Maytag MLG33PDAWW Installation & Operator'S Manual Download Page 11

113413-1

Telephone: (641) 787-7000

11

Fresh Air Supply Requirements________

When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of the
building.  Therefore, the room air must be continually
replenished from the outdoors.  If the make-up air is
inadequate, drying time and drying efficiency will be adversely
affected.  Ignition problems and sail switch “fluttering”
problems may result, as well as premature motor failure from
overheating.  The dryer must be installed with provisions for
adequate combustion and make-up air supply.

Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  As a general
rule, an unrestricted air entrance from the outdoors of 110
inch

2

 (710 cm

2

) is required for each MLG33  and 80 inch

2

(516 cm

2

) for each SL2020   .  (Based on 1 inch

2

 [6.5 cm

2

] per

1,000 Btu [252 kcal].)

It is not necessary to have a separate make-up air opening
for each dryer.  Common make-up air openings are
acceptable.  However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.

A = 14-inches (35.56 cm)

B = 16-inches (40.64 cm)

EXAMPLE: For a bank of 4 MLG33 dryers, 2 unrestricted
openings measuring 14-inches by 16-inches (35.56 cm by
40.64 cm) are acceptable.

To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%.  Make-up air openings should not be located in an area
directly near where exhaust vents exit the building.

Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.

Important

Make-up air must be free of dry cleaning solvent
fumes.  Make-up air that is contaminated by dry

cleaning solvent fumes will result in irreparable damage to
the motors and other dryer components.

Note

Component failure due to dry cleaning solvent
fumes will void the warranty.

!

!

Exhaust Requirements________________

Exhaust ductwork should be designed and installed by a
qualified professional.  Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airflow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat.  The dryer must be installed with a proper
exhaust duct connection to the outside.

Caution

This dryer produces combustible lint and must be
exhausted to the outdoors.

Improperly sized or installed exhaust ductwork can create
a potential fire hazard.

The ductwork should be laid out in such a way that the
ductwork travels as directly as possible to the outdoors with
as few turns as possible.  There should be a minimum
6-inch (15.24 cm) clearance between the back guard and the
first bend in the ductwork for ease of servicing.  Single or
independent dryer venting is recommended.  It is suggested
that the use of 90° turns be avoided; use 30° and/or 45°
bends instead.  The radius of the elbows should preferably
be 1-1/2 times the diameter of the duct.  All ductwork should
be smooth inside with no projections from sheet metal
screws or other obstructions, which will collect lint.  When
adding ducts, overlap the duct being connected.  All ductwork
joints must be taped to prevent moisture and lint from
escaping into the building.  Back draft dampers must be
installed in all commonly ducted systems.  Inspection doors
should be installed at strategic points in the exhaust ductwork
for periodic inspection and cleaning of lint from the ductwork.

Important

It is recommended that exhaust or booster fans
not be used in the exhaust ductwork system.

Exhaust back pressure measured by a manometer/
magnehelic in the exhaust duct must be no less than 0 and
must not exceed 0.6 in WC (1.48 mb).

Note

When the exhaust ductwork passes through a wall,
ceiling, or roof made of combustible materials, the

opening must be 2-inches (5.08 cm) larger than the duct
(all the way around).  The duct must be centered within this
opening.

As per the National Fuel Gas Code, “Exhaust ducts for type
2 clothes dryers shall be constructed of sheet metal or
other noncombustible material.  Such ducts shall be
equivalent in strength and corrosion resistance to ducts
made of galvanized sheet steel not less than 26 gauge
(0.0195-inches [0.50 mm]) thick.”

The ductwork for this appliance must be suitable for the
appliance category in accordance with national installation
regulations of the country of destination.

!

!

!

Summary of Contents for MLG33PDAWW

Page 1: ...ent professional AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incendie ou d explosion ou pour viter tout dommage mat riel to...

Page 2: ...__________________________________ MODELNO _________________ DEALER SNAME _________________________________________________________________________________________ Serial Number s ____________________...

Page 3: ...Personal injury or fire could result The dryer must never be operated without the lint filter screen in place even if an external lint collection system is used FOR YOUR SAFETY Do not dry mop heads in...

Page 4: ...mage plastics or rubber and also may be a fire hazard A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer...

Page 5: ..._________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ______...

Page 6: ...ER POCKET 40 000 Btu hr 10 080 kcal hr EXHAUST CONNECTION DIAMETER PER POCKET 4 10 16 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T 3 8 M B S...

Page 7: ...113413 1 Telephone 641 787 7000 7 Specifications _____________________________________________________________________ NOT AVAILABLE...

Page 8: ...EAT INPUT PER POCKET 55 000 Btu hr 13 860 kcal hr EXHAUST CONNECTION DIAMETER PER POCKET 6 15 24 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T...

Page 9: ...113413 1 Telephone 641 787 7000 9 MLG33 Specifications _____________________________________________________________...

Page 10: ...ed in this manual refer to Exhaust Requirements section Important The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clea...

Page 11: ...ch results in slow drying increased use of energy and shutdown of the burner by the airflow sail switch burner hi limits or lint chamber hi limit protector thermostat The dryer must be installed with...

Page 12: ...90 elbows should be used in the exhaust duct run If more than the equivalent of 4 90 elbows are used the cross sectional area of the ductwork must be increased Multiple Dryer Common Venting Important...

Page 13: ...to make changes in specifications at any time without notice or obligation Important A separate protected circuit must be provided to each pocket The dryer must be connected to the electric supply sh...

Page 14: ...ct voltage When fuses are used they must be dual element time delay current limiting class RK1 or RK5 ONLY Calculate determine correct fuse value by applying either local and or National Electrical Co...

Page 15: ...strain relief must be installed where the wiring enters the dryer For CE Models Only The means for disconnection from the supply must be incorporated into wiring having a minimum contact separation o...

Page 16: ...ning Fire or explosion could result due to failure of isolating or disconnecting the gas supply as noted Note Undersized gas piping will result in ignition problems slow drying increased use of energy...

Page 17: ...M3 H 36 2 705 1 Butane G30 3 175 28 30 40 000 11 72 0 845 kg H 44 2 184 1 Propane G31 2 500 37 40 000 11 72 0 845 kg H 44 2 184 1 Butane G30 3 175 28 30 50 40 000 11 72 0 845 kg H 39 2 527 1 6 1 Prop...

Page 18: ..._____________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ __________...

Page 19: ...e the gas train out of the gas train enclosure The carbon ignitor located at the far end of the gas train is very fragile Remove 2 burner tube mounting screws and remove burner tube in order to gain a...

Page 20: ...gas train engages into the mounting slot Connect the union and the 3 electrical plugs Repeat these steps for the other burner Open all shutoff valves reconnect electrical power to the dryer and test f...

Page 21: ...ack of the steam coils Important Coil failure due to improper pH level will void the warranty Gas Pressure Testing__________________ For proper operation the gas pressure must be correct consistent an...

Page 22: ...am Pressure Maximum 125 psig 861 85 kPa Heat Input Normal Load 1 75 Bhp Consumption Approximate 125 psi 8 6 bar 63 lb hr 28 58 kg hr Water pockets in the supply line caused by low points will provide...

Page 23: ...tumbler drum by hand to be sure it moves freely Check bolts nuts screws terminals and fittings for tightness and security Check that the vent is connected to the dryer and is exhausted to the outdoor...

Page 24: ...rt and the L C D will display the Dry Cycle selected and the remaining time The dryer will continue through the drying and cooling cycles until the vended time has expired Note To stop the dryer open...

Page 25: ...r from whom you purchased the equipment and request a dryer warranty form If the dealer cannot be contacted or is unknown warranty information can be obtained from the Maytag Co Note Whenever contacti...

Page 26: ...Clean lint accumulation from lint chamber thermostat and microprocessor temperature sensor area Warning To avoid the hazard of electrical shock discontinue electrical supply to the dryer Steam Dryers...

Page 27: ...gas electric or steam 2 Serial Number Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular dryer gas either natura...

Page 28: ...Part No 113413 1 06 02 05 0...

Reviews: