Maytag FS4BG024K Installation Instructions Manual Download Page 3

3

PREPARATION

Before proceeding with installation of iQ air conditioning 

equipment, consult with the distributor and homeowner to 

confirm that the equipment listed on the order is what was 

ordered, and that it matches labeling on the equipment 

packaging.

Determine (including consultation with the homeowner) the 

intended/preferred location for placement of the compressor/

outdoor coil unit. Unit envelope dimensions are shown in 

Figure 1

.

This air conditioner is designed for outdoor installation only. 

Unit  placement  must  take  into  consideration  the  following 

clearances:

•  A minimum of 12 inches must be provided between each 

of the four sides and any solid barrier or wall which might 

block free inlet air flow into the coil. A minimum clearance 

of 18 inches is required between multiple units. 

•  The corner of the unit covered by the control access cover 

must be clear enough to allow comfortable access by a 

serviceperson.

•  The top of the unit must be open and unobstructed to prevent 

recirculation of outdoor fan discharge air, particularly for air 

conditioning usage. A minimum distance of 4 feet overhead 

clearance is recommended. Do not locate the unit in a pit 
with high walls on all sides.

Locate the unit away from overhangs which would allow water 

runoff or ice to fall directly onto the air conditioner. In low 

temperature climates, place the unit where it is not directly 

in prevailing winds. Avoid placing the air conditioner near 

sleeping quarters or windows.

Slab Mounting

•  The preferred unit mounting is on an outdoor slab (concrete 

or plastic), on the ground, in an area with good drainage 

unlikely to be affected by heavy runoff, ground settling, or 

deep snowdrift accumulation.

•  The support slab should be level. Make sure that the drain 

holes in the bottom of the unit are not obstructed.

Roof Mounting

The method used for roof mounting should be designed so 

as not to overload roof structures nor transmit noise to the 

interior of the structure. Refrigerant and electrical lines should 

be routed through suitably waterproofed openings to prevent 

leaking into the structure. Make sure that the roof structure 

can adequately support the weight of the equipment. Consult 

local building codes for rooftop installations.
After a location has tentatively been selected, trace routing 

of new (or pre-existing) refrigerant lines (two), and power and 

control wiring. See further discussion below.

•  Maximum recommended length for refrigerant lines: 100 

ft.

•  Maximum elevation difference, compressor base to indoor 

coil base (compressor higher or lower): 50 feet. 

NOTE:

 An 

oil trap is required for elevations exceeding 50 feet.

•  Refrigerant  lines  should  NOT  be  buried  (in  concrete  or 

otherwise).

•  Refer  to  the  Application  Guideline  for  Refrigerant  Lines 

Over 75 Feet document 044B-0600, for piping details.

Once the above information has been confirmed and potential 

questions regarding location, refrigerant line routing, and 

wire routing have been resolved, proceed with unpacking the 

equipment. It is strongly recommended that inspection of the 

hardware be performed prior to bringing it to the installation 

site. Inspect for cosmetic as well as functional damage (such 

as obvious holes or gaps in tubes and joints, cut or pinched 

wires or wire insulation).
Verify that the iQ Drive

®

 air conditioner unit package includes 

the following:
•  Coil/compressor/control unit.

•  Packet containing installation instructions and one filter-

drier.

Figure 1. Unit Envelope Dimensions

EXTERIOR WALL

CONTROL

PANEL

24”

For Service

Access

12”

12”

12”

Summary of Contents for FS4BG024K

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the unit or failure to follow safety warnings could result in serious injury de...

Page 2: ...e adjustment or maintenance may cause electrical shock or other hazardous conditions which may result in personal injury or property damage WARNING The information listed below and the next page must...

Page 3: ...eep snowdrift accumulation The support slab should be level Make sure that the drain holes in the bottom of the unit are not obstructed Roof Mounting The method used for roof mounting should be design...

Page 4: ...to interconnect the two stage thermostat the indoor unit and the outdoor unit The source of the 24 vac is located within the indoor unit air handler or furnace The C side of this power source may be g...

Page 5: ...d method of charging is by weighing in the additional refrigerant required If a charging scale is not available the next preferred charging method would be to use the sub cooling method After weighing...

Page 6: ...cle The operating speed history for both the current and the previous operating cycles For example with a first stage call in cooling if the setpoint was satisfied quickly within 20 minutes the unit w...

Page 7: ...tup delay can be skipped by shorting the two J4 Test pins indicated in Figure 7 for about 1 second while the compressor is off and waiting to start NOTE Use this feature with forethought because it wi...

Page 8: ...l only and none are active Also if no code numbers are displayed there have been no faults recorded or the history has been cleared NOTE As standard practice write down the fault codes in the historyb...

Page 9: ...oise if none the compressor may need to be replaced Check compressor phase to phase resistances they should all be less than 1 5 ohms and within 0 2 of each other If compressor noise is loud squealing...

Page 10: ...face Board Software Corruption This code indicates that the interface board needs to be replaced It should never be encountered Compressor Discharge Temp Sensor Failure This fault code indicates an op...

Page 11: ...11 FIGURES Charts Figure 2 Air Conditioner Control Panel Cover Removed Inverter black plastic case Interface Board Contactor Low Voltage Compartment...

Page 12: ...12 Figure 4 Low Voltage Compartment for Control Wiring Vapor Line Service Valve Liquid Line Service Valve Figure 5 Service Valves Figure 3 Power Wiring Terminals Wire Entry Ground Lug Contactor...

Page 13: ...oling Charging Chart Outdoor Temperature above 60 F Remove refrigerant if above curve Add refrigerant if below curve Liquid Line Temperature F Liquid Line Pressure psig 3 4 TON MODELS 2 TON MODELS 5 T...

Page 14: ...ay transformer kits 7 Ferrite chokes are shown by an ellipse enclosing wires The number of turns per wire through the choke is shown by for example 2X 7113640 6 14 HIGH PRESSURE SWITCH 12V GND DX DX I...

Page 15: ...s shown by for example 2X FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 7113710 6 14 HIGH PRESSURE SWITCH 12V GND DX DX INTERFACE BOARD REV VLV OUTDOOR TEMP 2 P M E T L I O C 1 P M E T L I O C SUCTION...

Page 16: ...3 4 5 6 7 8 9 10 Deg F k Temperature vs Resistance for All Thermistors Part 1 10 0 10 20 30 40 50 60 70 80 10 20 30 40 50 60 70 80 90 100 Deg F Temperature vs Resistance for All Thermistors Part 2 k...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety...

Reviews: