Electrical Requirements - U.S.A. Only

If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrical installer determine that 
the ground path and wire gauge are in accordance with local 
codes.

Do not use an extension cord.

Be sure that the electrical connection and wire size are adequate 
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.

A copy of the above code standards can be obtained from: 
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269.

WARNING: Improper connection of the equipment-grounding 
conductor can result in a risk of electric shock. Check with a 
qualified electrician or service technician if you are in doubt as to 
whether the appliance is properly grounded. Do not modify the 
power supply cord plug. If it will not fit the outlet, have a proper 
outlet installed by a qualified electrician.

Electrical Connection

To properly install your range, you must determine the type of 
electrical connection you will be using and follow the instructions 
provided for it here.

Range must be connected to the proper electrical voltage 
and frequency as specified on the model/serial number rating 
plate. The model/serial/rating plate is located behind the 
control panel. Refer to the figures in “Product Dimensions” in 
the “Location Requirements” section.

This range is manufactured with the neutral terminal 
connected to the cabinet. Use a 3-wire, UL listed, 40- or 
50-amp power supply cord (pigtail) (see the following Range 
Rating chart). If local codes do not permit ground through the 
neutral, use a 4-wire power supply cord rated at 250 volts, 
40 or 50 amps and investigated for use with ranges.

*The NEC calculated load is less than the total connected load 

listed on the model/serial/rating plate.

**If connecting to a 50-amp circuit, use a 50-amp rated cord with 

kit. For 50-amp rated cord kits, use kits that specify use with a 
nominal 1

³⁄₈

" (34.9 mm) diameter connection opening.

A circuit breaker is recommended.

The range can be connected directly to the circuit breaker 
box (or fused disconnect) through flexible or nonmetallic 
sheathed, copper or aluminum cable. See the “Electrical 
Connection - U.S.A Only.” section.

Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that 
the range can be moved if servicing is ever necessary.

A UL listed conduit connector must be provided at each end 
of the power supply cable (at the range and at the junction 
box).

Wire sizes and connections must conform with the rating of 
the range.

The wiring diagram is located on the Tech Sheet.

The Tech Sheet is located on the back of the range inside a 
clear plastic bag.

If connecting to a 4-wire system:

This range is manufactured with the ground connected to the 
neutral by a link. The ground must be revised so the green 
ground wire of the 4-wire power supply cord is connected to the 
cabinet. See “Electrical Connection Section.”

Grounding through the neutral conductor is prohibited for new 
branch-circuit installations (1996 NEC); mobile homes; and 
recreational vehicles, or an area where local codes prohibit 
grounding through the neutral conductor.

When a 4-wire receptacle of NEMA Type 14-50R is used, a 
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power 
supply cord (pigtail) must be used. This cord contains 4 copper 
conductors with ring terminals or open-end spade terminals with 
upturned ends, terminating in a NEMA Type 14-50P plug on the 
supply end. 

The fourth (grounding) conductor must be identified by a green or 
green/yellow cover and the neutral conductor by a white cover. 
Cord should be Type SRD or SRDT with a UL listed strain relief 
and be at least 4 ft (1.22 m) long.

The minimum conductor sized for the copper 4-wire power 
cord are:

40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding

If connecting to a 3-wire system:

Local codes may permit the use of a UL listed, 3-wire, 250-volt, 
40- or 50-amp range power supply cord (pigtail). This cord 
contains 3 copper conductors with ring terminals or open-end 
spade terminals with upturned ends, terminating in a NEMA Type 
10-50P plug on the supply end. Connectors on the appliance end 
must be provided at the point the power supply cord enters the 
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.

Range Rating*

Specified Rating of 
Power Supply Cord Kit 
and Circuit Protection

120/240 Volts

120/208 Volts

Amps

8.8 - 16.5 KW
16.6 - 22.5 KW

7.8 - 12.5 KW
12.6 - 18.5 KW

40 or 50**
50

4-wire receptacle (14-50R)

3-wire receptacle (10-50R)

Summary of Contents for MET8665XB

Page 1: ...ment 21 V rification de l emplacement de la bride antibasculement 22 R glage de l aplomb de la cuisini re 22 Achever l installation 22 D placement de la cuisini re 23 W10289536A IMPORTANT Save for loc...

Page 2: ...od that projects horizontally a minimum of 5 12 7 cm beyond the bottom of the cabinets Cabinet opening dimensions that are shown must be used Given dimensions are minimum clearances The floor anti tip...

Page 3: ...not less than No 28 MSG sheet steel 0 015 0 4 mm stainless steel 0 024 0 6 mm aluminum or 0 020 0 5 mm copper 30 76 2 cm minimum clearance between the top of the cooking platform and the bottom of an...

Page 4: ...per or aluminum cable See the Electrical Connection U S A Only section Allow 2 to 3 ft 61 0 cm to 91 4 cm of slack in the line so that the range can be moved if servicing is ever necessary A UL listed...

Page 5: ...The NEC calculated load is less than the total connected load listed on the model serial rating plate If connecting to a 50 amp circuit use a 50 amp rated cord with kit For 50 amp rated cord kits use...

Page 6: ...tion NOTE To place range back up into a standing position put a sheet of cardboard or hardboard in front of range Using 2 or more people stand range back up onto the cardboard or hardboard 2 Adjust th...

Page 7: ...n be installed on either the left side or right side of the cutout Position mounting bracket in cutout so that right or left edge of the bracket is 2 4 cm from the marked edge of the range as shown 4...

Page 8: ...rd through the strain relief in the cord conduit plate on bottom of range Allow enough slack to easily attach the wiring to the terminal block Tighten strain relief screw against the power supply cord...

Page 9: ...stallation following instructions for your type of electrical connection 4 wire recommended 3 wire if 4 wire is not available Electrical Connection Options A Removable retaining nut B Strain relief A...

Page 10: ...Connect line 1 black and line 2 red wires to the outer terminal block posts with 10 32 hex nuts 7 Securely tighten hex nuts NOTE For power supply cord replacement only use a power cord rated at 250 v...

Page 11: ...slack in the wire to easily attach the wiring terminal block 3 Complete electrical connection according to your type of electrical supply 4 wire or 3 wire connection 4 wire Connection Direct Wire Use...

Page 12: ...e Use this method only if local codes permit connecting ground conductor to neutral supply wire 1 Pull the conduit through the hole and conduit plate on bottom of range Allow enough slack to easily at...

Page 13: ...nstalled If there is an extra part go back through the steps to see which step was skipped 2 Check that you have all of your tools 3 Dispose of recycle all packaging materials 4 Check that the range i...

Page 14: ...wired ranges 1 Disconnect power 2 Slide range forward 3 Complete cleaning or maintenance 4 To check that anti tip bracket is installed use a flashlight and look underneath the bottom of the range Look...

Page 15: ...15 Notes...

Page 16: ...Assurez vous de toujours lire tous les messages de s curit et de vous y conformer AVERTISSEMENT DANGER Voici le symbole d alerte de s curit Ce symbole d alerte de s curit vous signale les dangers pote...

Page 17: ...s de rangement sont envisag s le risque peut tre r duit par l installation d une hotte de cuisine d passant le bas des placards d au moins 5 12 7 cm horizontalement Respecter les dimensions indiqu es...

Page 18: ...m tallique d paisseur gale ou sup rieure acier calibre 28 MSG acier inoxydable 0 015 0 4 mm aluminium 0 024 0 6 mm ou cuivre 0 020 0 5 mm Distance de s paration de 30 76 2 cm ou plus entre le dessus d...

Page 19: ...nf rieure la charge totale connect e indiqu e sur la plaque signal tique En cas de raccordement un circuit de 50 A utiliser un cordon de 50 A nominaux avec son n cessaire Pour les cordons de 50 A nomi...

Page 20: ...en position verticale placer un carton ou un panneau de fibres dur devant la cuisini re l aide de deux personnes ou plus relever la cuisini re et la placer sur le carton ou le panneau de fibres dur 2...

Page 21: ...coupage Positionner la bride de montage dans la zone d coup e de fa on ce que le bord droit ou gauche de la bride se trouve 2 4 cm de l emplacement du bord de la cuisini re tel qu illustr 4 Percer deu...

Page 22: ...ubli e 2 V rifier la pr sence de tous les outils 3 liminer recycler tous les mat riaux d emballage 4 V rifier que la cuisini re est d aplomb Voir R glage de l aplomb de la cuisini re 5 Utiliser une so...

Page 23: ...iser une lampe de poche pour examiner le dessous de la cuisini re V rifier que la bride antibasculement est bien fix e au plancher ou au mur Faire glisser la cuisini re vers l arri re de fa on ce que...

Page 24: ...W10289536A 2010 All rights reserved Tous droits r serv s 1 10 Printed in U S A Imprim aux U...

Reviews: