![Maxlogic ML-121X Operating And Maintenance Manual Download Page 23](http://html1.mh-extra.com/html/maxlogic/ml-121x/ml-121x_operating-and-maintenance-manual_1745022023.webp)
KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 23
+Manual Control:
When this option is selected, all system
devices are checked instantaneously for contamination. Interrogation count for measuring
contamination status is selected between 8-255. The interrogation count represents the
amount of measurements. An analogue value greater than
75
is considered as the
contamination threshold by the panel. Upon detecting any contaminated device, device(s)
listed. After cleaning devices the contamination control should be repeated.
Loop: n
+Measure
-Interrogation Count: x
-List Results
-Print Results
+Automatic Control
+Interrogation Count: x
-Measuring Contamination Status
+Manual Control
-Measure
-Interrogation Count: x
+List Results
+Print Results
C o n t a m i n a t i o n C o n t r o l
M G 9 1 0 0
O p t
. S m o k
e
D e
t .
Z
o n
e : 1
P : 1 L : 1 A : 4 3
C o n t a m i n a t e d
d e v i
c e
_ _ _ _ _ _ _
_ _ _ _ _ _ _ _
_ _ _ _ _
_ _ _ _
_
_ _ _ _
_ _ _ _ _ _ _ _ _ _ _
[ U p / D o w n ] : S c r o
l l
[ E n t e r ] : U p d a t e
-Analog Update:
Due to this feature, the analogue values of system devices
can periodically be followed.
Note:
See, Annex-E Menu Functions Scheme for switch between menu functions.
12- NETWORKING PRINCIPLES
So that Maxlogic series fire alarm control panels can operate in network, each panel must contain 1 unit
of ML-1201 Network Module.
Please, see Section
“15- Panel Models” which includes ML-121X
.N
models having network module by
default. ML-1201 Network Module should NOT be added for those panels which have a network
module by default.
ML-1201 Network Module is compatible with all Maxlogic Series Intelligent Analogue Addressable Fire
Alarm Control Panels.
Up to 64 Maxlogic Series Intelligent Analogue Addressable Fire Alarm Control Panels can operate in a
network structure.
“16 loops x 127 devices x 64 panels = 130.048 devices” can operate in a network.
Summary of Contents for ML-121X
Page 29: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 29 ANNEX B CONNECTION SCHEME...
Page 30: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 30 ANNEX C PANEL SPARE PARTS...
Page 31: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 31 ANNEX D SERIAL COMMUNICATION CABLE...
Page 32: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 32 ANNEX E SCHEME OF MENU FUNCTIONS...
Page 33: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 33...
Page 34: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 34...
Page 35: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 35...
Page 36: ...ANNEX F NETWORK CONNECTION SCHEME KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 36...