BLAST CHILLERS AND FREEZERS
INSTALLATION MANUAL n° 6CE648070NI
–0712
Page 8
4. COMMISSIONING
4.1 GENERAL REQUIREMENTS
Check that no foreign body obstructs the evaporator and condenser ventilators. If the
appliance was laid flat during transportation, wait 24 hours before putting it in service so as to
allow oil to return from the refrigerating circuit to the compressor pan (housing).
Install the grid runners on the racks.
4.2 PRESENTATION OF CONTROL PANEL KEY BOARD
Key 1: "HACCP" and key (-)
Led 1°: Cycle "Soft Chill"
Key 2: "Select cycle" and key (+)
Led 2°: Cycle "Defrost"
Key 3: "Start cycle"
Led 3°: Cycle "Freezing"
4.3 CONFIGURATION OF ELECTRONIC CARD
4.3.1 PARAMETER CONFIGURATION
The assembly is factory-delivered with standard configuration, designed to meet most
current utilizations
(see § 1.2, page 3 of the user’s manual). As necessary, this configuration
can be changed.
The modifications of the parameters are definitively taken into account even after the
assembly is switched off.
4.3.2 PARAMETER CONFIGURATION
When the appliance is switched on, press keys 1 and 2 simultaneously for 5 seconds to
access parameter programming. Parameter P01 is displayed.
To move from one number to another, depress key 2 or 1.
To display a pre-adjusted parameter in a number, depress key 3
and actuate keys 2 or 1
simultaneously to modify it. Release key 3 to move automatically to the following parameter.
Programming is left automatic when neither key is actuated for 5 seconds.
Key 1
Led 3
Led 1
Led 2
Key 2
Key 3