011221 v3.11-RiA
Operating Instructions SG-EFS 104/4L
Page 13/17
1. Make sure no sensors are activated.
-
The green “Power” LED is lit
-
OSSDs 1, 2 and 3 are open
-
The signal output is closed
2. Activate the reset button.
-
The green “Power”, “Channel 1” and “Channel 2” LEDs are lit
-
OSSDs 1, 2 and 3 are closed
-
The signal output is open
3. Activate the sensor.
-
The green “Channel 1” and “Channel 2” LEDs go out
-
OSSDs 1, 2 and 3 are open
-
The signal output is closed
4. Repeat step 2.
5. Disconnect the sensor.
-
The green “Channel 1” and “Channel 2” LEDs go out
-
OSSDs 1, 2 and 3 are open
-
The signal output is closed
Commissioning
Function test: manual reset
Recommissioning
Ä
Carry out the commissioning process (see
Commissioning
).
Decommissioning
Ä
Disconnect the protective device and secure it to prevent unintentional recon-
nection.
Ä
Attach a clear notice to the protective device stating that it is temporarily or per-
manently out of service.