6

To confirm the fault place the red leg over the suspected faulted area. Pivot the A-frame 
in a 360-degree circle if the indicator continually shows Red then fault is beneath the red 
leg. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Multiple Faults

 –Place both legs of the A-frame in the ground with the red leg directly 

over the fault point. With a line that has multiple faults, the fault that registers the highest 
reading on the display is the fault. That needs to be repaired. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Cable Path 

Fault 

Ground            
 Stake    

 

  

Meter

 

Transformer

 

Transmitter

 

High Resistance 
Earth Ground 

FAULT 
Low Resistance 
Earth Fault 

Summary of Contents for VISION FLX2

Page 1: ...VISION FLX2 MANUAL AUG 22 2016 833 083...

Page 2: ...direction of the cable path Connect the black end of the direct connection cables to the ground stake Connect the red end of the direct connection cables on the cable to be checked Power on Press Fre...

Page 3: ...he direct connection cables to the ground stake Connect the red end of the direct connection cables on the cable to be checked Power on Press Frequency and select FF Press ADJUST Resistance is indicat...

Page 4: ...cable Press and hold the Gain Select key for one second this will adjust the sensitivity of the Receiver and display 70 0 If the Receiver displays OVER manually reduce the output on the Transmitter u...

Page 5: ...e A frame in the earth every five to ten feet Note If LCD does not display arrow or signal strength A frame is not reading signal The A frame may not be making contact with earth or signal is too weak...

Page 6: ...point will be in the center of the A frame CONFIRM THE FAULT LOCATION Turn the A frame 90 degrees perpendicular to the cable path Place the A frame in the earth and follow the direction the arrows ar...

Page 7: ...he red leg Multiple Faults Place both legs of the A frame in the ground with the red leg directly over the fault point With a line that has multiple faults the fault that registers the highest reading...

Page 8: ...rection of the arrow and measure the location of the cable When going back to Fault finding mode press Peak Null again The direction of the object line Receiving level No bar graph Yaw angle Real time...

Reviews: