EV Charger Connection Unit
V1.10
14 |
P a g e
Connect the incoming cable from the distribution board directly to the
4 pole isolator. The CPC should be connected to the terminal block
Connect the outgoing cable(s) to the MCB, RCBO or terminal blocks
depending on the unit being installed. The outgoing CPC should be
connected to the isolated earth bar except for the EVU-1-100TP.
THIS PRODUCT IS DESIGNED FOR AN ISOLATED
EARTHING ARRANGEMENT. CHECK BEFORE USING
SWA CABLE
On completion of installation the tightness of all electrical
connections should be checked before energising the unit.
See specifications for tightening torques.