Controller Operation
MicroTech III Inputs/Outputs
I/O for the unit control and for circuits one and two are found on CP1.
The chiller may be equipped with two or three compressors.
Analog Inputs
#
Description
Signal Source
Expected Range
AI1
Evaporator Entering Water Temp
NTC Thermister (10K@25°C)
-50°C – 120°C
AI2
Evaporator Leaving Water Temp
NTC Thermister (10K@25°C)
-50°C – 120°C
AI3
Evaporator #1 Leaving Water Temp (*)
NTC Thermister (10K@25°C)
-50°C – 120°C
X1
Evaporator #2 Leaving Water Temp (*)
NTC Thermister (10K@25°C)
-50°C – 120°C
X2
Outside Ambient Temperature
NTC Thermister (10K@25°C)
-50°C – 120°C
X4
LWT Reset
4-20 mA Current
1 to 23 mA
Analog Outputs
# Description Output
Signal Range
X5
Fan VFD #1
0-10VDC
0 to 100% (1000 steps resolution)
X6
Fan VFD #2
0-10VDC
0 to 100% (1000 steps resolution)
X7
Fan VFD #3
0-10VDC
0 to 100% (1000 steps resolution)
X8
Fan VFD #4
0-10VDC
0 to 100% (1000 steps resolution)
Digital Inputs
#
Description
Signal Off
Signal On
DI1
Unit PVM
Fault
No Fault
DI2
Evaporator Flow Switch
No Flow
Flow
DI3
Double Set Point/ Mode Switch
Cool mode
Ice mode
DI4 Remote
Switch
Remote off
Remote on
DI5
Unit Switch
Unit off
Unit on
DI6 Emergency
Stop
Unit off/rapid stop
Unit on
Digital Outputs
#
Description
Output OFF
Output ON
DO1
Evaporator Water Pump
Pump Off
Pump On
DO2
Unit Alarm
Alarm not Active
Alarm Active
(Flashing= circuit
alarm)
DO3
Circuit #1 Fan Step #1
Fan Off
Fan On
DO4
Circuit #1 Fan Step #2
Fan Off
Fan On
DO5
Circuit #1 Fan Step #3
Fan Off
Fan On
DO6
Circuit #1 Fan Step #4
Fan Off
Fan On
DO7
Circuit #2 Fan Step #1
Fan Off
Fan On
DO8
Circuit #2 Fan Step #2
Fan Off
Fan On
DO9
Circuit #2 Fan Step #3
Fan Off
Fan On
DO10
Circuit #2 Fan Step #4
Fan Off
Fan On