background image

 

 

Para-
meter 

Function 

Setting range 

Default value 

Your 
setting 

A90 Output 

connection, 

K1 

0: No connection  

1: Connect to regulation contact 1

 

2: Connect to regulation contact 2 
3: Connect to alarm contact 
4: Connect to buzzer function 
5: Connect to button 3 or 5 

 

 

A91 Output 

connection, 

K2 

0: No connection  
1: Connect to regulation contact 1 

2: Connect to regulation contact 2

 

3: Connect to alarm contact 
4: Connect to buzzer function 
5: Connect to button SET 2 

 
 

 

A92 Output 

connection, 

K3 

0: No connection  
1: Connect to regulation contact 1 
2: Connect to regulation contact 2 

3: Connect to alarm contact

 

4: Connect to buzzer function 
5: Connect to button SET 2 

 
 
 

 

Pro Program 

version 

 

A1/A2 Function of regulation contacts ½ 

Regulation contacts 1 and 2 can be set separately to act as a heating contact or a cooling contact. If set as a heating contact, the contact closes if the 
actual temperature is less than the setpoint. For use as a cooling contact, the function is inverted. See also Figs. 1 - 4. 

A3/A4 Function of regulation contacts 1/2 in the case of a sensor fault  

Regulation contacts 1 and 2 switch to the position specified here in the case of a sensor fault. If a fault is detected in the parameter memory (display: 
EP), which means that the saved settings cannot be used, regulation contacts 1 and 2 are switched to a state where no current flows. 

A5 Operation with setpoint or DeltaW for regulation contact 2 

This parameter determines whether the controller operates with two independently adjustable contacts (A5=0, operation with setpoint, factory 
setting) or with two mutually linked contacts (A5=1, operation with Delta W). 
This parameter always affects regulation contact 2. 

A8 Display mode 

The actual value can be displayed as an integer or with one digit after the decimal point (resolution 0.5 °C or 0.1 °C). If a resolution of 0.5 °C is 
selected, the actual value is rounded up or down. All parameter settings and setpoints are always displayed with a resolution of 0.1 °C. 

A9 Weighting factor 

The actual value can be weighted with the aid of this parameter. The measured value is multiplied by this factor and the resulting value is displayed 
and used for regulation. 

A19 Parameter locking 

With the setting A19=0, all parameters are accessible. 
With the setting A19=1, all A parameters are locked except for A19 itself (factory setting). 
With the setting A19=2, all A parameters and all P parameters are locked. 
When parameters are locked, they cannot be changed with the buttons on the front panel. Any attempt to do this results in the message ”---" on the 
display. 

A30 Function of alarm output 

The state of the alarm output depends on actual values with respect to the upper and lower limit values (see parameters P30 and P31). With this 
parameter, you can select whether the alarm is activated when the actual temperature lies between the two limit values or when the temperature lies 
outside the limit values. In the case of a sensor fault, the alarm is activated regardless of this setting. The output can also be inverted. See Figs. 5     
to 8. 

Summary of Contents for MTR 3000

Page 1: ...e setpoint and the alarm acknowledgement All regulation parameters P2 P32 can be set in the second level The third level permits programming of the basic functions A1 A92 of the controller UP button red arrow Down button blue arrow This button is used to acknowledge an alarm SET 1 SET 1 button Pressing this button displays set value S1 If the button is not depressed the actual value is displayed T...

Page 2: ...er reverts to its normal state Parameter Function Setting range Default value Your setting P0 Actual value P1 Setpoint S2 regulation contact 2 DeltaW regulation contact 2 P4 P5 if A5 0 factory setting 99 99 9K if A5 1 10 0 C K P2 Hysteresis contact 1 0 1 99 0 K 1 0 K P3 Hysteresis contact 2 0 1 99 0 K 1 0 K P4 Lower setpoint limit 99 C P5 99 C P5 Upper setpoint limit P4 999 C 999 C P6 Actual value...

Page 3: ...mend that this be done after all adjustments In the disabled state the setpoint cannot be adjusted with the buttons on the front panel Any attempt to adjust the setpoint then results in the message on the display P30 Lower limit value for alarm P31 Upper limit value for alarm The alarm output can be used as a limit value or bandwidth alarm It has an asymmetrical hysteresis see parameter P32 In bot...

Page 4: ...Para meter Function Setting range Default value Your setting A1 Function of regulation contact 1 0 Heating contact 1 Cooling contact 0 A2 Function of regulation contact 2 0 Heating contact 1 Cooling contact 0 A3 Function of regulation contact 1 in case of sensor fault 0 Off on fault 1 On on fault 0 A4 Function of regulation contact 2 in case of sensor fault 0 Off on fault 1 On on fault 0 A5 Operat...

Page 5: ...ntact 2 0 600 s 0 s A54 Delay after power on 0 600 s 0 s A55 Mutual delay regulation contacts 1 and 2 0 600 s 0 s A56 Alarm suppression after power on 0 60 min 20 min A60 Temperature sensor 11 12 PT100 three wire connection 12 A70 Software filter 1 Disabled Average over 2 2 measured values approx 0 6s 4 4 measured values approx 1 2s 8 8 measured values approx 2 4s 16 16 measured values approx 4 8s...

Page 6: ...rameter determines whether the controller operates with two independently adjustable contacts A5 0 operation with setpoint factory setting or with two mutually linked contacts A5 1 operation with Delta W This parameter always affects regulation contact 2 A8 Display mode The actual value can be displayed as an integer or with one digit after the decimal point resolution 0 5 C or 0 1 C If a resoluti...

Page 7: ...n active A sensor alarm display F1L or F1H is always signalled by a blinking display and the buzzer A32 Type of display If A32 0 is set the actual value is displayed If A32 1 is set setpoint S1 is always displayed and the actual value can then be displayed only with the aid of parameter P0 second operating level A33 Not used A40 Hysteresis mode regulation contact 1 A41 Hysteresis mode regulation c...

Page 8: ... A70 1 deactivates the software filter A80 Temperature scale The temperatures can be displayed in Fahrenheit or Celsius factory setting Note that the values and setting ranges for the parameters and setpoints remain unchanged when the scale is changed If for example a controller whose setpoint is set to 0 C is modified to display the temperatures in Fahrenheit the setpoint is then interpreted as 0...

Page 9: ...ous current 6 A make contact suitable for electric motors up to 0 5 HP Function see parameter A91 K3 Relay 250 V maximum switched current 6 A cosϕ 1 maximum continuous current 3 A make contact suitable for electric motors up to 0 5 HP Function see parameter A92 Supply voltage 230 V 50 60 Hz maximum power consumption 4 VA Terminals 12 pole screw terminal plug strip spacing 5 0 mm for cables up to 2...

Reviews: