background image

3

FRONT

SIDE VIEW

Top

Bottom

Top

Bottom

WIRING CONNECTION DETAIL

FPC-15007

DOC:  FPC 15007-INT
VER 1.0

WARNING: HIGH VOLTAGE

ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT

BY A SUITABLY QUALIFIED ELECTRICIAN

ACCESS BY AUTHORISED PERSONNEL ONLY

2 FLOAT SWITCH SYSTEM

3 FLOAT SWITCH SYSTEM

4 FLOAT SWITCH SYSTEM

INDICATOR LIGHTS GUIDE

NO FL

O

AT SWIT

CH

CONNEC

TED 

TO INPUT 2

START

LEVEL

COMMON

N/O  CL

OSE  ON  RISE

BL

UE NO

T REQUIRED

STOP

LEVEL

COMMON

N/O  CL

OSE  ON  RISE

BL

UE NO

T REQUIRED

COMMON

N/O  CL

OSE  ON  RISE

HIGH

LEVEL

BL

UE

 N

O

T REQUIR

ED

415Vac

MAINS POWER

SUPPLY

PUMP 415Vac

BRIDGE

IF NOT

REQUIRED

BRIDGING 

WIRE TO 

REMAIN IN

LOW LEVEL

BRIDGING 

WIRE TO 

REMAIN IN

LOW LEVEL

STOP

START

LEVEL

COMMON

N/O  CL

OSE  ON  RISE

BL

UE NO

T REQUIRED

COMMON

N/O  CL

OSE  ON  RISE

STAND BY

HIGH

LEVEL

BL

UE

 N

O

T REQUIR

ED

415Vac

MAINS POWER

SUPPLY

PUMP 415Vac

BRIDGE

IF NOT

REQUIRED

NO FL

O

AT SWIT

CH

CONNEC

TED 

TO INPUT 1

SUPPLY

415Vac Connections

E P1 P2

P3

N

E A1 A2

A3

Input 1

Low

Level

Input 2

Stop

Level

Input 3

Start

Level

Input 4

High

Level

INPUT SWITCHES

T1 T2

THERMAL

12Vdc Connections

COMMON

FAULT

BMS

VOLT/FREE

PUMP

SUPPLY

415Vac Connections

E P1 P2

P3

N

E A1 A2

A3

Input 1

Low

Level

Input 2

Stop

Level

Input 3

Start

Level

Input 4

High

Level

INPUT SWITCHES

T1 T2

THERMAL

12Vdc Connections

COMMON

FAULT

BMS

VOLT/FREE

PUMP

ON STEADY

A pump fault/overload has occured

FLASHING

A prime loss fault has occured

MOMENTARY PRESS

To mute audible buzzer

PRESS FOR 3 SECS

To reset alarms and faults

PRESS CONTINUOUS

To test indicator lights,

strobe and siren

ON STEADY

Pump is switched on to run

ON STEADY

A high level alarm has been present for the preset time

FLASHING

A low level alarm is present

MUTE/

RESET

PUMP ON

LEVEL ALARM

FAULT

NO FL

O

AT SWIT

CH

CONNEC

TED 

TO INPUT 1

415Vac

MAINS POWER

SUPPLY

PUMP 415Vac

BRIDGE

IF NOT

REQUIRED

SUPPLY

415Vac Connections

E P1 P2

P3

N

E A1 A2

A3

WORKING

LEVEL FLOAT

COMMON

N/O  CL

OSE  ON  RISE

BL

UE NO

T REQUIRED

HIGH

FLOAT LEVEL

COMMON

N/O  CL

OSE  ON  RISE

BL

UE NO

T REQUIRED

Working

Level

Float

Switch

INTRINSICALLY SAFE

BARRIER RELAY

CONNECTIONS

T1 T2

THERMAL

12Vdc

PUMP

COMMON

FAULT

BMS

VOLT/FREE

REMOVE

BRIDGE

WIRE TO USE 

LOW LEVEL

FLOAT

High

Level

Float

Switch

24Vdc

Mounting

Frame/

Wall

MAIN ISOLATOR

INSTALLATION

CONNECTION

MOUNTING

1. Controller enclosure must be   

    mounted in a vertical position.

2. Ensure mounting method does 

    not compromise enclosure

    weather proof rating.

3. Ensure access to main isolator is 

    not restricted.

4. Ensure cables/conduits entering 

    the panel have mechanical

    protection and that the

    penetrations are sealed and do   

    not compromise the weather 

    proof rating of the enclosure.

Note: 

Controller  must  be  earthed  and  all  electrical  connections  must  be  carried  out  by  a  suitably  qualified

Electrician. For Single Working Level Float Switch Applications, connect to “Start (Input 3)” terminals only, and NO 

bridge wire is required in “Stop (Input 2)” terminals.

Summary of Contents for FPC-15007-INT

Page 1: ...MAIN ISOLATOR DOC FPC 15007 INT VER 1 0 P U M P C O N T R O L OWNER S OPERATION MANUAL Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 INT...

Page 2: ...ician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 Addition or modifications to the control panel ar...

Page 3: ...H CONNECTED TO INPUT 1 415Vac MAINS POWER SUPPLY PUMP 415Vac BRIDGE IF NOT REQUIRED SUPPLY 415Vac Connections E P1 P2 P3 N E A1 A2 A3 WORKING LEVEL FLOAT COMMON N O CLOSE ON RISE BLUE NOT REQUIRED HIG...

Page 4: ...ternates after 6 hours continuous running 4 Off Anti seize Timer disabled On Anti seize Timer 6 seconds every 7 days enabled 5 Off When placed in Manual Mode pump remains in Manual Mode On When placed...

Page 5: ...for Sewerage applications High Level Alarm delay in this mode is 5 minutes Audible and Visual Alarm Test Setting this DIP Switch to On will cause the High level Alarm to remain active until the contro...

Page 6: ...0Vac Contactor 1 L1 T1 L2 T2 L3 T3 Contactor 3P C1 240V 240N 12V 0V Transformer 12Vac T1 12 Vac 0Vac 95 96 NC Contact TOL 1 Strobe Light Buzzer 415VAC Pump P1 Thermal Overload TOL1 1 2 3 4 5 6 ON Work...

Page 7: ...LARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime lo...

Reviews: