1-4 Points to be careful about in handling
・
For your safety connect the ground terminal of the chassis to EARTH securely
・
Use thicker (5SQ or thicker) and short wire for chassis grounding or load grounding, and
ground at one point of the ground.
・
Connect the shield wire of the output cable to the chassis side of the load.
(It will protect power supply or prohibit electrical shock from discharge at load)
・
DON’T TOUCH the load immediately after turning the output OFF. Before touching the
load, make sure that the Power ON/OFF switch of the unit is turned off and output
voltage is zero with power supply’s voltage monitor or another HV voltmeter.
How to GROUND
1-5 Troubleshooting
・In case there is no output voltage
1.Check if the proper input voltage is supplied to the power supply.
・
Power supply input voltage, 100-240V AC +/-10%, 50/60Hz single phase
Output cable
Ground terminal
Ground
EP
Load frame
load
1 Introduction