EN / SCM20 & SCM40 PWM User’s Manual  

 

 

3.4 

SPECIFICATIONS OF THE PV ARRAY 

 

WARNING 

When the PV array is exposed to light, it 
supplies a DC voltage to the Solar 
Chargemaster which can be dangerous to touch. 
For this reason, use of an external DC-switch is 
strongly recommended. Alternatively, before 
attempting any maintenance or cleaning the PV-
array should be protected from light exposure, 
e.g. by covering the PV modules.  

 

CAUTION! 

Do not connect Solar Chargemasters in parallel 
on the side of the PV array. 

 
The Solar ChargeMaster is appropriate for nominal 12V 
and 24V solar systems. The table shows the number of 
cells required for the nominal voltages.  
 

Battery voltage U

NOM

 = 12V 

Model 

Panel type 

Max input 
voltage 

Max input 
current 

SCM20 PWM 

36 cells 

28V 

20A 

SCM40 PWM 

36 cells 

28V 

40A 

 
 

Battery voltage U

NOM

 = 24V 

Model 

Panel type 

Max input 
voltage 

Max input 
current 

SCM20 PWM 

72 cells 

55V 

20A 

SCM40 PWM 

72 cells 

55V 

40A 

 

CAUTION! 

Never connect voltages higher than specified to 
the PV-input, as this will cause permanent 
damage to the Solar Chargemaster. 

 
Configuration examples for PV-arrays consisting of 
monocrystalline or polycrystalline PV-modules:  
 

3.5 

CONNECTION OF LOADS 

Depending on the energy system in which the Solar 
Chargemaster is used, there are two options to connect the 
electrical load to the Solar Chargemaster: 

  To the Load output on the Solar Chargemaster, or 

  Directly to the battery. 

 

3.5.1 

Load connected to the Load output 

See Figure 5 for a typical installation diagram. The Load 
output is provided with a protection circuit that switches off 
the connected load automatically in case of overload or if 
the battery voltage is too low. This kind of installation is 
typically used when the PV-modules are the only source of 
electrical power to charge the battery. 
 

3.5.2 

Load connected to the battery 

If the maximum load will exceed 20 Amps (SCM20 PWM), 
40 Amps (SCM40 PWM) or if the battery will also be 
charged by other energy sources, such as a battery 
charger or an alternator, the electrical load shall be 
connected to the battery directly. See Figure 6 for a typical 
installation diagram. In this situation the battery is no longer 
protected against too low battery voltages. Installation of 
additional undervoltage protection circuits may be 
necessary. See section 5.3 for ordering information 
 

3.6 

THINGS YOU NEED 

Make sure you have all the parts you need to install the 
Solar Chargemaster: 
 

  Solar Chargemaster (included); 

  Battery temperature sensor with cable and plug 

(optional, not included; see section 5.3 for ordering 
information); 

  DC cables to connect the Solar Chargemaster; see 

section 3.3 for specifications; 

  DC-fuse holder with a DC-fuse, to be integrated in the 

positive DC-cable to the battery; see section 3.3; 

  Screws / bolts (Ø 4mm max.) (with plugs) to mount the 

Solar Chargemaster to a surface; 

 Batteries; 

 

  Appropriate and reliable cable terminals, strain reliefs, 

battery terminals and boot lace ferrules. 

 
We recommend as a minimum tool kit:  

  Phillips screw driver nr.2 or flat blade screw driver 5 

mm to fix the DC-cables; 

  Tools to fix the screws / bolts with plugs to mount the 

Solar Chargemaster to a surface; 

 
 

 

Summary of Contents for SCM20 PWM

Page 1: ...SOLAR CHARGE MASTER SCM20 PWM SCM40 PWM PWM CONTROLLED PV BATTERY CHARGER EN USER S AND INSTALLATION MANUAL NL DE FR ES https www mastervolt com products solar charge controllers 10000014327 02...

Page 2: ...r s Manual OVERVIEW 1 MENU button 2 OK button 3 LCD display 4 Casing 5 Heatsink 6 PV input 7 Battery connection 8 Load output 9 Temperature sensor jack 10 Identification label rear side Figure 1 Overv...

Page 3: ...Load mode 8 3 INSTALLATION 9 3 1 Unpacking 9 3 2 Environment 9 3 3 Wiring and fuses 9 3 4 Specifications of the PV array 10 3 5 Connection of loads 10 3 5 1 Load connected to the Load output 10 3 5 2...

Page 4: ...ter further in this manual 1 3 USE OF PICTOGRAMS Safety instructions and warnings are marked in this manual and on the product by the following pictograms A procedure circumstance etc which deserves e...

Page 5: ...base at least once a year Defects such as loose connections burnt wiring etc must be corrected immediately If necessary use a soft clean cloth to clean the casing of the Solar Chargemaster Do not use...

Page 6: ...rolling through a selection of screens Manual Scrolling Mode Press OK shortly to scroll through all screens manually Static Display Mode Hold MENU and OK pressed simultaneously for 1 second to lock th...

Page 7: ...serious damage to your batteries and or the connected load Adjustments of settings may be undertaken by authorised personnel only If your Solar Chargemaster is not new you have to take into account th...

Page 8: ...6V 12 6 V 25 2V Dynamic Low voltage disconnect function Indication Disconnect threshold Reconnect threshold at full load at no load 11 0V 22 0V 11 6V 23 2V 12 4 V 24 8V 11 1V 22 2V 11 6V 23 2V 12 5 V...

Page 9: ...ly complies with all applicable EMC limits it may still cause harmful interference to radio communication equipment If such interference appears it is recommended to increase the separation between th...

Page 10: ...pical installation diagram The Load output is provided with a protection circuit that switches off the connected load automatically in case of overload or if the battery voltage is too low This kind o...

Page 11: ...trate the general placement of the Solar Chargemaster in a circuit They are not meant to provide detailed wiring instructions for any particular electrical installation Battery temperature sensor BATT...

Page 12: ...ential If grounding is required always do this on the negative wires Use one grounding point only NOTE If the battery temperature remains within 15 25 C connection of the battery temperature sensor is...

Page 13: ...er and the load 5 Check with a suitable voltage meter whether the Battery connection and the LOAD output of the Solar Chargemaster are voltage free 6 Disconnect the negative cable to the PV array from...

Page 14: ...harge battery voltage is too high 15 5 31 0V Check batteries Check other charging systems Use the battery temperature sensor Over temperature Check cooling of the Solar Chargemaster No battery chargin...

Page 15: ...lk Absorption Float Battery types Flooded AGM Gel LOAD OUTPUT UNOM 12V UNOM 24V UNOM 12V UNOM 24V Maximum output current 20A 20A 40A 40A Under voltage disconnect adjustable 10 8 11 8V 21 6 23 6V 10 8...

Page 16: ...ous 150A peak load 77020200 DC Distribution 500 The Mastervolt DC Distribution offers fused DC connections to install up to four different devices Mastervolt can offer a wide range of products for you...

Reviews: