12
Maysun Solar modules can be installed with the use ofthird party listed grounding devices for grounding the
metallic frames of PV modules. The devices have to be installed in accordance with the grounding device
manufacturer’ s specified instructions.
Maysun Solar modules can be installed with the use ofthird party listed grounding devices for grounding the
metallic frames of PV modules. The devices have to be installed in accordance with the grounding device
manufacturer’ s specified instructions.
Please refer to the “Product Catalogue” link for detailed grounding hole location and size at
Method 1: Tyco grounding bolt # 2058729-1:
4
5
Figure 4.
Tyco grounding bolt # 2058729- 1
1)Wire bolt and slot
3 ) Aluminum frame
5) Hex Nut
2 ) Mounting wash hex nut
4
) 0.006 to 0.025in
2
cable
Tyco grounding hardware comes in a package that includes the grounding bolt, mounting and grounding
hex nut.
Electrical contact is made by penetrating the anodized coating ofthe aluminum frame, and tightening
the mounting hex nut (come with the star washer) to the proper torque of 25lb f.in.
Grounding wire size (6 to 12 AWG solid bare copper) should be selected and installed underneath the
wire binding bolt.
The wire binding bolt should be tightened to the proper torque of45 lbf.in.
Summary of Contents for MS M-36 Series