MAXA HWA1 0140 User& Installer'S Manual Download Page 4

HWA1-A & HWA1-H 

Air/Water chillers and heat pumps with axial fans

 

The manual of 

HWA1-A/HWA1-H

 units describes all the necessary information concerning the better use of the appliance under 

the  operator’s  safety  conditions  which  meets  the  requirements  listed  in  the  2006/42/CE  Equipment  Directive  and  following 
amendments. 

Note:

 The pictures in this manual are for explanation purpose only. They may be slightly different from the unit you purchased. 

The actual shape shall prevail. 

1

 

PURPOSES AND CONTENTS OF THE MANUAL 

This  manual  provides  the  basic  information  concerning  the  selection,  installation,  operation  and  maintenance  of  the 

HWA1-

A/HWA1-H 

units. It is addressed to the installer and the user of the appliance and it includes the necessary indications allowing 

the user to operate the unit efficiently, even without any previous specific knowledge of it. 
The manual describes the characteristics of the appliance at the time of its marketing; therefore, it must be considered adequate 
respecting the state of the art in terms of potentiality, ergonomics, safety and functionality. 
The company introduces also technological improvements and is not constrained to update the manuals for previous versions of 
appliances that could not be compatible. So make sure to use, for the installed unit, the supplied manual. 
It’s recommended that, the user must follow the instructions contained in this booklet, especially those concerning the safety and 
routine maintenance. 

1.1

 

CONSERVATION OF THE MANUAL 

The  manual  has  to  be  always  kept  by  the  user  for  future  reference.  It  has  to  be  stored  in  a  safe  place,  away  from  dusts  and 
moisture. It has to be available and accessible to all users who shall consult it any time they are in doubt on how to operate the 
equipment. 
The company reserves the right to modify its products and related manuals without necessarily updating previous versions  of the 
reference  material.  It  declines  also  any  responsibility  for  possible  inaccuracies  in  the  manual  if  due  to  printing  or  transcription 
errors.

 

The customer shall store any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this 
manual. 
The company is available to give any detailed information about this manual and to give information regarding the use and the 
maintenance of its own units. 

1.2

 

GRAPHIC SYMBOLS 

 

Indicates operations that can be dangerous for people and/or disrupts the correct operation of the equipment.

 

 

Indicates prohibited operations. 

 

Indicates important information which should be respected by the operator in order to guarantee the correct and 
safe operation of the equipment. 

2

 

SAFETY LAWS 

The 

HWA1-A/HWA1-H

 units have been designed in accordance with the following directives and harmonised standards: 

 

EU Directives 2014/68/UE, 2006/42/EC, 2014/35/UE, 2014/30/EU, 2011/65/EU, 2012/19/EU, 

 

UNI EN 378-1, 378-2, EN 12735-1, 

 

UNI EN ISO 12100, EN 60204-1, UNI EN ISO 13857, 

 

CEI EN 61000-6-3, IEC 61000-6-2. 

2.1

 

PERMITTED USES 

 

The company excludes any contractual and extra-contractual liabilities for damages caused to persons, animals or objects, by 
incorrect installation, setting and maintenance, improper use of the equipment, and the partial or superficial reading of the 
information described in this manual. 

 

These  units  have  been  designed  only  for  heating  and/or  cooling  of  water.  Any  other  use  not  expressly  authorized  by  the 
manufacturer is considered improper and therefore not allowed. 

 

The location of the plant, the hydraulic and electrical circuits must be established by the planting designer and must take into 
account both technical requirements as well as any applicable local laws and authorized specifications. 

 

The execution of all works must be performed by skilled and qualified personnel, competent in the existing rules in different 
countries. 
The execution of all works must be performed by skilled and qualified personnel and specialist competent in the existing rules 
in the country in which the appliance will be installed. 

Summary of Contents for HWA1 0140

Page 1: ...rie Series Serie S rie Emissione Edition Au sgabeIssue HWA1 A H 10 2017 0140 0285 Catalogo Catalogue Katalog Brochure Sostituisce Superseedes Ersetzt Remplace AIR WATER CHILLERS AND HEAT PUMPS WITH AX...

Page 2: ...3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 11 7 4 HYDRAULIC CONNECTIONS 12 7 5 HYDRAULIC CIRCUIT 13 7 5 1 Drainage system 13 7 5 2 Plant circuit loading 14 7 5 3 Plant drainage system 14 7 6 REFRIGER...

Page 3: ...AND POWER INPUT CURVES IN COOLING MODE FOR HEAT PUMP VERSIONS 27 13 8 DECLARED TOTAL OUTPUT CAPACITIES AND POWER INPUT CURVES IN HEATING MODE TAKING INTO ACCOUNT OF THE DEFROSTING CYCLES ACCORDING TO...

Page 4: ...reference material It declines also any responsibility for possible inaccuracies in the manual if due to printing or transcription errors The customer shall store any updated copy of the manual or par...

Page 5: ...e health and safety laws including 89 391 CEE 89 686 CEE 2009 104 CE 86 188 CEE 89 655 CEE and 77 576 CEE should be respected by every employer who must oblige the employees to respect them It points...

Page 6: ...AEL 8 h e 12 h TWA 1000 ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier...

Page 7: ...ible through the front panel of the unit which allows also the monitoring of the inner components 5 4 AIR SIDE HEAT EXCHANGER The air side heat exchanger for chiller units is made entirely of aluminiu...

Page 8: ...quired protection also for the operation with low evaporation pressures especially when the thermal protection on the power supply circuit is not sure High pressure transducer for condensation control...

Page 9: ...tput capacity Water piping configuration Hydronic configuration Integrated tank kit Antifreeze Kit Plant system management module Fan motor type Silencing Coil treatment 00 Cooling only 01 40 kW 09 Re...

Page 10: ...only versions they are standard on heat pump models 3 Crankcase heaters for cooling only versions are standard in heat pump versions GI 0 Unit without plant management module 1 The additional module...

Page 11: ...at high temperatures Be sure to let the unit to become cool before beginning any maintenance work Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious...

Page 12: ...the next water flow Loading group and discharge valve where it s required WARNING Make sure that when determining the pipe sizes you should exceed the maximum head loss on the plant side please refer...

Page 13: ...rage Models HWA1 A HWA1 H with 1 or 2 pumps for storage tank and free cooling A Plate heat exchanger B Flow switch C Service valve D Manometer for inlet pressure E Air vent valve F Safety valve G AC c...

Page 14: ...nit in order to make easy the operation it is recommended to install externally two draining valves on the water inlet and on the water outlet between the unit and the manual gate valves 7 6 REFRIGERA...

Page 15: ...ature ST Compressor inlet temperature SV Solenoide valve 7 6 3 Total heat recovery HWA1 A unit Refrigerant circuit C Compressor DT Compressor outlet temperature EV Electronic expansion valve FD Unidir...

Page 16: ...let temperature CL Tandem collector SV N C Solenoid valve FM Mechanical filter NR Non return valve SD Desuperheated gas sensor SS DHW inlet temp sensor 7 6 5 Refrigerant circuit of HWA1 H 0140 0147 un...

Page 17: ...lector SV N C Solenoid valve FM Mechanical filter NR Non return valve 4WV 4 way valve 7 6 7 Total heat recovery HWA1 H unit refrigerant circuit in cooling only C Compressor DT Compressor outlet temper...

Page 18: ...t with a dedicated line if you use a residual current circuit breaker choose a four pole one with a trigger threshold of 300 mA and delayed triggering super resistant characteristic K The machine must...

Page 19: ...3 N for neutral line PE earth conductor Available for HWA1 A cooling only versions 7 8 PM MODULE PHASES PROTECTION The PM module detects the correct sequence of the 3 phases L1 L2 and L3 power supply...

Page 20: ...matically powered when the main switch is switched off The crankcase heaters are working properly if after some minutes the temperature of crankcase s compressor is about 10 C 15 C higher than ambient...

Page 21: ...nd ensure that the fan is stopped before opening the front panel The temperatures of heads and exhaust piping of the compressor are usually high Pay attention to the surfaces of the driver boards heat...

Page 22: ...Compressor Brand Bitzer Type D6 Scroll Number 1 2 Oil type quantity dm BVC32 2 7 BVC32 5 4 AC fan motor or Y for the model 0281 only for EC fan motor is available for EC data see the H version Type A...

Page 23: ...pressure high low MPa 4 2 2 7 Hydraulic circuit Water flow rate 2 L s 1 88 2 21 2 85 3 47 4 05 Available head pressure 2 kPa 75 7 73 4 64 5 73 4 64 7 Internal head loss 2 kPa 55 8 56 6 61 5 63 7 66 6...

Page 24: ...30 Y 87 8 25 7 3 42 104 3 27 2 3 83 35 84 7 29 2 2 90 100 6 29 4 3 42 40 79 8 30 7 2 60 95 5 32 2 2 97 45 75 1 34 4 2 18 89 4 35 0 2 56 13 4 COOLING PERFORMANCE DATA TABLES FOR HEAT PUMP UNITS AT DIFF...

Page 25: ...3 2 19 7 32 4 12 1 2 66 32 7 14 8 2 22 31 5 16 55 1 90 10 30 3 12 0 2 53 31 1 14 6 2 14 nd nd nd HWA1 0260 H 22 88 1 16 5 5 34 85 4 19 1 4 47 77 1 22 02 3 50 12 71 6 15 8 4 54 68 9 18 9 3 65 62 9 22 2...

Page 26: ...HWA1 A HWA1 H Air Water chillers and heat pumps with axial fans 26...

Page 27: ...apacity k W air temperature C HWA1 H 0140 HWA1 H 0147 HWA1 H 0260 HWA1 H 0272 HWA1 H 0285 10 0 12 0 14 0 16 0 18 0 20 0 22 0 24 0 26 0 28 0 30 0 32 0 34 0 36 0 20 25 30 35 40 45 input kW air temperatu...

Page 28: ...31 33 35 37 20 25 30 35 40 45 input kW air temperature C HWA1 H 0140 HWA1 H 0147 HWA1 H 0260 HWA1 H 0272 HWA1 H 0285 13 8 DECLARED TOTAL OUTPUT CAPACITIES AND POWER INPUT CURVES IN HEATING MODE TAKING...

Page 29: ...HWA1 A HWA1 H Chillers and Air Water heat pumps with axial fans 29...

Page 30: ...the hydronic circuit and the available head pressure of the plant gives us the minimum head of the circulator pump which should be installed 16 HEAT PUMPS AVAILABLE HEAD PRESSURE WITH INTEGRATED PUMP...

Page 31: ...w rate is referred to a T 5 C between the evaporator s inlet and outlet temperatures with nominal capacity at 7 C of the produced water The allowed maximum flow rate is corresponding to T 4 C Higher v...

Page 32: ...ure should not be lower than 25 C the lowest values which are not related to transitional or start up stages may cause system s failure with possible damages to compressor The maximum outlet water tem...

Page 33: ...at pump mode Operation s boundaries for chiller mode 0 5 10 15 20 25 30 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 Water temperature C Air ambient temperature C EC fan motor with pressure modulation AC...

Page 34: ...r flow rate correction factor is calculated in order to get the same temperature s difference that would be obtained without glycol The pressure drops correction factor takes into account the differen...

Page 35: ...rs and Air Water heat pumps with axial fans 35 22 DIMENSIONS Height H mm Max height of the packing mm 0140 0147 1985 2035 0260 0272 0285 2110 2170 Hydraulic connections Plant side 2 F Heat recoveries...

Page 36: ...a nufacturer reserves the right to modify the data whenever it is considered necessary Via S Giuseppe Lavoratore 24 37040 Arcole Verona Italy Tel 39 045 76 36 585 r a Fax 39 045 76 36 551 r a www maxa...