i-32V5H MIDI
Chiller and Inverter Air/Water heat pumps with axial fan
33
9.4.2
Model i-32V5H MIDI 0126
Operating limits
COLD source
OUTDOOR AIR
Operating temperature (cut-off)
min
-20°C
max
35°C
HOT source
WATER
Operating temperature (cut-off)
min
25°C
max
60°C
Useful heating capacity / COP at nominal conditions with defrosting contibution
Useful heating capacity [kW]
COP
DC
T
air
(cold
source)
T
water
(hot source)
T
air
(cold
source)
T
water
(hot source)
35
45
55
35
45
55
-7
17,3
17,3
17,0
-7
2,44
2,14
1,80
2
24,1
24,0
23,4
2
3,49
2,92
2,37
7
26,0
25,8
25,1
7
4,04
3,28
2,64
12
25,3
25,0
24,1
12
4,70
3,83
2,64
Performance data measured under partial load conditions according to UNI EN 14825
Operating conditions
F
A (E)
B
C
D
T
air
[°C]
-10
-7
2
7
12
PLR
[%]
100
88
54
35
15
Power DC
(Declared Capacity)
[kW]
15,4
17,4
10,6
9,3
10,7
COP
PL
2,27
2,49
3,93
4,88
6,53
COP
DC
2,26
2,44
3,49
4,04
4,70
Performance
35 °C
SCOP
ηs
Energy class
3,95
155%
A++