4
The ARUF**14** and ASPT**14** product lines may be in-
stalled in one of the upflow, downflow, horizontal left or hori
-
zontal right orientations as shown in Figures 2, 3, 4 and 5. The
unit may be installed in upflow or horizontal left orientation as
shipped (refer to specific sections for more information).
No field modifications are mandatory. However, to obtain
maximum efficiency, the horizontal drip shield, side drain
pan and drain pan extension can be removed.
Side Drain Pan and Extension Removal:
Refer to Figure
1, remove the two (2) screws that secure the drip shield sup-
port brackets to the condensate collectors (front and back).
Unsnap the side drain pan from the bottom drain pan using
a screw driver or any small lever. The side drain pan, drip
shield brackets and the drain pan extension may now be re-
moved. From Figure 1, drain port labeled (A) is the primary
drain for this application and condensate drain line must be
attached to this drain port. Drain port (a) is for the second-
ary drain line (if used). If the side drain pan is removed, the
drain port opening in the access panel must be covered by
the accessory drain port plug (DPK1) as shown in figure 1.1.
SIDE DRAIN PAN
DPK1 DRAIN PLUG
COIL ACCESS PANEL
MAIN DRAIN PAN
DRAIN PAN
Figure 1.1
Kit Number
Application
DPK1
All Models
Side Drain Port Plug
Description
Drain Port Plug
DRAIN PORT PLUG KIT
Table 1
Drip Pan
Extension
Side
Drain
Pan
Screw
B
b
A
Main Drain Pan
Drip Shield Bracket
Drip Shield
Pn
a
SIDE DRAIN PAN REMOVAL
Figure 1
6.1 Upflow Installation
No field modifications are mandatory.
6.2 Horizontal Left Installation
No field modifications are permissible for this application.
Install unit as shown in Figure 4.
Remove red plugs from side drain pan before connecting
condensate drain pipes. Use removed plug to close drain
ports on vertical drain pan. The bottom right drain connec-
tion in side drain pan is the primary drain for this application
and condensate drain line must be attached to this drain
connection. The bottom left drain connection in side drain
pan is for the secondary drain line (if used).
In applications where the air handler is installed in the hor-
izontal left position, and the return air environment see hu-
midity levels above 65% relative humidity coupled with to-
tal external static levels above 0.5” e.s.p., a condensate kit
is available for field application. Kit nomenclature can be
found in Table 2.
CMK0008
Condensate
Kit
CMK0009
Condensate
Kit
CMK0010
Condensate
Kit
CMK0011
Condensate
Kit
CMK0012
Condensate
Kit
CMK0013
Condensate
Kit
CMK0014
Condensate
Kit
ARUF25B14 ARUF31B14 ARUF37C14 ARUF47D14 ARUF61D14 ASPT33C14 ASPT49C14
ARUF29B14 ASPT29B14 ARUF37D14
ASPT49D14 ASPT39C14
ASPT25B14 ASPT37B14 ARUF43C14
ASPT61D14
ARUF43D14
ARUF49C14
ARUF49D14
ASPT37C14
ASPT47C14
ASPT47D14
ASPT59C14
CONDENSATE KIT
Table 2