The  addition  of  an  expansion  module  allows  to  manage  by  mean  of  the  controller  beyond  to  an  external  modulating  or  two 
positions 3-way valve, both the free cooling regulation and the  circulators of the desuperheater and of the  total heat recovery, 
and the eventual double pumps with alternating optimized use of them according to the number of unit’s working hours. 

5.9

 

CONTROL AND PROTECTION DEVICES 

The units are standard equipped with the following control and protection devices: 3-phase monitor allows to stop the unit if the 
phase sequence is incorrect or if the voltage of at least one phase is different with 15% from the others, return water temperature 
sensor with antifreeze function which is installed on the return water pipe line from the plant circuit, operation sensor installed on 
the water return pipe from plant circuit, low pressure transducer, high pressure transducer, compressors discharge temperature, 
relief valve on low pressure side which opens at temperatures higher than 68°C, compressor inlet temperature sensor, suctions 
compressors suction temperature sensors, air outside temperature sensor (HWA1-H), thermal protection switch for fan motors, 
thermal  protection  on  each  compressor,  water  side  flow  switch  to  protect  the  evaporator,  high  pressure  HP  flow  switch  with 
manual reset installed on the outlet pipe of the compressors near the high pressure intake of service. The below components are 
supplied also as standard: 

 

  The  integral  protection  module  which  is  installed  inside  the  compressors’  electrical  box  which  detects  by  means  of  an 

included  sensor  the  real  winding  temperature  and  stops  the  compressor’s  operation  when  the  limit  temperature  is 
reached and is a required protection also for the operation with low evaporation pressures especially when the thermal 
protection on the power supply circuit is not sure. 

 

  High pressure transducer for condensation control, defrost cycle termination and shutdown of compressors in sequence 

according  to  the  maximum  permitted  pressure  (allows  to  produce  hot  water  at  50°C  even  with  outside  temperatures 
above 40°C in bi-compressor heat pump units). 

5.10

 

HYDRAULIC CIRCUIT 

The 

HWA1-A/HWA1-H

 series can be supplied with an incorporated hydronic kit which includes: in addition to the flow switch, and 

the other components already mentioned, pressure gauges at the inlet and pressure intake at the outlet of the heat exchanger to 
assess  the  load  losses,  one  or  two  circulating  pump  with  AC  motor  which  are  suitable  for  the  utilization  of  chilled  water  and 
directly managed by the controller on-board unit in both on-off and modulation operations depending on the adopted solution. 
It is also possible to install an internal inertial tank with external closed-cell foam insulation material and with capacity of about 
180 liters. 
The 3 way flow switching valve is also supplied in the free cooling versions joined together with the 3 row aluminum fins

-

copper 

piping heat exchanges. 

5.11

 

FAN SPEED CONTROL 

One-speed fan motors with high pressure transducer as standard, available also for chillers of two-speed fan motors of star/delta 
(Y-Δ) connection. This type of regulation controlled by the microprocessor is necessary for optimizing the condensation pressure in 
cooling  operation  mode  in  order  to  allow  the  correct  operation  of  the  unit  with  a  wide  outdoor  temperatures  range.  The 

modulating control inverter with EC brushless motor

 can be supplied as optional particularly for heat pump units or when the 

chilling operation mode is required at outdoor air temperatures below -5°C, this feature 

is supplied as standard on both cooling 

only and heat pump models HWA1-A 0285 and HWA1-H 0285

 

Summary of Contents for HWA1 0140

Page 1: ...rie Series Serie S rie Emissione Edition Au sgabeIssue HWA1 A H 10 2017 0140 0285 Catalogo Catalogue Katalog Brochure Sostituisce Superseedes Ersetzt Remplace AIR WATER CHILLERS AND HEAT PUMPS WITH AX...

Page 2: ...3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 11 7 4 HYDRAULIC CONNECTIONS 12 7 5 HYDRAULIC CIRCUIT 13 7 5 1 Drainage system 13 7 5 2 Plant circuit loading 14 7 5 3 Plant drainage system 14 7 6 REFRIGER...

Page 3: ...AND POWER INPUT CURVES IN COOLING MODE FOR HEAT PUMP VERSIONS 27 13 8 DECLARED TOTAL OUTPUT CAPACITIES AND POWER INPUT CURVES IN HEATING MODE TAKING INTO ACCOUNT OF THE DEFROSTING CYCLES ACCORDING TO...

Page 4: ...reference material It declines also any responsibility for possible inaccuracies in the manual if due to printing or transcription errors The customer shall store any updated copy of the manual or par...

Page 5: ...e health and safety laws including 89 391 CEE 89 686 CEE 2009 104 CE 86 188 CEE 89 655 CEE and 77 576 CEE should be respected by every employer who must oblige the employees to respect them It points...

Page 6: ...AEL 8 h e 12 h TWA 1000 ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier...

Page 7: ...ible through the front panel of the unit which allows also the monitoring of the inner components 5 4 AIR SIDE HEAT EXCHANGER The air side heat exchanger for chiller units is made entirely of aluminiu...

Page 8: ...quired protection also for the operation with low evaporation pressures especially when the thermal protection on the power supply circuit is not sure High pressure transducer for condensation control...

Page 9: ...tput capacity Water piping configuration Hydronic configuration Integrated tank kit Antifreeze Kit Plant system management module Fan motor type Silencing Coil treatment 00 Cooling only 01 40 kW 09 Re...

Page 10: ...only versions they are standard on heat pump models 3 Crankcase heaters for cooling only versions are standard in heat pump versions GI 0 Unit without plant management module 1 The additional module...

Page 11: ...at high temperatures Be sure to let the unit to become cool before beginning any maintenance work Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious...

Page 12: ...the next water flow Loading group and discharge valve where it s required WARNING Make sure that when determining the pipe sizes you should exceed the maximum head loss on the plant side please refer...

Page 13: ...rage Models HWA1 A HWA1 H with 1 or 2 pumps for storage tank and free cooling A Plate heat exchanger B Flow switch C Service valve D Manometer for inlet pressure E Air vent valve F Safety valve G AC c...

Page 14: ...nit in order to make easy the operation it is recommended to install externally two draining valves on the water inlet and on the water outlet between the unit and the manual gate valves 7 6 REFRIGERA...

Page 15: ...ature ST Compressor inlet temperature SV Solenoide valve 7 6 3 Total heat recovery HWA1 A unit Refrigerant circuit C Compressor DT Compressor outlet temperature EV Electronic expansion valve FD Unidir...

Page 16: ...let temperature CL Tandem collector SV N C Solenoid valve FM Mechanical filter NR Non return valve SD Desuperheated gas sensor SS DHW inlet temp sensor 7 6 5 Refrigerant circuit of HWA1 H 0140 0147 un...

Page 17: ...lector SV N C Solenoid valve FM Mechanical filter NR Non return valve 4WV 4 way valve 7 6 7 Total heat recovery HWA1 H unit refrigerant circuit in cooling only C Compressor DT Compressor outlet temper...

Page 18: ...t with a dedicated line if you use a residual current circuit breaker choose a four pole one with a trigger threshold of 300 mA and delayed triggering super resistant characteristic K The machine must...

Page 19: ...3 N for neutral line PE earth conductor Available for HWA1 A cooling only versions 7 8 PM MODULE PHASES PROTECTION The PM module detects the correct sequence of the 3 phases L1 L2 and L3 power supply...

Page 20: ...matically powered when the main switch is switched off The crankcase heaters are working properly if after some minutes the temperature of crankcase s compressor is about 10 C 15 C higher than ambient...

Page 21: ...nd ensure that the fan is stopped before opening the front panel The temperatures of heads and exhaust piping of the compressor are usually high Pay attention to the surfaces of the driver boards heat...

Page 22: ...Compressor Brand Bitzer Type D6 Scroll Number 1 2 Oil type quantity dm BVC32 2 7 BVC32 5 4 AC fan motor or Y for the model 0281 only for EC fan motor is available for EC data see the H version Type A...

Page 23: ...pressure high low MPa 4 2 2 7 Hydraulic circuit Water flow rate 2 L s 1 88 2 21 2 85 3 47 4 05 Available head pressure 2 kPa 75 7 73 4 64 5 73 4 64 7 Internal head loss 2 kPa 55 8 56 6 61 5 63 7 66 6...

Page 24: ...30 Y 87 8 25 7 3 42 104 3 27 2 3 83 35 84 7 29 2 2 90 100 6 29 4 3 42 40 79 8 30 7 2 60 95 5 32 2 2 97 45 75 1 34 4 2 18 89 4 35 0 2 56 13 4 COOLING PERFORMANCE DATA TABLES FOR HEAT PUMP UNITS AT DIFF...

Page 25: ...3 2 19 7 32 4 12 1 2 66 32 7 14 8 2 22 31 5 16 55 1 90 10 30 3 12 0 2 53 31 1 14 6 2 14 nd nd nd HWA1 0260 H 22 88 1 16 5 5 34 85 4 19 1 4 47 77 1 22 02 3 50 12 71 6 15 8 4 54 68 9 18 9 3 65 62 9 22 2...

Page 26: ...HWA1 A HWA1 H Air Water chillers and heat pumps with axial fans 26...

Page 27: ...apacity k W air temperature C HWA1 H 0140 HWA1 H 0147 HWA1 H 0260 HWA1 H 0272 HWA1 H 0285 10 0 12 0 14 0 16 0 18 0 20 0 22 0 24 0 26 0 28 0 30 0 32 0 34 0 36 0 20 25 30 35 40 45 input kW air temperatu...

Page 28: ...31 33 35 37 20 25 30 35 40 45 input kW air temperature C HWA1 H 0140 HWA1 H 0147 HWA1 H 0260 HWA1 H 0272 HWA1 H 0285 13 8 DECLARED TOTAL OUTPUT CAPACITIES AND POWER INPUT CURVES IN HEATING MODE TAKING...

Page 29: ...HWA1 A HWA1 H Chillers and Air Water heat pumps with axial fans 29...

Page 30: ...the hydronic circuit and the available head pressure of the plant gives us the minimum head of the circulator pump which should be installed 16 HEAT PUMPS AVAILABLE HEAD PRESSURE WITH INTEGRATED PUMP...

Page 31: ...w rate is referred to a T 5 C between the evaporator s inlet and outlet temperatures with nominal capacity at 7 C of the produced water The allowed maximum flow rate is corresponding to T 4 C Higher v...

Page 32: ...ure should not be lower than 25 C the lowest values which are not related to transitional or start up stages may cause system s failure with possible damages to compressor The maximum outlet water tem...

Page 33: ...at pump mode Operation s boundaries for chiller mode 0 5 10 15 20 25 30 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 Water temperature C Air ambient temperature C EC fan motor with pressure modulation AC...

Page 34: ...r flow rate correction factor is calculated in order to get the same temperature s difference that would be obtained without glycol The pressure drops correction factor takes into account the differen...

Page 35: ...rs and Air Water heat pumps with axial fans 35 22 DIMENSIONS Height H mm Max height of the packing mm 0140 0147 1985 2035 0260 0272 0285 2110 2170 Hydraulic connections Plant side 2 F Heat recoveries...

Page 36: ...a nufacturer reserves the right to modify the data whenever it is considered necessary Via S Giuseppe Lavoratore 24 37040 Arcole Verona Italy Tel 39 045 76 36 585 r a Fax 39 045 76 36 551 r a www maxa...

Reviews: