Maytag FS4BG024K Installation Instructions Manual Download Page 9

9

present, the inverter needs to be replaced, or internal wiring 

is incorrect. If line voltage is absent, check for 24 vac across 

the main contactor coil, and verify line voltage between the 

lower terminals of the contactor. If 24 volt coil voltage is absent, 

check continuity through the high pressure switch, and verify 

that the 

COMMUNICATIONS PORT

 plug is in place at 

J6

 at 

the bottom edge right of the interface board.

No Control Board Display

If the 2-character display on the interface board shows nothing, 

verify that 24 vac control voltage is present between 

R

 and 

C

 

(red and black wires of the field wiring harness plugged into the 

right side of the control board. If voltage is absent, check field 

wiring back to the indoor unit and transformer and thermostat. 

If voltage is present but the display is blank, the control board 

needs to be replaced. Check wiring for indications of a direct 

short before trying a new board.

Troubleshooting Individual Fault Codes (when 

active)

Follow the recommended troubleshooting procedures in Table 

8 for “active” faults. In some cases more than one fault code 

or different active codes may be generated by one issue, e.g. 

interruption of line power. Always cycle line power (30 seconds 

off, then on for at least 1 minute) to confirm that an active fault 

returns, is re-declared, before considering replacing hardware.  

Most inverter-related faults are at least temporarily cleared by 

cycling power in this manner. Do not replace hardware based 

on history alone, on faults that are not “active”.

Table 8. Individual Fault Codes

CODES

DESCRIPTION

1





9

These codes indicate abnormal high current or high 

inverter temperature. If they persist and return as active 

fault codes, they may indicate a faulty inverter drive or a 

wrong interface board/inverter combination.



Compressor Drive Failure

 – This generally indicates 

a compressor problem which may be temporary or 

permanent.  If the compressor has just been replaced, 

recheck  the  U,  V,  and  W  compressor  leads  for  a 

connection  mistake.  Before  the  inverter  declares  this 

fault during an attempted startup, it will try to start the 

compressor 4 times, with approximately 20 seconds 

pause between attempts. During start attempts, listen 

for compressor noise; if none, the compressor may need 

to  be  replaced.    Check  compressor  phase-to-phase 

resistances;  they  should  all  be  less  than  1.5  ohms 

and within 0.2 

 of each other. If compressor noise is 

loud, squealing, or otherwise unusual, the compressor 

may need to be replaced. If the compressor restarts 

normally, this fault code may be simply an indication that 

the compressor speed has been temporarily disrupted 

by either starting or shutting down abruptly against a 

high pressure ratio. In either case, the system may 

be normal but only temporarily affected by abnormal 

running conditions.

4

1

11

1

1

These fault codes refer to internal inverter operation and 

are likely to indicate inverter failure. If they persist and 

return as active fault codes, replace the inverter assembly.

6

High DC Bus Voltage

 – This is an indication that line 

voltage exceeded 10% over nominal value. The cause 

is  likely  to  be  power  grid  abnormalities  or  a  poorly 

controlled generator.

7

low  DC  Bus  Voltage

 – In most cases this is an 

indication that 208/230 volt line power was interrupted 

or disconnected.  It may also indicate low line voltage 

or, rarely, an internal inverter failure.

8

low AC line Voltage

 – This indicates that line voltage 

has dropped below approximately 170 volts. It may also 

indicate loss of line power, in which case Code 

7

 may 

appear in addition to or instead of this code.

14

Loss of Communication Between Inverter and 

Interface Board

  –  Check  the  inverter  LEDs  (as 

described  in  Inverter  Circuit  Board  LEDs  section)  for 

an indication that the inverter has line power. Follow the 

troubleshooting steps described in that section first.  If 

the inverter LEDs are lit but the code is active, verify that 

the 4-pin plug at 

J5

 

(InVERtER PORt

) is connected at 

the bottom edge center of the interface board.  If these 

checks do not resolve the fault and the fault remains 

active, replace the interface board.

1

16

17

These are warning codes that simply indicate that a 

high current or temperature condition was reached, 

and that the inverter was able to keep the parameter in 

an acceptable range by automatically reducing speed.  

These conditions do not result in the unit shutting down 

(unless the current or temperature increased further 

and reached a shutdown limit, in which case another 

code would be displayed). 

NOTE:

 If a high current or 

temperature shutdown occurs, these warning codes are 

not necessarily displayed and stored.

Summary of Contents for FS4BG024K

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the unit or failure to follow safety warnings could result in serious injury de...

Page 2: ...e adjustment or maintenance may cause electrical shock or other hazardous conditions which may result in personal injury or property damage WARNING The information listed below and the next page must...

Page 3: ...eep snowdrift accumulation The support slab should be level Make sure that the drain holes in the bottom of the unit are not obstructed Roof Mounting The method used for roof mounting should be design...

Page 4: ...to interconnect the two stage thermostat the indoor unit and the outdoor unit The source of the 24 vac is located within the indoor unit air handler or furnace The C side of this power source may be g...

Page 5: ...d method of charging is by weighing in the additional refrigerant required If a charging scale is not available the next preferred charging method would be to use the sub cooling method After weighing...

Page 6: ...cle The operating speed history for both the current and the previous operating cycles For example with a first stage call in cooling if the setpoint was satisfied quickly within 20 minutes the unit w...

Page 7: ...tup delay can be skipped by shorting the two J4 Test pins indicated in Figure 7 for about 1 second while the compressor is off and waiting to start NOTE Use this feature with forethought because it wi...

Page 8: ...l only and none are active Also if no code numbers are displayed there have been no faults recorded or the history has been cleared NOTE As standard practice write down the fault codes in the historyb...

Page 9: ...oise if none the compressor may need to be replaced Check compressor phase to phase resistances they should all be less than 1 5 ohms and within 0 2 of each other If compressor noise is loud squealing...

Page 10: ...face Board Software Corruption This code indicates that the interface board needs to be replaced It should never be encountered Compressor Discharge Temp Sensor Failure This fault code indicates an op...

Page 11: ...11 FIGURES Charts Figure 2 Air Conditioner Control Panel Cover Removed Inverter black plastic case Interface Board Contactor Low Voltage Compartment...

Page 12: ...12 Figure 4 Low Voltage Compartment for Control Wiring Vapor Line Service Valve Liquid Line Service Valve Figure 5 Service Valves Figure 3 Power Wiring Terminals Wire Entry Ground Lug Contactor...

Page 13: ...oling Charging Chart Outdoor Temperature above 60 F Remove refrigerant if above curve Add refrigerant if below curve Liquid Line Temperature F Liquid Line Pressure psig 3 4 TON MODELS 2 TON MODELS 5 T...

Page 14: ...ay transformer kits 7 Ferrite chokes are shown by an ellipse enclosing wires The number of turns per wire through the choke is shown by for example 2X 7113640 6 14 HIGH PRESSURE SWITCH 12V GND DX DX I...

Page 15: ...s shown by for example 2X FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 7113710 6 14 HIGH PRESSURE SWITCH 12V GND DX DX INTERFACE BOARD REV VLV OUTDOOR TEMP 2 P M E T L I O C 1 P M E T L I O C SUCTION...

Page 16: ...3 4 5 6 7 8 9 10 Deg F k Temperature vs Resistance for All Thermistors Part 1 10 0 10 20 30 40 50 60 70 80 10 20 30 40 50 60 70 80 90 100 Deg F Temperature vs Resistance for All Thermistors Part 2 k...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety...

Reviews: