repeated wetting by liquids such as water (except rain 

water), detergents, or sewage. The gas piping may 

enter the left or right side of the furnace cabinet. The 

installer must supply rigid pipe long enough to reach 

the outside of the cabinet to seal the grommet cabinet 

penetration. A semi-rigid connector to the gas piping 

can be used outside the cabinet per local codes. 1/2” 

NPT pipe and fittings are required. Model requires 

one 90 deg elbow, one 2” nipple and additional nipple 

to reach outside the cabinet. A semi-rigid connector 

to the gas piping can be used outside the cabinet 

per local codes. From the elbow, the length of pipe 

and the fittings required will vary by the side chosen, 

location of union and cabinet width. The union may 

be placed inside or outside of the cabinet.

General Furnace Layout

Figure 8

Upflow Installations

A ground joint union, drip leg, and manual shutoff valve must 

also be supplied by the installer. In some cases, the installer 

may also need to supply a transition piece from 1/2” to another 

pipe size.
When the gas piping enters through the side of the furnace, 

the installer must supply the following fittings (starting from 

the gas valve nipple elbow):

• 

Straight pipe to reach the exterior of the furnace.

• 

A ground joint union, drip leg, and manual shutoff 

valve must also be supplied by the installer.

Gas Piping Checks 

Before placing unit in operation, leak test the unit and gas 

connections.  

T

O

 

AVOID

 

THE

 

POSSIBILITY

 

OF

 

EXPLOSION

 

OR

 

FIRE

NEVER

 

USE

 

A

 

MATCH

 

OR

 

OPEN

 

FLAME

 

TO

 

TEST

 

FOR

 

LEAKS

.

WARNING

Check for leaks using an approved chloride-free soap and 

water solution, an electronic combustible gas detector, or 

other approved testing methods.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

Nominal Black  Pipe Size

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on

0.60 Specific Gravity Gas)

CFH = BTUH Furnace Input   

Heating Value of Gas (BTU/Cubic Foot)

Table 6

To connect the furnace to the building’s gas piping, the installer 

must supply a ground  joint union, drip leg, manual shutoff 

valve, and line and fittings to connect to gas valve.  In some 

cases, the installer may also need to supply a transition piece 

from 1/2” pipe to a larger pipe size.
The following stipulations apply when connecting gas piping.  

• 

Gas piping must be supported external to the furnace 

cabinet so that the weight of the gas line does not 

distort the burner rack, manifold or gas valve. 

• 

Use black iron or steel pipe and fittings for the building 

piping. Where possible, use new pipe that is properly 

chamfered, reamed, and free of burrs and chips. If 

old pipe is used, be sure it is clean and free of rust, 

scale, burrs, chips, and old pipe joint compound. 

•  Use pipe joint compound on male threads ONLY. 

Always use pipe joint compound (pipe dope) that 

is APPROVED FOR ALL GASSES. DO NOT apply 

compound to the first  two threads.

• 

Use ground joint unions.

• 

Install a drip leg to trap dirt and moisture before it can 

enter the gas valve.  The drip leg must be a minimum 

of three inches long.

• 

Install a 1/8” NPT pipe plug fitting, accessible for test 

gage connection, immediately upstream of the gas 

supply connection to the furnace.

•  Always use a back-up wrench when making the 

connection to the gas valve to keep it from turning. 

The orientation of the gas valve connection is 374 

in-lbs; excessive over-tightening may damage the 

gas valve and/or gas manifold assembly. 

•  Install a manual shutoff valve between the gas 

meter and unit within six feet of the unit.  If a union 

is installed, the union must be downstream of the 

manual shutoff valve, between the shutoff valve and 

the furnace.

• 

Tighten all joints securely.

•  Protect connectors and semi-rigid tubing against 

physical and thermal damage when installed.  Ensure 

aluminum-alloy tubing and connectors are coated to 

protect against external corrosion when in contact 

with masonry, plaster, or insulation, or subjected to 

Summary of Contents for Amana M9S80-U Series

Page 1: ...stat Location 9 COMBUSTION AND VENTILATION AIR REQUIREMENTS 10 CATEGORY I VENTING VERTICAL VENTING 10 MASONRY CHIMNEYS 11 Masonry Chimney Termination 11 ELECTRICAL CONNECTIONS 11 Wiring Harness 11 120...

Page 2: ...peed Selection 22 Heat Pump Heating Mode Speed Slection 22 Circulator Blower Fan Timing Adjustment 23 On Off Fan Delay Selection 23 OPERATIONAL CHECKS 23 Checking Duct Static 23 SAFETY CIRCUIT DESCRIP...

Page 3: ...ce qui peut entra ner la mort des blessures ou des dommages mat riels IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL I...

Page 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Page 5: ...ing precautions during furnace installation and servicing to protect the integrated control module from damage By putting the furnace the control and the person at the same electrostatic potential the...

Page 6: ...furnace A return air temperature range between 60 F 16 C and 80 F 27 C is maintained Air filters are installed in the system and replaced daily during construction and upon completion of construction...

Page 7: ...icals halogen type refrigerants printing inks cleaning solutions such as perchloroethylene paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers m...

Page 8: ...gas electrical and drain line connections NOTE In addition to the required clearances to combustible materials a minimum of 24 service clearance must be available in front of the unit Installation Po...

Page 9: ...ndition c In so far as practical close all building doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the build...

Page 10: ...oset or utility room must have two ventilation openings with a total minimum free area of 0 25 square inches per 1 000 BTU hr of furnace input rating Refer to Specification Sheet applicable to your mo...

Page 11: ...ation purposes Refer to the wiring diagram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rat...

Page 12: ...NG OR CHANGING ANY ELECTRICAL WIRING WARNING 4 Attach the junction box to the left side of the fur nace using the screws removed in step 2 5 Check the location of the wiring Confirm that it will not b...

Page 13: ...e is equipped with de di cated inch EAC and HUM relay terminals for controlling external power to an optional field supplied humidifier and or electronic air cleaner Additional line voltage wiring to...

Page 14: ...90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 0 5 psig or less and pressure drop of 0 3 W C Based on 0 60 Specific Gravity Gas CFH BTUH Furnace Input Heating Value of Gas BTU Cubi...

Page 15: ...he furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensa tion in the heating element With a parallel flow arrange ment the dampers or other means u...

Page 16: ...thermostat contacts close initiating a call for heat The control will display heat mode in status menu g h Integrated control module performs safety circuit checks Induced draft blower is energized fo...

Page 17: ...od The electronic air cleaner EAC and humidifier HUM relays will close the contacts After the thermostat is satisfied the compressor is de energized and the electronic air cleaner EAC and humidifier H...

Page 18: ...The control is now ready to receive demands from the room thermostat Refer to Status Menu in this manual for interpretation of items displayed in the status menu Quick Start Initial set up of outdoor...

Page 19: ...irculation blower will shut down when the time delay expires Time delay is selectable on all models 2 Turn off the electrical power supply to the furnace 3 Remove the burner compartment door 4 White R...

Page 20: ...re gauge at the gas valve outlet pressure tap See White Rodgers 36J22Y 204 gas valve Figure 13 for location of outlet pressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W...

Page 21: ...the supply air temperature to determine the air temperature rise Allow adequate time for thermometer readings to stabilize 4 Adjust temperature rise by adjusting the circulator blower speed Increase...

Page 22: ...Cooling Speed Table Gas Heating Mode Speed Selection To change the main blower speed in GAS HEATING mode see the following steps 1 Press menu button until LED displays gAF Press option button and LED...

Page 23: ...ic refers to everything external to the furnace cabinet Cooling coils filters ducts grilles registers must all be considered when reading your total external static pressure The supply duct pressure m...

Page 24: ...horizontal right and horizontal left installations Regardless of airflow direction it does not need to be relocated Burner Temperature Switch The burner temperature switch is mounted on the burner ass...

Page 25: ...lubricated by the manufacturer No further lubrication is required Check motor windings for accumulation of dust which may cause overheating Clean as necessary Flame Sensor Qualified Servicer Only Und...

Page 26: ...ailable from your distributor Functional Parts List Gas Valve Natural Gas Orifice Burner Assembly Hot Surface Igniter Flame Sensor Gas Manifold Ignition Control Blower Mounting Bracket Pressure Sensor...

Page 27: ...ntegrated Control Module 10 Transformer 11 Blower Door Interlock Switch 12 Circulator Blower Tubular Heat Exchanger Pressure Sensor Assembly Flue Pipe Connection Gas Line Entrance Gas Valve Inducer Ga...

Page 28: ...o call for heat Correct short at flame sensor or in flame sensor wiring Short to ground in flame sense circuit Lingering burner flame Slow closing gas valve Open fuse Replace fuse Short in low voltage...

Page 29: ...sor and pressure switch Check Red Black Green harness connections to pressure sensor control board Replace pressure sensor Check Red Black Green harness connections to pressure sensor control board Re...

Page 30: ...72 1353 1325 1291 1255 1219 SP6 1528 1485 1438 1409 1383 1349 1317 1285 SP7 1619 1579 1551 1523 1495 1463 1430 1402 SP8 1746 1697 1667 1642 1617 1593 1570 1540 SP9 1772 1735 1698 1674 1645 1622 1598 1...

Page 31: ...1485 30 1438 31 1409 32 1383 32 1349 1317 1285 SP7 1619 27 1579 28 1551 29 1523 29 1495 30 1463 1430 1402 SP8 1746 25 1697 26 1667 27 1642 27 1617 27 1593 1570 1540 SP9 1772 25 1735 26 1698 26 1674 27...

Page 32: ...9 R233 R243 R245 NTC1 R209 R212 R215 R219 R227 R231 R248 R261 R208 R283 R61 R86 R87 R103 R107 R141 R203 Y1 Y2 R76 R238 R262 R8 R40 R44 R45 R46 R55 R70 R74 R75 R81 CR1 CR8 CR11 CR12 C R15 CR16 CR2 0 CR...

Page 33: ...lta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG Natural Ga...

Page 34: ...34 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 35: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 36: ...rchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the...

Reviews: