Intelligent Analogue Addressable Fire Alarm Control Panels
1- INTRODUCTION
Maxlogic ML-121X series intelligent analogue addressable fire alarm control panels are
provided with 0, 1, 2 loop options and 1000 user-defined zone capacity. Up to 127 analogue
addressable devices per loop are allowed to be connected.
Devices operating with VIP protocol such as Photo-Electric Smoke Detectors, Heat Detectors,
Multi-Sensor Detectors, Switch Monitor Modules, Relay Controller Modules, Sounder
Controller Modules, Loop-powered Addressable Sounders and Zone Monitor Modules are
compatible with ML-121X series control panels.
The project planning must be made carefully, in order not to have any difficulties when
commissioning the system. Zone location text (up to 40 characters including blank spaces) for
each device should be predetermined. Then, the devices should be categorized in zones
depending on the physical specifications of the building. After these steps, the panel can be
configured via the software program called
‘Loop Manager’.
The panel is equipped with 4 programmable and fault monitored 24 V DC 500mA sounder
outputs. Panel also contains 3 volt-free 30 V DC 1A relay outputs (fire relay, alarm relay, fault
relay) and a 24V DC 500mA auxiliary power supply output. Furthermore, 4 remote control
inputs (alarm, silence/sound alarm, reset and fault) exist in the panel.
ML-121X series fire alarm control panels have the optional functions described in TS EN 54-2
standards;
Sounder outputs
ML-121X series fire alarm control panels have also the supporting functions described in TS
EN 54-2 standards;
Network: The supporting function used to communicate in network.
NOTE: This user manual is valid for the panel models indicated in 14
th
section.
Producer-manufacturer or importer firms’ title, address, and telephone number
Manufacturer Firm:
MAVILI ELEKTRONIK TICARET VE SANAYI A.S.
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY
TEL: +90 216 466 45 05 - +90 216 466 45 10
Service stations’ communication information that related spare parts have been
provided
Authorized Services:
MAVILI ELEKTRONIK TICARET VE SANAYI A.S.
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY
TEL: +90 216 466 45 05 - +90 216 466 45 10
TEKSIS TEKNIK ELEKTRONIK SIS.TIC. VE SAN. LTD. STI.
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/3 UMRANIYE / ISTANBUL / TURKEY
TEL: +90 216 313 60 60 - +90 216 313 47 49
Expected operation life which has been determined and announced by related ministry
This device’s expected operation life is 7 years.
Summary of Contents for ML-121X
Page 29: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 29 ANNEX B CONNECTION SCHEME...
Page 30: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 30 ANNEX C PANEL SPARE PARTS...
Page 31: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 31 ANNEX D SERIAL COMMUNICATION CABLE...
Page 32: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 32 ANNEX E SCHEME OF MENU FUNCTIONS...
Page 33: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 33...
Page 34: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 34...
Page 35: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 35...
Page 36: ...ANNEX F NETWORK CONNECTION SCHEME KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 36...