3
FRONT
SIDE VIEW
Top
Bottom
Top
Bottom
WIRING CONNECTION DETAIL
FPC-15007
DOC: FPC 15007-INT
VER 1.0
WARNING: HIGH VOLTAGE
ALL ELECTRICAL CONNECTIONS MUST BE CARRIED OUT
BY A SUITABLY QUALIFIED ELECTRICIAN
ACCESS BY AUTHORISED PERSONNEL ONLY
2 FLOAT SWITCH SYSTEM
3 FLOAT SWITCH SYSTEM
4 FLOAT SWITCH SYSTEM
INDICATOR LIGHTS GUIDE
NO FL
O
AT SWIT
CH
CONNEC
TED
TO INPUT 2
START
LEVEL
COMMON
N/O CL
OSE ON RISE
BL
UE NO
T REQUIRED
STOP
LEVEL
COMMON
N/O CL
OSE ON RISE
BL
UE NO
T REQUIRED
COMMON
N/O CL
OSE ON RISE
HIGH
LEVEL
BL
UE
N
O
T REQUIR
ED
415Vac
MAINS POWER
SUPPLY
PUMP 415Vac
BRIDGE
IF NOT
REQUIRED
BRIDGING
WIRE TO
REMAIN IN
LOW LEVEL
BRIDGING
WIRE TO
REMAIN IN
LOW LEVEL
STOP
START
LEVEL
COMMON
N/O CL
OSE ON RISE
BL
UE NO
T REQUIRED
COMMON
N/O CL
OSE ON RISE
STAND BY
HIGH
LEVEL
BL
UE
N
O
T REQUIR
ED
415Vac
MAINS POWER
SUPPLY
PUMP 415Vac
BRIDGE
IF NOT
REQUIRED
NO FL
O
AT SWIT
CH
CONNEC
TED
TO INPUT 1
SUPPLY
415Vac Connections
E P1 P2
P3
N
E A1 A2
A3
Input 1
Low
Level
Input 2
Stop
Level
Input 3
Start
Level
Input 4
High
Level
INPUT SWITCHES
T1 T2
THERMAL
12Vdc Connections
COMMON
FAULT
BMS
VOLT/FREE
PUMP
SUPPLY
415Vac Connections
E P1 P2
P3
N
E A1 A2
A3
Input 1
Low
Level
Input 2
Stop
Level
Input 3
Start
Level
Input 4
High
Level
INPUT SWITCHES
T1 T2
THERMAL
12Vdc Connections
COMMON
FAULT
BMS
VOLT/FREE
PUMP
ON STEADY
A pump fault/overload has occured
FLASHING
A prime loss fault has occured
MOMENTARY PRESS
To mute audible buzzer
PRESS FOR 3 SECS
To reset alarms and faults
PRESS CONTINUOUS
To test indicator lights,
strobe and siren
ON STEADY
Pump is switched on to run
ON STEADY
A high level alarm has been present for the preset time
FLASHING
A low level alarm is present
MUTE/
RESET
PUMP ON
LEVEL ALARM
FAULT
NO FL
O
AT SWIT
CH
CONNEC
TED
TO INPUT 1
415Vac
MAINS POWER
SUPPLY
PUMP 415Vac
BRIDGE
IF NOT
REQUIRED
SUPPLY
415Vac Connections
E P1 P2
P3
N
E A1 A2
A3
WORKING
LEVEL FLOAT
COMMON
N/O CL
OSE ON RISE
BL
UE NO
T REQUIRED
HIGH
FLOAT LEVEL
COMMON
N/O CL
OSE ON RISE
BL
UE NO
T REQUIRED
Working
Level
Float
Switch
INTRINSICALLY SAFE
BARRIER RELAY
CONNECTIONS
T1 T2
THERMAL
12Vdc
PUMP
COMMON
FAULT
BMS
VOLT/FREE
REMOVE
BRIDGE
WIRE TO USE
LOW LEVEL
FLOAT
High
Level
Float
Switch
24Vdc
Mounting
Frame/
Wall
MAIN ISOLATOR
INSTALLATION
CONNECTION
MOUNTING
1. Controller enclosure must be
mounted in a vertical position.
2. Ensure mounting method does
not compromise enclosure
weather proof rating.
3. Ensure access to main isolator is
not restricted.
4. Ensure cables/conduits entering
the panel have mechanical
protection and that the
penetrations are sealed and do
not compromise the weather
proof rating of the enclosure.
Note:
Controller must be earthed and all electrical connections must be carried out by a suitably qualified
Electrician. For Single Working Level Float Switch Applications, connect to “Start (Input 3)” terminals only, and NO
bridge wire is required in “Stop (Input 2)” terminals.