Maytag FS4BG024K Installation Instructions Manual Download Page 6

6

SYSTEM OPERATION

Thermostat

The primary control for the overall cooling system is provided 

by the indoor thermostat. Any standard two-stage thermostat 

will be sufficient for operation. Refer to the manual for the 

thermostat selected or installed for configuration and usage 

details.

Blower Flow Rates

Depending on the indoor equipment installed, blower air flow 

may be adjustable. When paired with a matching model air 

handler or gas furnace, the airflow is set by DIP switches on 

the blower control board, providing one flow for second stage 

compressor speeds and a lower flow for first stage compressor 

speeds. Refer to the indoor equipment manuals for instructions 

on how to select the desired air flows. High stage airflows used 

for equipment ratings are as follows:

•  2 ton - 810 cfm

•  3 ton - 1050 cfm

•  4 ton - 1480 cfm

•  5 ton - 1675 cfm

Refer to indoor equipment installation instructions for options, 

operation, and field wiring relating to dehumidification and 

humidification.

Start-Up Sequence

The recommended sequence is to provide 208/230 volt line 

power to the outdoor unit first (via the disconnect), then apply 24 

vac control power second. This sequence will avoid generating 

potentially confusing fault codes, which will continue to be 

displayed as part of fault history when the unit is subsequently 

operating normally.

Run Sequence

After power-up and between cycles (after the preceding 

shutdown) there will always be a five minute compressor 

(re)start delay imposed. With a call for cooling and before 

the compressor is turned on, the outdoor fan will run for one 

minute to assure that the outdoor temperature measurement 

is close to that of the ambient air. The compressor will then 

ramp up to a speed selected by the capacity control scheme.
The 20 SEER air conditioner is a true variable speed unit. 

Normally  the  compressor  will  operate  at  one  of  5  cooling 

speeds, each predetermined for a balance of optimum 

efficiency and capacity.The outdoor fan motor will also operate 

at multiple speeds, following the compressor.

The speeds used will depend on several factors, including:

•  Whether first or second stage operation is called for by the 

thermostat (which must be two stage-capable),

•  Outdoor ambient temperature.

•  The length of time the equipment has been operating during 

the current cycle

•  The operating speed history, for both the current and the 

previous operating cycles.

For example, with a first stage call in cooling, if the setpoint 

was satisfied quickly (within 20 minutes), the unit will restart 

the next time at a lower speed. At a low or intermediate speed, 

if the setpoint is not satisfied within 45 minutes, the speed 

will be increased. If the unit cycles off after having a speed 

increase, the entire next cycle will be at the higher speed. 

Also, the outdoor fan will run for an extra minute after the 
compressor shuts off at the end of a cycle.

Charging Operation

For charging in the field, the unit should be run with a call for 

second stage cooling, with both 

Y1

 and 

Y2

 outputs energized. 

This may be accomplished by setting the thermostat to cool 

with a setpoint substantially lower than room temperature. 

This will provide 45 minutes of operation at the nominal rating 

speed (interface board display “

C4

”) before there is a speed 

change (to a higher speed). If this speed change occurs before 

the charging process is complete, turn the system off, turn 

control power off and on again, and then restart the process.

Alternate Procedure for Charging the Air 

Conditioner in Cooling Mode

With outdoor temperature above 60° F (Based on 

Subcooling):

While charging based on weight is preferred, this method is 

acceptable. Use this method when the outdoor temperature 

is  60°  F  or  higher  to  verify  the  correct  charge. The  indoor 

temperature should be between 70° F and 80° F.

1. Connect the gauge manifold to the liquid and vapor service 

valves. See 

Figure 5 (page 

12)

.

2. Start the system in cooling mode. Allow the system to run 

15 minutes to stabilize.

3. Record the refrigerant pressure in psig at the liquid service 

valve.

4. Record the liquid refrigerant line temperature (in ° F) at or 

near the liquid service valve.

5. Using  the  temperature  value  recorded,  determine  the 

corresponding liquid refrigerant pressure from the curve 

in the charging chart appropriate for the unit model. See 

Figure 6 (page 

13)

.

•  If the pressure measured in step 3 is less than the required 

liquid  refrigerant  pressure  determined  in  step  5,  then 

refrigerant needs to be added.

•  If  the  pressure  measured  in  step  3  is  greater  than  the 

required liquid refrigerant pressure determined in step 5, 

then the system is over-charged.

6. Add or remove charge from the system depending on the 

measurements recorded. Allow the system to stabilize for 

15 minutes before taking the next readings.

Summary of Contents for FS4BG024K

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the unit or failure to follow safety warnings could result in serious injury de...

Page 2: ...e adjustment or maintenance may cause electrical shock or other hazardous conditions which may result in personal injury or property damage WARNING The information listed below and the next page must...

Page 3: ...eep snowdrift accumulation The support slab should be level Make sure that the drain holes in the bottom of the unit are not obstructed Roof Mounting The method used for roof mounting should be design...

Page 4: ...to interconnect the two stage thermostat the indoor unit and the outdoor unit The source of the 24 vac is located within the indoor unit air handler or furnace The C side of this power source may be g...

Page 5: ...d method of charging is by weighing in the additional refrigerant required If a charging scale is not available the next preferred charging method would be to use the sub cooling method After weighing...

Page 6: ...cle The operating speed history for both the current and the previous operating cycles For example with a first stage call in cooling if the setpoint was satisfied quickly within 20 minutes the unit w...

Page 7: ...tup delay can be skipped by shorting the two J4 Test pins indicated in Figure 7 for about 1 second while the compressor is off and waiting to start NOTE Use this feature with forethought because it wi...

Page 8: ...l only and none are active Also if no code numbers are displayed there have been no faults recorded or the history has been cleared NOTE As standard practice write down the fault codes in the historyb...

Page 9: ...oise if none the compressor may need to be replaced Check compressor phase to phase resistances they should all be less than 1 5 ohms and within 0 2 of each other If compressor noise is loud squealing...

Page 10: ...face Board Software Corruption This code indicates that the interface board needs to be replaced It should never be encountered Compressor Discharge Temp Sensor Failure This fault code indicates an op...

Page 11: ...11 FIGURES Charts Figure 2 Air Conditioner Control Panel Cover Removed Inverter black plastic case Interface Board Contactor Low Voltage Compartment...

Page 12: ...12 Figure 4 Low Voltage Compartment for Control Wiring Vapor Line Service Valve Liquid Line Service Valve Figure 5 Service Valves Figure 3 Power Wiring Terminals Wire Entry Ground Lug Contactor...

Page 13: ...oling Charging Chart Outdoor Temperature above 60 F Remove refrigerant if above curve Add refrigerant if below curve Liquid Line Temperature F Liquid Line Pressure psig 3 4 TON MODELS 2 TON MODELS 5 T...

Page 14: ...ay transformer kits 7 Ferrite chokes are shown by an ellipse enclosing wires The number of turns per wire through the choke is shown by for example 2X 7113640 6 14 HIGH PRESSURE SWITCH 12V GND DX DX I...

Page 15: ...s shown by for example 2X FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 7113710 6 14 HIGH PRESSURE SWITCH 12V GND DX DX INTERFACE BOARD REV VLV OUTDOOR TEMP 2 P M E T L I O C 1 P M E T L I O C SUCTION...

Page 16: ...3 4 5 6 7 8 9 10 Deg F k Temperature vs Resistance for All Thermistors Part 1 10 0 10 20 30 40 50 60 70 80 10 20 30 40 50 60 70 80 90 100 Deg F Temperature vs Resistance for All Thermistors Part 2 k...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety...

Reviews: