2

WELCOME TO SINGLE PUMP CONTROL

Your  Single  Pump  Controller  reflects  the  superior  quality  and  attention  to  detail  in  design,  engineering  and

manufacturing that has distinguished MATelec Products for decades. The controller incorporates the very latest in 

micro-processor technology, ensuring you, the owner/operator, of many years of functional, reliable and ‘user friendly’ 

operation.

Please read this manual prior to installation and operation of the controller.

• 

Prior to Installation, ensure power supply is isolated.

• 

Power supply must be Circuit Breaker Protected. (Qualified Electrician to determine appropriate amp rating.)

• 

Electrical connection to the panel must be carried out in accordance with ‘Connection Instructions’, see page 3.

• 

Addition or modifications to the control panel are not permitted and will void warranty.

• 

The controller is not intended for use by children or infirm persons without supervision.

• 

Repairs to the Controller must only be carried out by a suitably qualified Electrician

SAFETY

WARNING: All electrical connections must be carried out by a suitably qualified and

registered electrician

SAFETY 

  2 CIRCUIT 

DIAGRAM 7

INSTALLATION   

AT A GLANCE   

8

Mounting   

 

 

Indicators

Connection  

 

 

Push Buttons

GETTING STARTED 

4

Operations
Features

CONTENTS

THIS CONTROLLER MUST BE INSTALLED OUTSIDE OF A HAZARDOUS AREA 

AS DESCRIBED IN AS/NZS 3000 SEC 7.7

Summary of Contents for FPC-15007-INT

Page 1: ...MAIN ISOLATOR DOC FPC 15007 INT VER 1 0 P U M P C O N T R O L OWNER S OPERATION MANUAL Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 INT...

Page 2: ...ician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 Addition or modifications to the control panel ar...

Page 3: ...H CONNECTED TO INPUT 1 415Vac MAINS POWER SUPPLY PUMP 415Vac BRIDGE IF NOT REQUIRED SUPPLY 415Vac Connections E P1 P2 P3 N E A1 A2 A3 WORKING LEVEL FLOAT COMMON N O CLOSE ON RISE BLUE NOT REQUIRED HIG...

Page 4: ...ternates after 6 hours continuous running 4 Off Anti seize Timer disabled On Anti seize Timer 6 seconds every 7 days enabled 5 Off When placed in Manual Mode pump remains in Manual Mode On When placed...

Page 5: ...for Sewerage applications High Level Alarm delay in this mode is 5 minutes Audible and Visual Alarm Test Setting this DIP Switch to On will cause the High level Alarm to remain active until the contro...

Page 6: ...0Vac Contactor 1 L1 T1 L2 T2 L3 T3 Contactor 3P C1 240V 240N 12V 0V Transformer 12Vac T1 12 Vac 0Vac 95 96 NC Contact TOL 1 Strobe Light Buzzer 415VAC Pump P1 Thermal Overload TOL1 1 2 3 4 5 6 ON Work...

Page 7: ...LARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime lo...