CALIBRATION
www.maxcessintl.com
DLCA NET-IP65-ECAT
MI 850A366 1
Page 37 of 44
If the returned tension values in the cyclic data are negative,
you will need to manually set the
Tension Polarity
parameter
(0x216 or 0x223) so that the tension values are positive.
The following parameters in the group
Configuration Tension 1
or
Configuration Tension 2
are set by the calibration procedure.
Parameter
Name
Default
Range
0x208 or 0x218 ADC PGA Gain 1
5
{0, 7}
0x209 or 0x219 Display Tension 1A Zero Offset
0
{-0xFFFFFF,
0xFFFFFF}
0x20A
Display Tension 1B Zero Offset (IP65 1 only)
0
{-0xFFFFFF,
0xFFFFFF}
0x20E or 0x21B
Display Tension 1 Scale
623
{0, 0x7FFFFFFF}
0x20F or 0x21C Display Tension 1 Number Format
0x10
{0, 0xFF}
The above parameter set is determined by the DLCA NET-IP65-ECAT
during calibration. Do not modify the value of these parameters. The
parameters above, along with those in the following list, may be read
from a DLCA NET IP65-ECAT and can be sent to the same DLCA NET IP65-
ECAT to restore a corrupted calibration if needed.
Decimal Point Position
Maximum Tension
Load Cell Rating
Web Wrap Angle
Angle from Force Direction
Load Cell Sensitivity
Tension Polarity
Load Cell Excitation Voltage
Which Sensor Inputs Used
T = Web Tension
W = Roller weight
R = Resultant force from web tension
X = Web Wrap Angle
Y = Angle from resultant force direction
Figure 5. Weightless Calibration Angles