rules so that proprietary configuration tools are not required to
commission and configure LonWorks devices. The MicroTech II LonWorks Communications Module is self-documenting
so that any network management tool can obtain all the information needed over the network to connect it into the system
and to configure and manage it. An external interface file (a specially formatted PC text file with an extension .XIF) is also
available so that any network tool can design and configure it prior to installation. For a copy of the XIF file contact your
local McQuay International representative.

Configuring the Unit Controller

All MicroTech II Main Control Boards for Rooftop and Self-contained units are loaded with software and configured at the
factory for stand-alone unit operation. The unit is ready to operate in a stand-alone manner with default set point parameters
that can be changed with the unit’s keypad/display or via a network signal. See the appropriate operation manual for the
default values and keypad/display operating instructions.  See the appropriate MicroTech II Protocol Information Data for
descriptions of the available network variables. See Reference Documents for manual numbers.

There are 12 communication parameters involved in setting up the unit controller for proper communication with the
various communication module options (BACnet IP, BACnet MS/TP or LON). These parameters are set differently by the
factory depending on which communication module is ordered and shipped with the unit. The table below lists the four
possible sets of default parameter settings. Not all the parameters apply to all the module options. The entries in the table
that are shown in 

bold 

font apply to a particular module option.

If unit is equipped with a factory installed LONWORKS communication module (DAC or SCC) the controller is configured
as shown in the table. These parameters do not require field modification. If a LONWORKS module is added in the field to
a unit that shipped with no module or a BACnet module is removed and a LONWORKS module is installed in the field,
refer to the table to determine whether or not changes are required to communication setup parameters.

Note: 

The PC based McQuay MicroTech II ServiceTools is required to modify these parameters.

Summary of Contents for IM 702-3

Page 1: ...s module into the unit and connect the unit to your network You also need the appropriate McQuay Engineering Data Sheet known as the Protocol Data Packet to integrate the unit into your network The Pr...

Page 2: ...7 Integration 12 Network Connection 12 Network Topology 12 Free Topology Networks 12 Free Topology Restrictions 13 Doubly Terminated Networks 13 Doubly Terminated Topology Restrictions 14 Addressing a...

Page 3: ...MicroTech II Vertical Self Contained Unit Controller Installation Manual OM711 McQuay International MicroTech II Vertical Self Contained Discharge Air Controller Operation Manual OM712 McQuay Internat...

Page 4: ...protection against harmful interference when the equipment is operated in a commercial environment Operation of this equipment in a residential area is likely to cause harmful interference in which c...

Page 5: ...ce Documents for part numbers Figure 2 Building Automation System MicroTech II Main Control Board MicroTech II LonWorks Communications Module MicroTech II Keypad LonWorks Interface Adapter LonWorks Wo...

Page 6: ...Standard Network Variable Types SNVTs and Standard Network Configuration Parameters SCPTs in accordance with the LonMark profiles used on the LonWorks network into the variables and parameters used in...

Page 7: ...able harness down to the shelf below the controller and to the left along the shelf to the edge Route the cable through a hole down the raceway to Terminal Block TB2 c Connect the cable harness white...

Page 8: ...10 Connect the MicroTech II LonWorks Communications Module to the network a Replace the network plug in P8 See Figure 3 11 Reconnect the network to TB 2 terminals 128 and 129 if it is necessary Figure...

Page 9: ...nection Schematic Diagram 522 523 LonWorks Communications Module Main Control Board MCB Unit Terminal Block Tb2 128 129 LonWorks Network A B Figure 6 Mount LonWorks Communications Module 12 Pin Header...

Page 10: ...10 IM702 3 Figure 7 Cable Harness Routing Applied Rooftop Unit LonWorks Comunications Module Controller Cable Shelf Cable Raceway Terminal Block TB2 Network Cable Communications...

Page 11: ...IM702 3 11 Figure 8 Cable Harness Routing Self Contained Unit Controller LonWorks Comunications Module Terminal Block TB2 Network Cable Harness Communications...

Page 12: ...s Additional nodes may be added with little regard to existing cable routing Free Topology Networks A LonWorks free topology network means that devices nodes can be connected to the network in a varie...

Page 13: ...ft 450 m 22 AWG 1312 ft 400 m 1640 ft 500 m 16 AWG 1640 ft 500 m 1640 ft 500 m The longest cable path between any possible pair of nodes on a segment must not exceed the maximum node to node distance...

Page 14: ...ld connect two controllers with one continuous piece of cable in order to reduce the risk of com munications errors If you must splice the cable use crimp type butt connectors good or solder best Do n...

Page 15: ...ware and configured at the factory for stand alone unit operation The unit is ready to operate in a stand alone manner with default set point parameters that can be changed with the unit s keypad disp...

Page 16: ...Length parameter should not be set higher than 1024 for BACnet IP or 501 for BACnet MSTP 4 The Xs in Device Object Name are factory set equal to the last nine digits of the 18 digit number on the bar...

Page 17: ...ce personnel of McQuay International in Minneapolis Minnesota 763 553 5330 A Return Goods tag must be included with the returned material Enter the required information to expedite handling and prompt...

Page 18: ...2 3 2004 McQuay International www mcquay com 800 432 1342 This document contains the most current product information as of this printing For the most current product information please go to www mcqu...

Reviews: