PRODUCT DESIGN
36
Cooling Mode
The normal operational sequence in cooling mode is as
follows:
1. R and Y thermostat contacts close, initiating a call for
cool.
2. Integrated control module performs safety circuit
checks.
3. Outdoor fan and compressor are energized.
4. Circulator blower is energized on cool speed following
a fixed five (5) second on delay. Electronic air cleaner
terminals are energized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run,
integrated control module monitors safety circuits con-
tinuously.
6. R and Y thermostat contacts open, completing the call
for cool.
7. Outdoor fan and compressor are de-energized.
8. Circulator blower is de-energized following a fixed forty
five (45) second cool off delay period. Electronic air
cleaner terminals are de-energized.
9. Furnace awaits next call from thermostat.
Fan Only Mode
The normal operational sequence in fan only mode is as
follows:
1. R and G thermostat contacts close, initiating a call for
fan.
2. Integrated control module performs safety circuit
checks.
3. Circulator blower is energized on
heat speed
. Elec-
tronic air cleaner terminals are energized.
4. Circulator blower runs, integrated control module moni-
tors safety circuits continuously.
5. R and G thermostat contacts open, completing the call
for fan.
6. Circulator blower is de-energized. Electronic air
cleaner terminals are de-energized.
7. Furnace awaits next call from thermostat.