30

Blower Performance Data

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

SP1

590

540

483

429

369

311

247

203

SP2

690

643

597

547

498

443

389

343

SP3

750

702

660

618

572

525

477

421

SP4

876

832

794

758

716

678

641

598

SP5

927

881

841

806

771

734

698

662

SP6

1058

1015

976

945

915

881

849

818

SP7

1116

1071

1036

1003

975

943

919

884

SP8

1238

1192

1158

1124

1098

1070

1044

1016

SP9

1398

1357

1320

1293

1269

1239

1216

1194

SP1

587

542

490

437

382

318

266

207

SP2

685

638

590

543

498

448

392

339

SP3

856

814

774

732

693

657

622

581

SP4

937

892

855

819

786

752

715

684

SP5

1060

1017

981

950

921

886

856

828

SP6

1108

1068

1033

1003

972

942

914

882

SP7

1274

1233

1203

1174

1146

1118

1089

1065

SP8

1374

1340

1306

1278

1254

1227

1201

1179

SP9

1437

1395

1362

1332

1305

1278

1253

1228

SP1

836

774

711

655

596

523

456

397

SP2

1274

1228

1188

1147

1107

1064

1027

990

SP3

1295

1256

1214

1181

1140

1100

1062

1024

SP4

1385

1337

1301

1260

1222

1186

1149

1114

SP5

1454

1407

1372

1353

1325

1291

1255

1219

SP6

1528

1485

1438

1409

1383

1349

1317

1285

SP7

1619

1579

1551

1523

1495

1463

1430

1402

SP8

1746

1697

1667

1642

1617

1593

1570

1540

SP9

1772

1735

1698

1674

1645

1622

1598

1574

SP1

722

658

599

534

458

386

330

268

SP2

1270

1223

1179

1139

1105

1066

1029

996

SP3

1304

1254

1212

1173

1135

1104

1069

1032

SP4

1367

1318

1277

1236

1199

1169

1135

1102

SP5

1473

1429

1386

1355

1320

1289

1258

1224

SP6

1560

1518

1476

1441

1409

1382

1350

1321

SP7

1647

1605

1562

1531

1497

1467

1440

1408

SP8

1720

1710

1674

1642

1611

1581

1553

1527

SP9

1796

1759

1721

1687

1655

1628

1604

1578

SP1

1280

1228

1178

1134

1086

1036

986

936

SP2

1401

1356

1313

1273

1234

1190

1145

1099

SP3

1593

1550

1512

1475

1436

1399

1360

1319

SP4

1706

1662

1621

1586

1550

1515

1479

1444

SP5

1821

1775

1736

1703

1669

1636

1605

1576

SP6

1836

1793

1757

1721

1689

1659

1628

1592

SP7

1932

1888

1855

1825

1794

1762

1733

1701

SP8

2184

2143

2110

2072

2048

2017

1989

1959

SP9

2221

2178

2145

2109

2082

2053

2025

1992

THERMOSTAT 

CALL

TAP #

EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)

GM9S800403AU*

Y1/Y2

GM9S80-U COOLING AIFLOW

GM9S800603AU*

Y1/Y2

GM9S800604BU*

Y1/Y2

GM9S800804BU*

Y1/Y2

GM9S800805CU*

Y1/Y2

MODEL

Summary of Contents for Amana M9S80-U Series

Page 1: ...stat Location 9 COMBUSTION AND VENTILATION AIR REQUIREMENTS 10 CATEGORY I VENTING VERTICAL VENTING 10 MASONRY CHIMNEYS 11 Masonry Chimney Termination 11 ELECTRICAL CONNECTIONS 11 Wiring Harness 11 120...

Page 2: ...peed Selection 22 Heat Pump Heating Mode Speed Slection 22 Circulator Blower Fan Timing Adjustment 23 On Off Fan Delay Selection 23 OPERATIONAL CHECKS 23 Checking Duct Static 23 SAFETY CIRCUIT DESCRIP...

Page 3: ...ce qui peut entra ner la mort des blessures ou des dommages mat riels IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL I...

Page 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Page 5: ...ing precautions during furnace installation and servicing to protect the integrated control module from damage By putting the furnace the control and the person at the same electrostatic potential the...

Page 6: ...furnace A return air temperature range between 60 F 16 C and 80 F 27 C is maintained Air filters are installed in the system and replaced daily during construction and upon completion of construction...

Page 7: ...icals halogen type refrigerants printing inks cleaning solutions such as perchloroethylene paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers m...

Page 8: ...gas electrical and drain line connections NOTE In addition to the required clearances to combustible materials a minimum of 24 service clearance must be available in front of the unit Installation Po...

Page 9: ...ndition c In so far as practical close all building doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the build...

Page 10: ...oset or utility room must have two ventilation openings with a total minimum free area of 0 25 square inches per 1 000 BTU hr of furnace input rating Refer to Specification Sheet applicable to your mo...

Page 11: ...ation purposes Refer to the wiring diagram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rat...

Page 12: ...NG OR CHANGING ANY ELECTRICAL WIRING WARNING 4 Attach the junction box to the left side of the fur nace using the screws removed in step 2 5 Check the location of the wiring Confirm that it will not b...

Page 13: ...e is equipped with de di cated inch EAC and HUM relay terminals for controlling external power to an optional field supplied humidifier and or electronic air cleaner Additional line voltage wiring to...

Page 14: ...90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 0 5 psig or less and pressure drop of 0 3 W C Based on 0 60 Specific Gravity Gas CFH BTUH Furnace Input Heating Value of Gas BTU Cubi...

Page 15: ...he furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensa tion in the heating element With a parallel flow arrange ment the dampers or other means u...

Page 16: ...thermostat contacts close initiating a call for heat The control will display heat mode in status menu g h Integrated control module performs safety circuit checks Induced draft blower is energized fo...

Page 17: ...od The electronic air cleaner EAC and humidifier HUM relays will close the contacts After the thermostat is satisfied the compressor is de energized and the electronic air cleaner EAC and humidifier H...

Page 18: ...The control is now ready to receive demands from the room thermostat Refer to Status Menu in this manual for interpretation of items displayed in the status menu Quick Start Initial set up of outdoor...

Page 19: ...irculation blower will shut down when the time delay expires Time delay is selectable on all models 2 Turn off the electrical power supply to the furnace 3 Remove the burner compartment door 4 White R...

Page 20: ...re gauge at the gas valve outlet pressure tap See White Rodgers 36J22Y 204 gas valve Figure 13 for location of outlet pressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W...

Page 21: ...the supply air temperature to determine the air temperature rise Allow adequate time for thermometer readings to stabilize 4 Adjust temperature rise by adjusting the circulator blower speed Increase...

Page 22: ...Cooling Speed Table Gas Heating Mode Speed Selection To change the main blower speed in GAS HEATING mode see the following steps 1 Press menu button until LED displays gAF Press option button and LED...

Page 23: ...ic refers to everything external to the furnace cabinet Cooling coils filters ducts grilles registers must all be considered when reading your total external static pressure The supply duct pressure m...

Page 24: ...horizontal right and horizontal left installations Regardless of airflow direction it does not need to be relocated Burner Temperature Switch The burner temperature switch is mounted on the burner ass...

Page 25: ...lubricated by the manufacturer No further lubrication is required Check motor windings for accumulation of dust which may cause overheating Clean as necessary Flame Sensor Qualified Servicer Only Und...

Page 26: ...ailable from your distributor Functional Parts List Gas Valve Natural Gas Orifice Burner Assembly Hot Surface Igniter Flame Sensor Gas Manifold Ignition Control Blower Mounting Bracket Pressure Sensor...

Page 27: ...ntegrated Control Module 10 Transformer 11 Blower Door Interlock Switch 12 Circulator Blower Tubular Heat Exchanger Pressure Sensor Assembly Flue Pipe Connection Gas Line Entrance Gas Valve Inducer Ga...

Page 28: ...o call for heat Correct short at flame sensor or in flame sensor wiring Short to ground in flame sense circuit Lingering burner flame Slow closing gas valve Open fuse Replace fuse Short in low voltage...

Page 29: ...sor and pressure switch Check Red Black Green harness connections to pressure sensor control board Replace pressure sensor Check Red Black Green harness connections to pressure sensor control board Re...

Page 30: ...72 1353 1325 1291 1255 1219 SP6 1528 1485 1438 1409 1383 1349 1317 1285 SP7 1619 1579 1551 1523 1495 1463 1430 1402 SP8 1746 1697 1667 1642 1617 1593 1570 1540 SP9 1772 1735 1698 1674 1645 1622 1598 1...

Page 31: ...1485 30 1438 31 1409 32 1383 32 1349 1317 1285 SP7 1619 27 1579 28 1551 29 1523 29 1495 30 1463 1430 1402 SP8 1746 25 1697 26 1667 27 1642 27 1617 27 1593 1570 1540 SP9 1772 25 1735 26 1698 26 1674 27...

Page 32: ...9 R233 R243 R245 NTC1 R209 R212 R215 R219 R227 R231 R248 R261 R208 R283 R61 R86 R87 R103 R107 R141 R203 Y1 Y2 R76 R238 R262 R8 R40 R44 R45 R46 R55 R70 R74 R75 R81 CR1 CR8 CR11 CR12 C R15 CR16 CR2 0 CR...

Page 33: ...lta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG Natural Ga...

Page 34: ...34 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 35: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 36: ...rchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the...

Reviews: